FM-200© Component Description P 


Pressure Operated Switch 


FEATURES 
¢ For Use with UL Listed, ULC Listed and 
FM Approved Systems 


P/N:  81-486536-000 


WIRING 
SCREW 
TERMINALS 


<—#§| 4.00" ——> 





FRONT VIEW 
COVER REMOVED 






SWITCH 3PDT 


COVER 


=ee === = ---4 8 o---- 


GASKET 


PIPING 


SIDE SECTION 


NOTES: 

e The switch may be mounted in any position; how- 
ever, the preferred installation is upright, as shown. 

e Any load connection to the switch must not exceed 
the switch rating, and shall utilize a suitable protec- 
tion device (i.e., circuit breaker, fuse). 


FM-200 is a registered trademark of the Great Lakes Chemical Corporation. 


Oo. oo 








oa BOX 3 EACH SIDE 
1/2” CONDUIT 
KNOCKOUTS 


‘2” NPT FEMALE, 
CONNECT TO SYSTEM 


4 


BA 





Kidde Fire Systems 


A UTC Fire & Security Company 


~~ 


Effective: September 2010 
K-90-5180 


e See Kidde® Manual 90-FM200M-0271 for 
USCG Approval 


STEM SHOWN IN SET POSITION- 
PULL UP ON STEM TO MANUALLY 
OPERATE SWITCH 










OPERATED 
SET [OF 








0.375" 





8 COVER SCREWS 


PRESSURE OPERATED SWITCH 
3P.D.T. 
TO RESET 
PUSH STEM TO SET POSITION 
10 AMP.—250 V.AC 





15 AMP.— 125 V.AC 







PT. NO. 486536 


TO RESET 
PUSH STEM TO SET POSITION 


15 AMP 125 VAC 


T 10 AMP 250 VAC 
L oo E 3/4 HP 1-2-3 PH 125-480 VAC 
Tr 
I 
LIN 1/2” SUPPLY PIPE WITH UNION 
FRONT VIEW 
OPERATED 
—— SET 
NC NC NC 
2 \ \ C 
ele ee Leese 3 
Pg 
© © © 
NO NO NO 


JILL 


PRESSURE INLET 
WIRING DIAGRAM 


e Contact Ratings (3 PDT): 
— 15 Amp @125 Vac 
— 10Amp @ 250 Vac 
3/4 HP @ 250 Vac 
1,2 or 3 Phase 


Kidde Fire Systems 


This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes 
no responsibility for the product's suitability for a particular application. The product must be 


properly applied to work correctly. 
If you need more information on this product, or if you have a particular problem or question, 
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. 





K-90-5180 Rev AC © 2010 Kidde-Fenwal Inc. Printed in USA 


A UTC Fire & Security Company 
400 Main Street 

Ashland, MA 01721 

Ph: 508.881.2000 

Fax: 508.881.8920 
www.kiddefiresystems.com