CASE STUDY 1
Using life-cycle assessments to drive innovation in data centre cooling –
Microsoft and Schneider Electric.126
PRIORITY ACTIONS: WATER USE ELECTRICITY USE
Microsoft conducted an in-depth life-cycle assessment
of data centre cooling technologies that demonstrated how
shifting from air-cooling to advanced liquid-cooling methods
(direct-to-chip and immersion cooling) can substantially
reduce nature impacts.
The study identified reductions in GHG emissions (15-21%),
energy demand (15-20%) and blue water consumption
(31-48%) when moving from air-cooling to liquid-cooling
in a 100% grid electricity scenario.
In a 100% renewable energy scenario, the study found similar
reductions in GHG emissions (13-20%) and energy demand
(15-20%), but a considerably greater reduction in blue water
consumption of 50-82%, when moving from air-cooling to
liquid-cooling. When modelling a fully renewable energy scenario,
a 10 MW data centre could see annual savings of $1.0-1.4
million in energy costs and $220,000-365,000 in water costs.
While not directly experienced by the data centre, this would
also save an additional $3.4-5.6 million in water costs from
energy generation.
When comparing capital considerations between air-cooling
versus liquid-cooling, Schneider Electric published a white
paper that calculated capex costs are almost identical for 10
kW racks, at $7.02 for air-cooling and $6.98 for liquid-cooling.
As rack density increases, liquid-cooling sees additional cost
savings as it enables more compact racks without requiring
equivalent increases in equipment. Microsoft’s cooling
assessment, supported by Schneider Electric’s capital review,
highlights that liquid-cooling is a feasible way to reduce
nature impacts and reduce costs for data centre operators.
Shift from air-cooling to liquid-cooling reduces data centre impacts and costs
GHG emissions Energy demand Blue water consumptionReductions in
Cost savings/year for 1 0 MW data centre100% grid electricity scenario
100% renewables scenario15-21% 15-20% 31-48%
13-20%
$1.0 – 1.4 million $220,000 – 365,00015-20% 50-82%