Data centres – key metrics for existing and emerging hubs232TABLE A3Data centre archetypes
Data centre archetypes, illustrated in Figure 12, were developed based
on 15 global data centre hubs, made up of the 10 largest data centre hubs
based on power load and five emerging hubs, as shown in Table A3 below.
Location# of
data
centersIT load
(MW)2023-2024 Cooling
degree days above
15.5 C (C)Water
stress
level Renewable
energy
share (%)Daily direct
normal irradiation
(kWh/sq m)Wind power
density
(W/sq m)Geothermal
favourability
(scale 1-5)
Virginia 537 4,700 1387 40-80% 9 4.3 294 0.9
Beijing 48 1,900 1667 >80% 31 3.2 93 2.8
Oregon 131 1,600 814 <10% 60 3.7 262 3.3
Phoenix 109 1,500 3920 >80% 16 7.4 44 2.6
Shanghai 51 1,400 2152 >80% 31 2.2 132 3.2
Dallas 156 1,300 2668 10-20% 29 5.0 168 1.7
Columbus 108 1,200 1174 20-40% 5 3.8 189 0.9
Atlanta 96 1,100 1917 40-80% 6 4.5 183 0.9
Tokyo 84 1,000 1783 20-40% 23 3.5 177 1
London 137 1,000 285 40-80% 47 2.4 258 1
Brazil 162 880 2093 20-40% 89 3.7 73 1
Sydney 82 700 1348 40-80% 34 4.9 248 3.2
Mumbai 67 500 4852 10-20% 20 3.9 129 1
UAE 32 240 5340 >80% 8 5.0 133 1
Johannesburg 31 230 2115 >80% 9 5.9 132 1
Metrics were applied against the framework shown
in Table A4 below to determine ratings and identify
the archetype. The different levels within the
framework were designed based on global averages
and industry analysis and validated through review
and consultation with industry experts. While these archetypes can be used to help inform
design choices for cooling technology, there are
additional nuances and specifics, including local
regulatory requirements, that must be accounted
for that are not included in this framework.
Archetype metrics and value ranges for each rating TABLE A4
Metric Low Medium High Very high
2-year cooling degree days above 15.5 C (C) <730 730-1,459.99 1,460-2,190 >2190
Water stress level (%) <20 20-39.99 40-80 >80
Region renewable energy share (%) <10 10-19.99 20-30 >30
Potential for
renewable energyDaily direct normal
irradiation (kWh/sq m)<2.6 2.6-2.99 3-4 >4
Wind power
density (W/sq m)<100 100-199 200-299 >300
Geothermal
favourability (scale 1-5)<1.01 1.01-1.99 2-3.49 3.5-5