SIEMENS 


FM 458-1 DP 
Function Blocks 


Manual 


Edition 12.2004 


Contents, Foreword 


Input/output blocks 


Communication blocks 








Service-/diagnostic blocks 





SIMOLINK blocks 





Closed-loop control blocks 





= i 
O 
= 
ö 
z 
fo] 
fa) 
A 
ø 


ndex 


Safety guidelines 


/\ DANGER 
/N WARNING 
/N CAUTION 
CAUTION 
NOTICE 


Correct usage 


Trademarks 


This Manual contains notices which you should observe to ensure your own personal 
safety, as well as to protect the product and connected equipment. These notices are 
highlighted in the Manual by a warning triangle and are marked as follows according to 
the level of danger: 


indicates an imminently hazardous situation which, if not avoided, will result in death or 
serious injury. 


indicates a potentially hazardous situation which, if not avoided, could result in death or 
serious injury. 


used with the safety alert symbol indicates a potentially hazardous situation which, if not 
avoided, may result in minor or moderate injury. 


used without safety alert symbol indicates a potentially hazardous situation which, if not 
avoided, may result in property damage. 


used without the safety alert symbol indicates a potential situation which, if not avoided, 
may result in an undesireable result or state. 


Note the following: 


This device and its components may only be used for the applications described in the 
catalog or the technical description, and only in connection with devices or components 
from other manufacturers which have been approved or recommended by Siemens. 


SIMATIC® and SIMADYN DØ are registered trademarks of Siemens AG. 


Third parties using for their own purposes any other names in this document which refer 
to trademarks might infringe upon the rights of the trademark owners. 


Copyright © SIEMENS AG 2004 All rights reserved 


The reproduction, transmission or use of this document or its 
contents is not permitted without express written authority. 
Offenders will be liable for damages. All rights, including rights 
created by patent grant or registration of a utility model or design, 
are reserved. 


Siemens AG 

A&D 

Frauenauracher Straße 80 
91056 Erlangen 


Siemens Aktiengesellschaft 


Disclaimer of liability 


We have checked the contents of this manual for agreement with 
the hardware and software described. Since deviations cannot be 
precluded entirely, we cannot guarantee full agreement. 
However, the data in this manual are reviewed regularly and any 
necessary corrections included in subsequent editions. 
Suggestions for improvement are welcomed. 


© Siemens AG 2004 
Technical data subject to change. 


Editions 


NOTE 


Overview 
(chapter editions) 


FM 458-1 DP 


Manual 


Function Blocks 


Edition 12.2004 


Please note that the current edition of this documentation contains 
different editions of the individual chapters. The following overview tells 


you when a chapter was revised the last time. 


Chapter 
Foreword 
Input/output blocks 
Communication blocks 
Logic blocks 
Service-/diagnostic blocks 
SIMOLINK drive coupling 


Closed-loop control blocks 


Function Blocks - FM 458-1 DP 


Edition 12.2004 


Edition 12.2004 
Edition 12.2004 
Edition 12.2004 





Foreword 


Purpose of this 
Manual 


Basic knowledge 
required 


Validity of the 
Manual 


Additional support 


Training Center 


NOTE 


This Manual explains the principle use and functions of the STEP 7 
automation software with the main focus on the appropriate technological 
and drive control components T400, FM 458-1 DP, SIMADYN D, 
SIMATIC TDC or D7-SYS. 


TDC: Technology and Drives Control 


This Manual addresses programmers and commissioning engineers. 
General knowhow regarding automation technology is required in order to 
understand the contents of the Manual 


This Manual is valid for SIMATIC D7-SYS Version 6.2. 


If you have questions relating to the use of the products described in the 
Manual, which cannot be answered here, then please contact your local 
Siemens office. You can also call the Hotline: 


e Tel.: +49 (180) 5050-222 
e Fax: +49 (180) 5050-223 
e e-mail: [email protected] 


Appropriate training courses are available in order to make it easier to get 
to know the SIMADYN D automation system. Please contact the central 
Training Center in D-Erlangen (1&S IS INA TC): 


e Tel.: +49 (9131) 7-27689, -27972 


e Fax: +49 (9131) 7-28172 


e Internet: |www.siemens.de/sibrain 


e Intranet: | http://info-tc.erlm.siemens.de/ 


This user part of the Manual does not include any detailed 
information/instructions with individual descriptions, but is only intended 
to provide a basic procedure. More detailed information on the dialog 
boxes in the software and how they are handled is provided in the 
appropriate online help. 


Function Blocks - FM 458-1 DP iii 


Edition 12.2004 


Foreword 


Information 


This manual is part of the overall documentation for the technological and 
drive control components T400, FM 458, SIMADYN D, SIMATIC TDC 


overview and SIMATIC D7-SYS: 


System and 
communications 
configuring D7-SYS 


STEP 7 option packages 
for D7-SYS 


Hardware 


Function blocks 





The first project in a few steps 


This Section provides an extremely simple entry into the methodology when 
assembling and programming the SIMATIC TDC/SIMADYN D control 
system. It is especially conceived for first-time users of a control system. 


System software 
This Section provides basic know-how about the structure of the operating 
system and an application program of a CPU. It should be used to obtain an 


overview of the programming methodology, and basis for configuring user 
programs. 


Communications configuring 


This section provides you with basic know-how about the communication 
possibilities and how you configure links to the communication partners. 

Changeover from STRUC V4.x to D7-SYS 

Essential features are included in this section, which have changed over 
STRUC V4.x with the introduction of SIMATIC D7-SYS. 

Basis software 


This section explains the essential use and the functions of the STEP 7 
automation software. For first users, it provides an overview on configuring, 
programming and commissioning a station. 


When working with the basis software, you can access the online help which 
provides you with support when it comes to detailed questions on using the 
software. 

CFC 


The CFC language (Continuous Function Chart) allows you to graphically 
interconnect blocks. 

When working with the particular software, you can also use the online help 
which can answer detailed questions regarding the use of the 
editors/compiler. 

SFC 


Configuring sequence controls using SFC (Sequential Function Chart) of 
SIMATIC S7. 


In the SFC editor, you generate a sequence chart using graphic resources. 
The SFC elements of the chart are then positioned according to specific 
rules. 


The complete hardware spectrum is described as reference in this Manuals. 


These Reference Manuals provide you with an overview of selected function 
blocks for the associated technological and drive control components T400, 
FM 458-1 DP, SIMADYN D and SIMATIC TDC. 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


Foreword 


Guide Ås first time user, we recommend that this Manual is used as follows: 
e Please read the first section on using the software in order to get to 
know some of the terminology and basic procedure. 


e Then use the particular sections of the Manual if you wish to carry-out 
certain processing steps (e.g. loading programs). 


If you have already executed a small project, and have gained some 
experience, then you can read individual sections of the Manual in order 
to get up to speed about a specific subject. 


A&D Technical Can be accessed globally at any time of the day: 
Support 





World-wide (Nurnberg) 
Technical Support 


Local time: 0:00 to 24:00 / 365 days 
Phone: +49 (180) 5050-222 


Fax: +49 (180) 5050-22: 


GMT: +1:00 


Europe / Africa (Nurnberg) United States (Johnson City) Asia / Australia (Peking) 


Authorization Technical Support and Technical Support and 
Authorization Authorization 


Local time: Mo.-Fr. 8:00 to 17:00 Local time: Mo.-Fr. 8:00 to 17:00 Local time: Mo.-Fr. 8:00 to 17:00 
Phone: +49 (180) 5050-222 Phone: +1 (423) 262 2522 Phone: +86 10 64 75 75 75 
Fax: +49 (180) 5050-223 Fax: +1 (423) 262 2289 Fax: +86 10 64 74 74 74 


E-Mail: [email protected] | | E-Mail: [email protected] | | E-Mail: [email protected] 


GMT: +1:00 GMT: -5:00 GMT: +8:00 
Technical Support and Authorization speak generally German and English. 











Function Blocks - FM 458-1 DP V 
Edition 12.2004 


Contents 


Foreword.uLunn. høstes iii 
1 JInput/output bIOCKS:. 42245056. hei ee ie Ain ee ee ei eaa r aa ied 1-1 
1.1 SBM Rotary encoder block siisii injana hanain aaan na AEA a aAA EY 1-2 
2; Gommiunication blocksaninsatelraananuemnisgidpd ae e eaa aaa no ameh oana saaa maeaea Tanie e ei aana Eai 2-1 
2.1 Gentral:coupling: POCKET ita EE NAE 2-1 
2.1.1 @CSL2F PROFIBUS FMS coupling central block ........rursrrrrnnnnonvrrnnnrnnrrnnrennrrnnnnrnnnn 2-1 
2.1.2 @CSL2L PROFIBUS FDL central block..........rrrnnnnnnonnnnnrnrrnnrnnnrrrrnnnnrrnnrernrnrrnnnnnnnnnen 2-1 
2.1.3 @CSPRO Central block PROFIBUS DP coupling ..............:.::cccceseeeeeeeceeeeeeeteeneneees 2-1 
2.1.4 @PRODP Central block PROFIBUS DP coupling ................::cccceeceeeeceeceeeeeeeteeeenaeees 2-2 
2.2 Kopplung PROFIBUS DP ............:::cccccceeeeeeeeeeeaeceeeeeeeeecaaeaeeeeeeeseseeeceaaeceeeeeeesecsanneeeees 2-3 
2.2.1 DPDIAG Diagnostics overview, PROFIBUS DP.............0::::ccccceeeeeeceeeeeeeeeeeteestnaeeeeees 2-3 
2.2.2 DPSLDG Slave diagnostics, PROFIBUS DP ...............cccccccceeeeeeeeeeceeeceeeeeeeteestnaneeeees 2-6 
2.2.3 DPEVT Alarm information, PROFIBUS DP ......rrununnrrannnnrnrernernnrnnnnnrsnernnransnersvnrnerrnnen 2-9 
2.2.4 DPPEVT Process alarm information, PROFIBUS DP Symbol................::::::cee 2-12 
2.3 FM 458-specific coupling ..........2...:ccccceceeeeeeeceeeeeeceeeeeeeseceaeaeeeeeeesesensaeaeeeeeeeeeeteeeeaees 2-15 
2.3.1 @CPB P-bus, central coupling DIOCK...0..... eee eect ee eet ee ee eetneeeeeteeeeetineeeeetnaeeeernnaa 2-15 
2.3.2 S7RD_P Reading data from a SIMATIC-CPU (P Bus) seese 2-16 
2.3.3 S7WR_P Sending data to a SIMATIC-CPU (P BUS) .......rrrrnrornnrnnrnrrnnrnnnnnnrrnrnnnnnnen 2-18 
2.3.4 BRCV Block-oriented data reception via an S7 Coupling ...........:::::::cceeceeeeeeeeeeeeees 2-20 
2.3.5 S7STAT S7 CPU operating State nisrani E EE ARAA 2-23 
2.3.6 S7RD, S7RD B, S7RD I, S7RD D Read from the peripheral area of the S7- 
GRU LL mane ete ea eae a ee tad ead ee eed 2-25 
2.3.7 S7WR, S7WR B, S7WR |, S7WR D Write into the peripheral area of the S7- 
GPU ai orei ek AR dar telle eee ruger Re 2-27 
2.4 Parameterizing SIMADYN D orori aa A a E EA A EAEn R 2-29 
2.4.1 @FMPAR Parameter processing on FM 458-1 DP modules........urrnnrrrnronnrrrrnven vnr 2-29 
2.4.2 CBCONF COMBOARD configuration. ............:::::ccccceeeeeeeeceecaeeeeeeeeeseceanaeeeeeeesetennaees 2-32 
2.4.3 CBRFAW Receiving warnings from a COMBOARD ....rurnnnrrnnnnnnrrnnrennrrrenernnrrersennnne 2-36 
2.4.4 PNAME Parameter names: ans acs actee tase ee cedies eee eens ade neida 2-38 
2.4.5 PSTAT Change enable for parameters .......0...ccccceeeeeeeeeeeeneeeeeeeneeeeeeneeeeeeneeeeeeaas 2-40 
3 Logic blocks ihrer raider arenaer keine mesk akser arkiveres endene dekade eee 3-1 
3.1 SAV TR Save FB for NOV RAM ....arrnnnnnornnonnnnrrnnrnnnrrrrnnrnrrnnrnrernrrrrnn nn nnnennernrrnnnnnnnnen 3-1 
3.2 PAS7 Initiate process interrupt at the S7-CPU........rnrrnnrnnnrnnvnnrnrrrnnnnrnnrrrnrnnrrnrennernern 3-3 
Function Blocks - FM 458-1 DP vii 


Edition 12.2004 


Contents 


4 Service-/diagnostic blocks .....rrrrnannvnnnnnnnnvennnnnnvnnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnsnnnnnnnnnnnnnnene 4-1 
4.1 FMLED Control FM 458-1 DP diagnostics LED ....rrannrrrnnrrnnrrnnrnnnrrvnrrnnrrenernnrrrersrnnnnn 4-1 
5: -SIMOLINK drive coupling --:.m-sermasserennnsnnnenndanrknndnnnrennmndnnnennndnnrknndmnnrennnndnranevnndaennnksnrsnnennd nd 5-1 
5.1 @SL SIMOLINK central block .........rrnnnnrrnnrrrnrnnnn eeeeeeee cece ee eeeeccceaaeeeeeeeeesecciaeeeeeeeeeneees 5-1 
5.2 SLAV, SLAVE R SIMOLINK receive block for one actual value...........».rrrvrvrrrvrrrerer 5-9 
5.3 SLD SIMOLINK delta evaluation. ..............cccccceeeeeececeeeeeeeeeececeeeeeeeeeesecsicieeeeeeeeeteees 5-11 
5.4 SLDIS SIMOLINK dispatchet..............::::ccccececeeeeeeeceeceeeeeeeseceneaeeeeeeesetennueaeeeeeeeeeeteees 5-12 
5.5 SLSV, SLSV R SIMOLINK send block for one setpoint ...........arrrrrnnrrrrrnrrrrrrrrrnnnnnn 5-13 
5.6 SLSV2, SLSV2R SIMOLINK send block for 2 setpoints..........r.rererererererernnnnnnnnnnnnnn 5-15 
5.7 SLSVAV SIMOLINK send and receive block for one Slave ...............:::::c:ceseeeeeeeees 5-17 
6: Glosed-loop Control. blocks a ea arer Taea are pa aaaea a aa aaa a Eal waen Ea aaa iie eraai 6-1 
6.1.1 INT_M Modulo integrator for axis cycle correct integration .........rrassnvrrnnnonnrrnnnrnnnnnn 6-1 
ea EEE S de |-1 
viii Function Blocks - FM 458-1 DP 


Edition 12.2004 


1 Input/output blocks 


Assignment of the input/output blocks to processor- and peripheral 
devices. 


ee 
Å he hdd ba bd ba ei 
458 mel EF 
EV a E A 


*) with SBM2 Module 





Function Blocks - FM 458-1 DP 1-1 
Edition 12.2004 


Input/output blocks 


1.1 SBM Rotary encoder block 


Symbol 


hardware address 
encoder type 


alarm- or normal FP 
rated speed 


Brief description 


Mode of operation 


1-2 


— position in increments 

— max. increments/revolution 
baud rate — normalized speed 
resolution 
— group error message 


— error detection 





The SBM function block is used to realize the following tasks: 
e Initialize the rotary encoder, which is connected at the SBM2 module 
e Determine the position and speed from the encoder data 


e Error handling when communication errors develop between the 
encoder and SBM2 module 


During the initialization phase of the system, the initialization I/O are read 
and the appropriate mode set at the SBM2 module. The following 
settings are made for the EQN1325 encoder: 


e The encoder power supply is set to 5 V 
e Number of revolutions to 4096 


e Signal periods per revolution 8192 


After the mode has been set, the zero position is determined, and the 
starting values for the position and the speed output at the connections. 


In the standard mode, the block can assume four different statuses: 


e NRM 
The values read-out from the SBM2 module (position and speed) are 
displayed at the block connections. If an error is detected, the block 
goes into the ERR error condition. 


e ERR 
The following errors can occur in operation: 


e Encoder is defective or is not connected 
e Encoder was disconnected 


e Data transfer error for serial communications between the encoder 
and SBM2 module 


e SBM2 module not available 


In the first three cases, the block goes into the "INI" initialization 
status and in the latter case into the "OFF" status. 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


Input/output blocks 


e INI 
as for the "initialization phase“ mode 


e OFF 
Output QF is set and processing terminated. 


Hardware address of the SBM2 (initialization input) 


Encoder type (initialization input 


TYP = 0 not available default: 1) 
TYP = 1 EQN1325 
TYP > 1 incorrect encoder type 


Baud rate (initialization input 


BDR = 0100 kHz default: 0) 
BDR = 1500 kHz 

BDR = 21 MHz 

BDR = 32 MHz 

BDR > 3incorrect baud rate 


Resolution in bits (default: 23) 
Value range: 16 < EXP < 32 


I/O 
Configure the block in cyclic tasks or interrupt tasks (initialization input 
DM=0 SBM in interrupt tasks default: 0) 
This mode is only practical in conjunction with the alarm- 
controlled SIMOLINK events (sync interrupt from SLB). Using this 
sync interrupt, in this mode, the values of the SBM module are 
de-latched. The block should then be configured in the alarm task 
started by the same event. 
DM=1 SBM in cyclic tasks 
If the block is computed in cyclic tasks, then the SBM2 module 


register is read-out in the system mode. The contents of the register 
are then read-out in the normal mode and the values for the output 
connections computed. 


Rated speed in revolution/min (RS>0) (default: 1.0) 


:0) 
Max. number of increments per revolution (default: 0) 
(depending on the input connection EXP) 
RPMmi default: 0.0 
Normalized speedform the rotary encoder ar 
) 
) 


Group error message (default: 0 
no error, QF=1 for error (if YFz0) 


Error status of the block (default: 
YF=0x0000 no error, YF>0x0000 (refer to error statuses) 160000 0000) 





Function Blocks - FM 458-1 DP 1-3 
Edition 12.2004 


Input/output blocks 


0x0040 Encoder fault/error 
— Check the hardware (encoder, cable etc.) 


0x0080 No voltage or short-circuit 


0x0100 No data transfer from or to the encoder 
— check the hardware (encoder, cable etc.) 


— check the hardware (encoder, cable etc.) 


0x2000 Invalid baud rate parameterized 


0x4000 Sampling time too high; speed computation not possible 
3 Sampling time: < 4.0 ms 


Configuringdata Computation time [us] FM 458-1 DP 13,2 


Can be configured in Interrupt tasks 
Cyclic tasks 

Executed in Initialization mode 
Normal mode 


Special features Can only be used with an EQN 1325 encoder 





1-4 Function Blocks - FM 458-1 DP 
Edition 12.2004 


2 Communication blocks 


2.1 Central coupling blocks 


NOTE Additional information on this group of function blocks, e.g. symbol, 
mode of operation, I/O and technical data are provided in the online 
help for the particular block. 


2.1.1 @CSL2F PROFIBUS FMS coupling central block 


Brief description e the function block initializes and monitors the PROFIBUS FMS 
coupling (CS7 and SS5 module). 


e the function block may only be configured in the sampling interval 
32 ms <= TA <= 256 ms and only in the communications FP 
"Transmit". Otherwise, an entry is made in the communications error 
field. 


2.1.2 @CSL2L PROFIBUS FDL central block 


Brief description e the function block initializes and monitors the PROFIBUS FDL 
coupling (CS7 and SS5 module). 


e the function block may only be configured in the sampling interval 
32 ms <= TA <= 256 ms and only configured in the communications 
FP "transmit". Otherwise an entry will be made in the communications 
error field. 


2.1.3 @CSPRO Central block PROFIBUS DP coupling 


Brief description e the function block initializes and monitors the PROFIBUS DP coupling 
(EXM 448/EXM 448-1). 


e the function block may only be configured in the sampling interval 
32 ms <= TA <= 256 ms . Otherwise an entry is made in the 
communications error field. 


Function Blocks - FM 458-1 DP 2-1 
Edition 12.2004 


Communication blocks 


2.1.4 @PRODP Central block PROFIBUS DP coupling 


Brief description e the function block initializes and monitors the PROFIBUS DP coupling 
at connector X03 on FM 458-1 DP. 


e the function block may only be configured in the sampling interval 
32 ms <= TA <= 256 ms . Otherwise an entry is made in the 
communications error field. 


2-2 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


2.2 Kopplung PROFIBUS DP 


2.2.1 DPDIAG Diagnostics overview, PROFIBUS DP 


Symbol 


DP module name.connector 


Brief description 


Mode of operation 














DPDIAG 


BO 
DW 
DW 
DW 
DW 
DW 
DW 
DW 
DW 
BY 


—Diagnostics valid 
— Slave diagnostics; bits 0 to 31 








— Slave diagnostics; bits 32 to 63 
— Slave diagnostics; bits 64 to 95 
— Slave diagnostics; bits 96 to 127 
— Data transfer list; bits 0 to 31 

— Data transfer list; bits 32 to 63 

— Data transfer list; bits 64 to 95 

— Data transfer list; bits 96 to 127 
— Master status 




















ID W |-- Identification number 
QTS BO |- Block status 
YTS W |- Status display 


The task of the DPDIAG function block is to provide the following 
information and data to the user program (i.e. the configured CFC 


software): 


System diagnostics (an overview of which slave had signaled 
diagnostics) 


Data transfer list (overview of with which slave data transfer took 
place within the PROFIBUS-DP time frame) 


Master status (master-specification information such as the Stop, 
Operate and Clear stati) 


The PROFIBUS-DP interface is selected using connection CTS. 


The function block only enters a communications error for errors, which 
are detected during initialization. A communications error cannot be 
acknowledged and this function block is only used for diagnostics. This 
means, that in normal operation, a communications error is not entered. 
Only the cause of the error is signaled at output YTS. 


Function Blocks - FM 458-1 DP 


Edition 12.2004 


Communication blocks 


I/O 





CTS 


Module name.connector of the Profibus-DP interface 


(Initialization 
connection) 





EN 


Block enable 
The block is not processed if EN=0; output OK=0 and YTS=1; 
the last value is kept at the other outputs 


(Default: 1) 





OK 


Diagnostics data valid 


(Default: 0) 





DG1 


Overview of which slave signaled diagnostics data. This output is 
bit-coded. Every bit is assigned to a slave with its Profibus 
address. 

Bit 3 of the 32 bit is, for example, assigned to the slave with 
Profibus address 3. 


Comment: The bits 0 up to and including 2 are always 0 as the 
associated addresses (0 to 2) should be reserved for the DP 
master, for a PG and an OP. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





DG2 


Overview of which slave had signaled diagnostics data. This 
output 

is bit-coded. Every bit is assigned to a slave with its Profibus 
address. The bit 0 of the 32-bit word is, for example, assigned to 
the slave with Profibus address 32. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





DG3 


Overview of which slave had signaled diagnostics data. This 
output 

is bit-coded. Every bit is assigned to a slave with its Profibus 
address. The bit 0 of the 32-bit word is, for example, assigned to 
the slave with Profibus address 64. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





DG4 


Overview of which slave had signaled diagnostics data. This 
output 

is bit-coded. Every bit is assigned to a slave with its Profibus 
address. The bit 0 of the 32-bit word is, for example, assigned to 
the slave with Profibus address 96. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 








DL1 





Overview of with which slave data transfer took place. This output 
is bit-coded. Every bit is assigned to a slave with its Profibus 
address. For example, bit 3 of the 32-bit word is assigned to the 
slave with Profibus address 3. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 





(Default: 0) 





2-4 


Function Blocks - FM 458-1 DP 


Edition 12.2004 





Communication blocks 





DL2 


Overview of with which slave data transfer took place. This output 
is bit-coded. Every bit is assigned to a slave with its Profibus 
address. For example, bit 0 of the 32-bit word is assigned to the 
slave with Profibus address 32. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 


oO 
= 





DL3 


Overview of with which slave data transfer took place. This output 
is bit-coded. Every bit is assigned to a slave with its Profibus 
address. For example, bit O of the 32-bit word is assigned to the 
slave with Profibus address 64. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 





DL4 


Overview of with which slave data transfer took place. This output 
is bit-coded. Every bit is assigned to a slave with its Profibus 
address. For example, bit 0 of the 32-bit word is assigned to the 
slave with Profibus address 96. 


For a more detailed description, refer to the user manual 
"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 





MST 


Status of the DP master: 
Stop (0x40 ), Clear (0x80) or Operate (0xCO) 


(Default: 





Master identification number: 
(0x8037 for EXM448 as Profibus interface, Ox80EB when 
using X3 of the FM458-1) 


(Default: 





QTS 


Block output QTS is used to display whether the block is operating 
error-free (QTS = 1) or was de-activated after a communications 
error message was entered (QTS = 0). 


(Default: 








YTS 





Detailed status display: 
e YTS=0 Dok. 
e YTS=1 > Block processing inhibited (EN=0) 


For additional values at YTS, refer to: D7-SYS Online Help "Help 
events". (Press the F1 button in the CFC and call the topic 
"Help on events" under "CFC for D7-SYS".) 





(Default: 





Configuring data 





Computation time [us] FM458-1 DP 42,7 





Can be inserted online No 





Can be configured in Cyclic tasks 





Executed in Initialization mode 
Normal mode 











module. 


Special features This function block may only be configured 
once for each PROFIBUS communications 








Function Blocks - FM 458-1 DP 
Edition 12.2004 


2-5 





Communication blocks 


2.2.2 DPSLDG Slave diagnostics, PROFIBUS DP 


Symbol 












DPSLDG 


BO |-- Diagnostics valid 
BY |-- Status 1, standard diagnostics 
BY |- Status 2, standard diagnostics 


DP module name. connector 
Slave address 

Number of device-related 
diagnostic bytes 


Enable BY |- Status 3, standard diagnostics 


BY |- Master Profibus address 
W |- Slave identification number 
DW |- Diagnostic bytes v, w, x u. y 1) 


DW |-- Diagnostic bytes v, w, x u. y ” 
BO |- Block status 
W |- Status display 


9 normally invisible 


Brief description The DPSLDG function block provides diagnostics data from a DP slave 
to the user program. This diagnostics data correspond, with the exception 
of the maximum possible length, to EN 50170. According to this 
Standard, the diagnostics data can be a maximum of 244 bytes long. The 
function block supports a maximum of 240 bytes 


On the EXM448, there are restrictions regarding the quantity of 
diagnostics data. Only diagnostics data (Standard diagnostics data) is 
supplied which the function block DIAPRO supplies. 


Note The consistency of the outputs is not ensured. When new diagnostics 
data is received, some of the outputs can have "New" information and 
some can still have "old" information. 


Mode of operation The PROFIBUS-DP interface is selected using connection CTS. 


The function block only enters a communications error for errors, which 
are detected during initialization. A communications error cannot be 
acknowledged and the function block DPSLDG is only used for 
diagnostics. This means, that in normal operation, a communications 
error is not entered. Only the cause of the error is signaled at output 
YTS. 


2-6 Function Blocks - FM 458-1 DP 
Edition 12.2004 


I/O 


Communication blocks 





CTS 


DP module name, connector of the Profibus DP interface 


(Initialization connection) 





SLA 


Diagnostics data required from the slave with the appropriate 
station number (3 to 123) 


(Initialization connection) 
(Default: 3) 





LEN 


Number of the device-related diagnostic bytes; this means the 
diagnostics bytes which extend beyond the Standard diagnostics. 
Here, a maximum value of 234 may be set. Whether device-related 
diagnostics data is available and, if yes, which significance they 
have, should be taken from the user documentation of the relevant 
DP slave. 


(Initialization connection) 
(Default: 0, i.e. only 
Standard diagnostics, not 
device-related diagnostic 
bytes) 





EN 


Block enable. If EN=0, the block is not processed; 
output OK=0 and YTS=1, the last value remains at the other 
outputs. 


(Default: 1) 





OK 


Diagnostics data valid 


(Default: 0) 





ST1 


Status 1 of the diagnostics according to the Standard (byte 1). 
For a more detailed description, refer to the user manual 

"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





ST2 


Status 2 of the diagnostics according to the Standard (byte 2). 
For a more detailed description, refer to the user manual 

"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





ST3 


Status 3 of the diagnostics according to the Standard (byte 3). 
For a more detailed description, refer to the user manual 

"FM 458-1 DP", chapter "Configuring", section "PROFIBUS DP 
coupling". 


(Default: 0) 





MPA 


Master Profibus address (byte 4 of the diagnostics according to the 
Standard) 





Identification number of the slave 
(bytes 5 and 6 of the diagnosics according to the Standard) 





D01 
to 
D59 


Device-related diagnostic bytes; 4 bytes are combined in one 
32-bit 

word. Bytes 7, 8, 9 and 10 of the diagnostics telegram can be 
found 

in D01. 

For a more detailed description, refer to the user manual 

"FM 458-1 DP", chapter "Configuring", section "PROFIBUS 
DP 

coupling". 


When data is entered at LEN, this has an influence on the 
update 

of the outputs. For LEN=0, these outputs are not updated. 
For LEN=234, D01 up to and including D59 are updated. 


Comment: 

Bytes 1 to 6 of a diagnostics telegram for PROFIBUS DP 
corresponds to the Standard Diagnostics; bytes from 7 onwards 
depend on the particular slave (referred to the particular device). 


(Default: 0) 








QTS 





Block output QTS is used to display whether the block is operating 
error-free (QTS = 1) or was de-activated after a communications 
error message was entered (QTS = 0). 





(Default: 0) 





Function Blocks - FM 458-1 DP 
Edition 12.2004 


2-7 





Communication blocks 
































YTS Detailed status display: (Default: 0) 
e YTS=0 > o.k. 
e YTS=1 > Block processing inhibited (EN=0) 
e YTS=2 > An initialization connection (SLA er LEN) was 
changed in cyclic opertion; this change only becomes effective 
the next time that the FM458-1 starts 
e YTS=3 > The block has already been configured once for the 
slave addressed via SLA 
e YTS=4 > The slave, with the address specified at SLA, has not 
been configured in the PROFIBUS network. 
For additional values at YTS, refer to: D7-SYS Online Help "Help 
events". (Press the F1 button in the CFC and call the topic 
"Help on events" uncer "CFC for D7-SYS".) 
Configuring data Computation time [us] FM458-1 DP 29 
Can be inserted online No 
Can be configured in Cyclic tasks 
Executed in Initialization mode 
Normal mode 
Special features The function block may only be configured 
once for each slave. 


2-8 














Function Blocks - FM 458-1 DP 
Edition 12.2004 





Communication blocks 


2.2.3 DPEVT Alarm information, PROFIBUS DP 


Symbol 


Brief description 


Mode of operation 


Expanded info 











—Sub-module 

— Sub-network 

YO!1 DW |-- Diagnostic bytes 0, 1, 2 and 3 
YO2 DW |-- Diagnostic bytes 4, 5,6 and 7 
YO3 DW |- Diagnosebytes 8, 9, 10 and 11 
YO4 DW |-- Diagnostic bytes 12, 13,14 and 15 
YO5 DW |-- Diagnostic bytes 16, 17, 18 and 19 
YO6 DW |- Diagnostic bytes ... 1) 

— Diagnostic bytes ... 1 
— Block status 

W |- Status display 


1) normally invisible 


The DPEVT function block (DP event) provides more detailed information 
about a Profibus-DP process or diagnostics alarm. The information/data, 
provided at the outputs, correspond to the information/data which a 
SIMATIC S7 module also has when processing the appropriate alarm 
OBs (e.g. 0B40, OB55 etc.). 


When an alarm event is output, all of the values at the outputs are 
updated. 


When the appropriate alarm occurs, the alarm task configured for this 
purpose, is started, Within the alarm task, DPEVT reads-out the alarm 
information. Å new alarm of the same time is only detected again after 
the alarm task has been completed. 


When a communications error occurs, the cause is also output at output 
YTS and the QTS output is set to "0". 


Function Blocks - FM 458-1 DP 2-9 


Edition 12.2004 


Communication blocks 


I/O 





EXT 


For EXT=0, only the data/information at outputs Y01 
to Y05 is updated. 


For EXT=1, in addition, the information/data at outputs Y06 to 
Y21 is updated. 


(Default: 





OB 


The number of the appropriate SIMATIC S7 organizational block 
(OB) is displayed at this output. In an error-free state, values 40, 
55, 56, 57, 82, 83 and 86 are possible here. The actual value 
depends on the process alarm configured in the HWConfig for the 
particular alarm task. 


(Default: 





STA 


Station address of the slave which had initiated the alarm. Values 
of between 1 and 126 are valid values for this address. 


(Default: 





SLO 


Slot of the module which initiated the alarm. Values of between 1 
and 244 are valid values for the slot data. 


(Default: 





SUB 


Sub-module of the module which initiated the alarm. Values of 
between 1 and 31 are valid values for the sub-module data. 
A value of 0 means no sub-module. 


(Default: 





SBN 


Sub-network to which the module, which initiated the alarm, is 
connected. Values of between 1 and 255 are valid values for the 
sub-network data. The number for the sub-network can be taken 
from the properties dialog box in NetPro or HY-Config. 


(Default: 





YO1 


The first 4 bytes with information about the last alarm event are 
available at this output. The actual significance corresponds to 
the first byte of the local data of the appropriate S7-OB. 

As a whole, the local data comprise 20 bytes; the structuring of 
the local data can be taken from the help for the appropriate OB. 


(Default: 





YO2 


The second 4 bytes with information about the last alarm event 
are available at this output. 


(Default: 





YO3 


The third 4 bytes with information about the last alarm event are 
available at this output. 


(Default: 





YO4 


The fourth 4 bytes with information about the last alarm event are 
available at this output. 


(Default: 





Y05 


The fifth 4 bytes with information about the last alarm event are 
available at this output. 


(Default: 





Y06 
to 
Y21 


You can obtain additional information/data about the alarm, which 
goes beyond the local data of the S7-OBs, at these outputs. 

The information/data correspond to that which you would obtain if 
you would have called the SFB54 "RALRM" within the appropriate 
S7-OBs. The outputs are only updated if EXT=1 is set to 1. 
Normally, these outputs are switched so that they are invisible, 
and, when required, must be first made visible in the CFC, under 
the tab "I/O". 


(Default: 





QTS 


Block output QTS is used to display whether the block is 
operating error-free (QTS = 1) or was de-activated after a 
communications error message was entered (QTS = 0). 


(Default: 








YTS 





Detailed status display for additional values at YTS, 

refer to: D7-SYS Online Help "Help events". 

(Press the F1 button in the CFC and call the topic "Help on 
events" uncer "CFC for D7-SYS".) 





(Default: 





2-10 


Function Blocks - FM 458-1 DP 


Edition 12.2004 





Communication blocks 














Configuring data Computation time [us] FM458-1 DP 23,6 
Can be inserted online No 
Can be configured in Alarm tasks 
Executed in Initialization mode 


Normal mode 





Special features The DPEVT may only be configured in an 


alarm 

task for which one of the following alarm 
CAUSES 

is configured in HW-Config: 

e Process alarm 1 (0B40) 

e DPV1 status alarm (0B55) 

e DPV1 update alarm (0B56) 

e DPV1 manufacturer-specific alarm (0B57) 
e Diagnostics alarm (OB82) 

e Withdraw/insert alarm (OB83) 

e Failure, subrack alarm (OB86) 


If this is not the case, DPEVT signals an 
appropriate communications error and stops 
processing. 














Function Blocks - FM 458-1 DP 2-11 
Edition 12.2004 


Communication blocks 


2.2.4 DPPEVT Process alarm information, PROFIBUS DP Symbol 


Symbol 









I |- Station 

I |- Slot 

I |- Sub-module 

I |- Sub-network 

— Event classes and IDs 
—10 flag 

— Input module 

— Output module 

— Logical address 
—0B40 POINT ADDR 


— Block state 
W |-- Status display 


The DPPEV (DP process event) provides more detailed information 
about the Profibus DP process alarm (OB40 alarm). Contrary to the 
DPEVT, only selected information/data is available, but then, in a 
conditioned form. 


Brief description 


Mode of operation When an alarm event is output, all of the values at the outputs are 
updated. 


For a communications error, the cause is additionally output at YTS and 
the QTS output is set to "0". 


2-12 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 








I/O 

STA Station address of the slave which had initiated the alarm. Values (Default: 0) 
of between 1 to 126 are valid values for this address. 

SLO Slot of the module which initiated the alarm. Values of between 1 (Default: 0) 
and 244 are valid values for the slot data. 

SUB Sub-module of the module which initiated the alarm. Values of (Default: 0) 


between 1 and 31 are valid values for the sub-module data. 
A value of 0 means no sub-module. 





SBN Sub-network to which the module, which initiated the alarm, is (Default: 0) 
connected. Values of between 1 and 255 are valid values for the 
sub-network data. The number for the sub-network can be taken 
from the properties dialog box in NetPro or HW-Config. 





EVC This output corresponds to the local data variables (Default: 0) 
0B40 EV CLASS of the 0B40 for a SIMATIC-S7. A value of 
B#16#11(11 hexadecimal) means that the alarm is active. 





IOF This output corresponds to the local data variables (Default: 0) 
0B40 IO FLAG of the OB40 for a SIMATIC-S7. 
The significance is as follows: 


B#16#54 (54 hexadecimal) > Input module 
B#16#55 (55 hexadecimal) > Output module 


The (present) possible information is available, in a 
conditioned form, at outputs IN and OUT. 








IN IN=1 > Input module has initiated an alarm (Default: 0) 
IN=0 > The alarm was not initiated from an input module 
OUT OUT=1 > Output module had initiated an alarm (Default: 0) 


OUT=0 > The alarm was not initiated from an output module 





MDL This value outputs the logical basis address of the module. (Default: 0) 
The value corresponds to the local data variables 
OB40_MDL_ADDR of the OB40 for a SIMATIC-S7. 





PAD This value supplies additional information about the cause of the (Default: 0) 
process alarm. The value corresponds to the local data variables 
OB40_POINT_ADDR of the OB40 for a SIMATIC-S7. Additional 

information about this is provided in the SIMATIC documentation. 


























YYR Year (Default: 0) 
(specifies in which year the alarm was initiated) 

YMO Month (Default: 0) 
(specifies in which month the alarm was initiated) 

YDA Day (Default: 0) 
(specifies on which day the alarm was initiated) 

YHR Hour (Default: 0) 
(specifies at which hour the alarm was initiated) 

YMI Minute (Default: 0) 
(specifies at which minute the alarm was initiated) 

YSE Second (Default: 0) 
(specifies at which second the alarm was initiated) 

QTS Block output QTS is used to display whether the block is (Default: 0) 


operating error-free (QTS = 1) or was de-activated after a 
communications error message was entered (QTS = 0). 











Function Blocks - FM 458-1 DP 2-13 
Edition 12.2004 





Communication blocks 








YTS Detailed status display; for additional values at YTS, (Default: 0) 
refer to: D7-SYS Online Help "Help events". 
(Press the F1 button in the CFC and call the topic 
"Help on events" uncer "CFC for D7-SYS".) 























Configuring data Computation time [us] FM458-1 DP 23,6 
Can be inserted online No 
Can be configured in Alarm tasks 
Executed in Initialization mode 


Normal mode 





Special features The DPPEV may only be configured in an 
alarm task for which the following alarm 
cause is configured in HW-Config 


e Process alarm 1 (0B40) 


If this is not the case, DPPEV signals an 
appropriate communications error and stops 
processing. 

A new alarm of the same time is only again 
detected after the alarm task has been 
completed. 














2-14 Function Blocks - FM 458-1 DP 
Edition 12.2004 





Communication blocks 


2.3 FM 458-specific coupling 


2.3.1 @CPB P-bus, central coupling block 


Symbol 


@CPB 





CPU-module-name.PBUS {GV CTS CDM] BOJ-— coupling status 
QTS| BO} - block status 


Brief description The central block for the P-bus coupling can only run with an FM 458 
application module. 


e This function block is responsible for initializing and monitoring the P 
bus coupling. 


e The function block can only be configured once for each application 
module FM 458, as there is only one P-bus coupling for each FM 458. 
If a function block is configured a multiple number of times, this is 
detected when initializing, and results in an entry in the 
communications error field. 


e The block may only be configured in the sampling interval 
32 ms <= TA <= 256 ms. Otherwise, an entry is made in the 
communications error field. 


Mode of operation When initializing the function block, general preparations are made to 
enable the coupling. The coupling is only enabled after the standard 
mode has been run-through (executed) several times. 


After the coupling has been enabled, the central block monitors that 
senders and receivers are correctly registered. Further, if required, it re- 
organizes and updates the block output CDM at each processing cycle. 


The function block cannot be used to initialize another P-bus coupling or 
monitor this. It can only initialize its own P-bus coupling on which CPU is 
configured. An entry is made in the communications error field if another 
module name is specified at the CTS input (other than its own). 


The CDM block output provides information about the coupling status. 
The connection is a 1, if the coupling is enabled for general send/receive 
operation. The CDM block output is 0, as long as the coupling is still 
being initialized, or is being re-initialized (after a temporary fault). 


Function Blocks - FM 458-1 DP 2-15 
Edition 12.2004 


Communication blocks 


The configured name of its own CPU is specified 
at this initialization input. 
Specifies the coupling status (default: 0) 
(faulted = 0, not faulted = 1). 
:0) 





Operating status of the function block (default: 0 
There is an irreparable fault for QTS = 0, for QTS 

= 1, 

the function block operates error-free. 


Configuringdata Computation time [us] FM 458-1 DP 16,5 


Can be configured in Cyclic tasks 


Executed in Normal mode 
Initialization mode 


Special features - 








2.3.2 S7RD P Reading data from a SIMATIC-CPU (P Bus) 


Symbol 








S7RD P 
Offs in 128By-PBus-Buffer OFF PTR| DWF PirBuffer Transmitdata 
Number bytes to be read LEN QF] BO Error-Status Block 
Enable EN YF WF Statusinfo Block 


Brief description This block can only be used for the SIMATIC application module FM 458- 
1 DP. 
A SIMATIC-CPU can transfer up to 128 bytes to the FM 458-1 DP in its 
output area of the P bus. Block S7RD_P reads this data from the P-Bus 
and provides it, via its pointer interface, to the read blocks (DRD..., 
CPY_Y) for further processing in the CFC configured software. 


Mode of operation This block operates similar to the telegram block CRV_P. A maximum of 
128 bytes can be accessed via the pointer interface. These bytes are 
sent from the SIMATIC-CPU to the FM 458-1 DP via the P bus. 

Data can be read using the read blocks (DRD...) or the copy block 
(CPY_P). 


This block only communicates with a SIMATIC-CPU. This means that the 
required byte or word swap operations are automatically made 
(depending on the data type of the connected read/write blocks). The 
entry, which is normally required at the SW-connection of the read/write 
block, is not evaluated and is therefore not required. 


2-16 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


The computation time essentially depends on the amount of data 
transferred. A base computation time of approx. 10 us as well as approx. 
1 us/byte can be assumed as nominal value. 


Associated blocks The following blocks can be connected to this block (pointer input): 
DRD, DRD 8, DRD 8D, DRD_8I, DRD BY, DRD_D, DRD I, CPY_P 


I/O 





Default: 





OFF Offs in 128By-PBus-Buffer 0 
Offset of the value to be sent within the 128 byte memory relative to the start of 
the buffer; max. offset: Buffer length - length of the data type 





LEN Number bytes to be read 0 
Number of bytes which are read by the SIMATIC-CPU via the P bus. 
Max. number: 128 bytes 








EN Enable 1 
For EN=1 at each call, the data sent from the SIMATIC-CPU (max. 128 bytes) 
is read. 
PTR PtrBuffer Transmitdata 16400000000 


Pointer to the telegram data buffer; to connect with the same connection type 
of other pointer-based communication blocks. The CFC connection can be 
changed online. 

The connection also includes monitoring information to ensure correct 











configuring. 

QF Error status block 0.0 
QF=1: There is an error; for details, refer to YF 

YF Statusinfo Block 1640000 


88 as for the DRD block! 


























Configuring data Computation time [us] FM 458-1 DP 10,0 + 1 for each byte 
Can be inserted online Yes 
Can be configured in Interrupt tasks 
Cyclic tasks 
Executed in Initialization mode 


Normal mode 





Special features The block must be configured in the same 
sampling time 

as the blocks, connected via the pointer interface 
(CFC connection via connections PTR). This can 
only be used for the FM 458-1 DP! 

Several S7RD P blocks can be configured. 
Although this is not a typical application, it can 
make sense if, for example, the 128 byte area 
should be read in several blocks or if data is 
required in different sampling times. 














Function Blocks - FM 458-1 DP 2-17 
Edition 12.2004 


Communication blocks 


2.3.3 S7WR P Sending data to a SIMATIC-CPU (P Bus) 


Symbol 


Offs in 128By-PBus-Buffer 
Number bytes to be write 
Number bytes to be write 


Brief description 


Mode of operation 


Associated blocks 


I/O 





This block can only be used for the SIMATIC application module FM 458- 
1 DP. 

An FM 458-1 DP can send up to 128 bytes to the SIMATIC-CPU via the 
P-Bus. The block S7WR_P sends data which were previously loaded 
with write blocks via the pointer interface. 


This block operates similar to the telegram block CTV_P. A maximum of 
128 bytes can be transferred via this pointer interface and via the P bus 
to the SIMATIC CPU. This data is previously loaded into the telegram 
buffer using write blocks DWR... of the copy block CPY_Y. 


This block only communicates with a SIMATIC-CPU. This means that the 
required byte or word swap operations are automatically made 
(depending on the data type of the connected read/write blocks). The 
entry, which is normally required at the SW-connection of the read/write 
block, is not evaluated and is therefore not required. 


The computation time essentially depends on the amount of data 
transferred. A base computation time of approx. 5 us as well as approx. 
0.7 us/byte can be assumed as nominal value. 


The following blocks can be connected to this block (pointer input): 
DWR, DWR_8, DWR_8D, DWR_8I, DWD_BY, DWR_D, DWR_I, CPY_P 





Default: 





OFF Offs in 128By-PBus-Buffer 0 
Offset of the value to be sent within the 128 byte memory relative 
to the start of the buffer; 

max. offset: 


Buffer length - length of the data type 





LEN Number of bytes to be written 0 
Number of bytes which are to be sent to the SIMATIC CPU via the P bus. 
Max. number: 128 bytes 





EN Enable 


For EN=1, at each call, the telegram buffer (max. 128 bytes) is sent to 
the SIMATIC-CPU. 








PTR PtrBuffer Transmitdata 16#00000000 
Pointer to the telegram/data buffer; to connect with the same connection 
type of other pointer-based communication blocks. 

The CFC connection can be changed online. 

The connection also includes monitoring information to ensure correct 
configuring. 














2-18 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


























QF Error status block 0.0 
QF=1: There is an error; for details, refer to YF 
YF Statusinfo Block 16440000 
88 as for the DRD block! 
Computation time [us] FM 458-1 DP 5,0 + 0.7 for each byte 


Configuring data 





Can be inserted online 


Yes 





Can be configured in 


Interrupt tasks 
Cyclic tasks 





Executed in 


Initialization mode 
Normal mode 





Special features 





Function Blocks - FM 458-1 DP 
Edition 12.2004 





The block must be configured in the same 
sampling time 

as the blocks, connected via the pointer interface 
(CFC connection via connections PTR). 

This can only be used for the FM 458-1 DP! 
Several S7WR_P blocks can be configured. 
Although this is not a typical application, it can 
make sense if, for example, the 128 byte area 
should be written in several blocks or if data is 
required in different sampling times. 





2-19 


Communication blocks 


2.3.4 BRCV Block-oriented data reception via an S7 coupling 


Symbol 


Establish ready to receive 
Addressing parameters ID 
Addressing parameters R ID 
Maximum length, receive data 


— Receive data is ready 

— Status parameter NDR 

— Length of data received before 
— Number of receive operations 
— Status parameter ERROR 

— Status, fault display 

— Block status 

W |- Status display 





Brief description The function block allows block-oriented data reception via a configured 
S7 coupling. 


Mode of operation The BRCV block receives data from a "remote" partner. The "remote" 
partner is an SFB/FB, type BSEND (SFB/FB 12) on a SIMATIC S7-400 
CPU. 


After each data segment which has been received, an acknowledgement 
is sent to the partner SFB/FB and the LEN parameter is updated. 


The block is ready to receive when a "1" is connected to the control input 
ENR. A running task can be interrupted with ENR=0. 


The maximum length of the receive area is specified by the data at input 
RLN. The length of the data block received is displayed at output LEN. 





























I/O 

ENR Control parameter Default: 0 
The block is ready to receive with ENR = 1 

ID Addressing parameter Initialization input, 
Reference to the local connection description Default: 0 
(this is specified as a result of the STEP7 configured connection) 

RID The value at input RID specifies the association with the send SFB/FB. Initialization input, 
The value at the input must match the R_ID parameter for SFB/FB on Default: 0 
the 
send side. This allows several SFB/FB pairs to communicate via the 
same logical coupling. The block pairs of a logical coupling, defined 
using 
RID or R_ID must be unique for this coupling. 

RLN The maximum length of the received data is defined here. Initialization input, 
Only values of between 0 and 65535 may be configured. Default: 0 

PTR The receive data, to be evaluated by the blocks for direct Default: 0 
communication, 
is made available here (e.g. types DRD, DRD |, etc.). 

2-20 Function Blocks - FM 458-1 DP 


Edition 12.2004 





Communication blocks 





NDR Status parameter NDR Default: 0 


0: Task was still not started (ENR input)or is still running 
1: Task was successfully completed 








LEN Length of the previously received data in bytes Default: 0 
CTR This output counts the total number of successfully complete data Default: 0 
receive 


cycles since the last change from STOP to RUN. 





ERR An error is output at block output ERR. The detailed information about Default: 0 
the 

type of the error is available at output STA. 

This output corresponds to the ERROR output of an SFB/FB 13 
of an S7-CPU. 





STA Detailed status display Default: 0 
This output corresponds to the STATUS output of an SFB/FB 13 of an 
S7-CPU. 


ERR = 0: 

e STA=00H 
No alarm, no fault 

e STA=11H 
Non-synchronous data is received, output LEN indicates the number 
of pieces of data previously received in bytes. 

ERR = 1: 


e STA=01H 
Communication problems 
(e.g. the coupling description to the ID not loaded, coupling has still 
not been established from the partner or the coupling was 
interrupted) 


e STA=04H 
Error regarding the data length 
The data block sent is longer than the receive range set using input 


RLN. 
e STA=05H 

Reset request received, incomplete transfer 
e STA=12H 

R_ID already exists in the coupling 
e STA=14H 


too little working memory 





QTS Block output QTS indicates whether the block is operating (QTS = 1)or | Default: 0 
became inactive after a communications error message was entered 








(QTS = 0). 
YTS Detailed status display Default: 0 
e YTS=0 > O.K. (ready) 
e YTS=1 
The block is in the DISABLED state, i.e. ENR=0 
e YTS=2 


The initialization connection is changed, the change only becomes 
effective at the next STOP > RUN transition; the FB operates with 
the values at ID, RID and RLN set when running-up 


For other values at YTS, in addition, a communications error is entered 
in 
the diagnostics buffer and the block is no longer processed (QTS=0) 











Function Blocks - FM 458-1 DP 2-21 
Edition 12.2004 





Communication blocks 


Configuring data 


2-22 





Computation time [us] 


FM458-1 DP 5,7 








Can be inserted online No 
Can be configured in Alarm tasks 
Cyclic tasks 





Executed in 


Initialization mode 
Normal mode 








Special features 











Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


2.3.5 S7STAT S7 CPU operating state 


Symbol 


Brief description 


Mode of operation 








S7STAT 


BO |- S7-CPU in RUN 
BO |- S7-CPU in STOP 
BO |- S7-CPU in HOLD 






outputs. 


—actual operating state 
— previous operating state 


The actual and previous S7-CPU operating states are displayed at the 


The actual and previous operating state of the S7-CPU is determined and 


displayed at connectors ACT for the actual and OLD for the previous 
operating state. Output RUN is set to TRUE if the S7-CPU is either in the 


RUN or RUN-R state. 






























































Output value Operating state RUN STP HLD 
to ACT or OLD 
0x0010 Stop 0 1 0 
0x0020 Cold start 0 0 0 
0x0040 New start 0 0 0 
0x0080 Re-start 0 0 0 
0x0100 RUN 1 0 0 
0x0200 RUN-R 1 0 0 
0x0400 Hold 0 0 1 
NOTE All other values are used for extended diagnostics. 
I/O 
RUN S7-CPU in RUN (Default: 0) 
STP S7-CPU in STOP (Default: 0) 
HLD S7-CPU in HOLD (Default: 0) 
ACT Actual operating state of the S7-CPU (Default: 0x8000) 
OLD Previous operating state of the S7-CPU (Default: 0x8000) 











Please refer to the help for STEP7 for a more detailed description of the 


operating states. 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


2-23 








Communication blocks 


Configuring data 


2-24 











Commutation time [ys] FM458-1 DP 

Can be inserted online yes 

Can be configured in Alarm tasks 
Cyclic tasks 





Executed in 


Normal mode 








Special features 











Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


2.3.6 S7RD, S7RD B, S7RD |, S7RD D Read from the peripheral area of the 


S7-CPU 


Symbol 


Brief description 


Mode of operation 


Offset 
Enable 


— Output 
— error output 





The function blocks, read from the peripheral area of the S7-CPU, can 
only run with an FM 458 application module. 


The S7RD, S7RD B, S7RD I, S7RD D blocks only differ by the data 
type at the output, which must correspond with the parameters to be 
read: 


e S7RD: REAL 
e S7RD B: BOOL 
e S7RD I: INT 

e S7RD D: DINT 


With this block, data can be read into the assigned net data area of the 
SIMATIC S7-CPU, (periphery output) assigned to the FM 458 application 
module. This PE area is 128 bytes. 


If the enable signal is set, the appropriate value is read from the PA area 
and made available at output Y. 


The offset determines at which location in the PA area, the value is 
retrieved. 


Depending on the block- or data type, the offset is specified as follows: 


e for REAL data type in 4-byte steps (data length) 
value range of the offset: 0... 31 


e for BOOL data type in 1-byte steps (data length). 
value range of the offset: 0... 127 


e for INT data type in 2-byte steps (data length). 
value range of the offset: 0... 63 


e for DINT data type in 4-byte steps (data length). 
value range of the offset: 0... 31 


Output QF has the value 1, if an invalid offset was selected, or the block 
is not configured on the FM 458. 


Function Blocks - FM 458-1 DP 2-25 


Edition 12.2004 


Communication blocks 


å or Jose fem 
len — fees fee) 
far ferro dere) ——SSSCSC*Y 


Configuringdata Computation time [us] FM 458-1 DP 3,3 


Can be configured in Interrupt tasks 
Cyclic tasks 

Executed in Normal mode 
Initialization mode 





2-26 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


2.3.7 S7WR, S7WR B, S7WR 1, S7WR D Write into the peripheral area of 


the S7-CPU 


Symbol 


Brief description 


Mode of operation 


1/0 


Input 
Offset 
Enable 


— Error output 





The function blocks, write the peripheral area (I/O) of the S7-CPU can 
only run with one FM 458 application module. 


The S7WR, S7WR_B, S7WR I, S7WR D blocks differ by the data type 
at the input, which must correspond with the parameters to be written: 


e S7WR: REAL 
e S7WR B: BOOL 
e S7WR I: INT 

e S7WR D: DINT 


Using this block, data can be written into the net (useful) data area of the 
SIMATIC S7-CPU, assigned to the FM 458 application module (periphery 
input). This PE area is 128 bytes. If the enable signal is set, the input 
value is accepted via the input and entered in the PE area. 


The offset determines at which position in the PE area, the input value is 
saved. Depending on the block- or data type, the offset is specified as 
follows: 


e for REAL data type in 4 byte steps (data length). 
value range of the offset: 0... 31 


e for BOOL data type in 1 byte steps (data length). 
value range of the offset: 0... 127 


e for INT data type in 2 byte steps (data length). 
value range of the offset: 0... 63 


e for DINT data type in 4 byte steps (data length). 
value range of the offset: 0... 31 


Output QF has the value 1, if an invalid offset was selected, or the block 
is not configured on the FM 458 application module. 


(frue 00) 
or fora feee 


C 
‘QF Error output (default: 0) 





Function Blocks - FM 458-1 DP 2-27 


Edition 12.2004 


Communication blocks 


Configuringdata Computation time [us] FM 458-1 DP 3,3 
alpene 


Can be configured in Interrupt tasks 
Cyclic tasks 


Executed in Normal mode 
Initialization mode 





2-28 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


2.4 Parameterizing SIMADYN D 


2.4.1 (ØFMPAR Parameter processing on FM 458-1 DP modules 


Symbol 


EXM448 module name. connector 
Parameter language selection 
Parameter type float to Comboard 
Parameter change enable 
BASEBOARD-Function 


Brief description 


Mode of operation 


@FMPAR 


COMBOARD status 

Block status 

Status 1.COMBOARD parameter channel 
Status 2.COMBOARD parameter channel 





The FB @FMPAR can only be configured on a FM 458-1 DP module. 

FB @FMPAR monitors the COMBOARD (communications submodule of 
the SIMOVERT MASTER DRIVES, e.g. CBP for PROFIBUS DP) and 
processes the parameter tasks which are defined for it. 


Several @FMPAR central blocks for various COMBOARDs can be 
configured on a FM 458-1 DP module. 


It should be configured in a slow sampling time (approx. 100 ms). The 
maximum permissible sampling time is 200 ms (as a result of the 
monitoring using adjacent modules). 


The existence and correction functioning of the COMBOARD is 
automatically identified and is displayed at output CS. 


Only one COMBOARD may be configured using FB @FMPAR. 


Parameter processing: 
Parameters are configured in the comment at each I/O. If the comment 
starts with "@TP_", then this I/O is designated as parameter. Every 
parameter can be allocated a parameter name (FB-PNAME). Further, a 
setting parameter can also be allocated a minimum and a maximum (FB- 
PLIM). 
The block handles the following tasks: 

e Checks the module code of the COMBOARD 

e Monitors the COMBOARD (lifebit counter) 

e Transfers the configuration data to the COMBOARD 


e Processes the parameter channels 


e In standard operation, processes the parameter tasks (in the 
sampling time cycle). 


Function Blocks - FM 458-1 DP 2-29 


Edition 12.2004 








Communication blocks 


The name of the COMBOARD which is to be processed, is configured at 
input CTS of the FB @FMPAR. If a name has not be configured at input 
CTS, then the FB @FMPAR shuts itself down with an error signal at 
output YT 1/2. 


NOTE Function blocks CRV and CTV may only be configured once. They can 
be configured on any and on different processor modules. However, 
parameter processing is possible for all processor modules. 


Initialization I/O: 








CTS Configured name of the EXM448 coupling module and connector X02, separated by ".". 
(Default: - ) 
CF Parameter data type to transfer SIMADYN D data types REAL and 


SDTIME via the parameter channel of the COMBOARD: 
e CF=1: Parameter data type, float 
e CF=0: 32-bit integer "14" 

(Default: 1) 

PLA Parameter language selection (parameter language): 





The parameter names are activated, which are configured at all PNAME 
function blocks, whose PLA input has the same value 


(Default: 0) 











Inputs: 





PEN Enables the parameter change: 


e PEN=1: allows the operator control parameters to be changed through all of the 
parameter channels 


e PEN=0: inhibits operator control parameter changes via all parameter channels 
(Default: 1) 
BBF BASEBOARD-Function 


e BBF=0: SIMATIC FM 458-1 DP operates as TECHBOARD (parameter number from 
external view 1000..1999, 3000..3999) 


e BBF=1: SIMATIC FM 458-1 DP operates as BASEBOARD (parameter number from 
external view 0..999, 2000..2999) 


(Default: 0) 














Status outputs: 








CS COMBOARD status: 
e CS=1, COMBOARD is operational. 
e CS=0, COMBOARD has failed or is not available. 


(Default: 0) 











2-30 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


Diagnose outputs: 





QTS Block status: 
e QTS=1: Block is operational and is operating error-free. 
e QTS=0: Block is shutdown due to a fault with an error output at YT1/2 


(Default: 0) 





YT1 e YT1=0: OK status 
e Initialization mode: status of the block initialization 
e Standard mode: Status of the 1“ parameter channel from COMBOARD 


For additional values, refer to: D7-SYS online help "Help on Events". (press 
the F1 key in the CFC and call-up the topic "Help on events" 
under "CFC for D7-SYS".) 


(Default: 0) 








YT2 e YT2=0: OK status 
e Intialization module: Status of the block initialization 
e Standard mode: Status of the 2" parameter channel of COMBOARD 


For additional values, refer to: D7-SYS online help "Help on events". (press key F1 in the 
CFC and call-up the topic "Help on events" 
under "CFC for D7-SYS".) 



































(Default: 0) 

Configuringdata Computation time [us] FM 458-1 DP 3,3 

Can be inserted online -- 

Can be configured in Cyclic tasks 

Executed in Initialization mode 

Normal mode 
Special features e 10<=sampling time<=200 ms 
e Block may not be switched-in or 
switched-out per task group. 

Function Blocks - FM 458-1 DP 2-31 


Edition 12.2004 


Communication blocks 


2.4.2 CBCONF COMBOARD configuration 


Symbol 


name of the module to the right 
new configuration command 
station address 
COMBOARD parameter 01 
COMBOARD parameter 02 
COMBOARD parameter 03 
COMBOARD parameter 04 
COMBOARD parameter 05 
COMBOARD parameter 06 
COMBOARD parameter 07 
COMBOARD parameter 08 
COMBOARD parameter 09 
COMBOARD parameter 10 
COMBOARD parameter 11 
COMBOARD parameter 12 
COMBOARD parameter 13 
COMBOARD parameter 14 
COMBOARD parameter 15 
COMBOARD parameter 16 
COMBOARD parameter 17 
COMBOARD parameter 18 
COMBOARD parameter 19 
COMBOARD parameter 20 
COMBOARD parameter 21 
COMBOARD parameter 22 
COMBOARD parameter 23 
COMBOARD parameter 24 
COMBOARD parameter 25 
COMBOARD parameter 26 
COMBOARD parameter 27 
COMBOARD parameter 28 


Brief description 


CBCONF I cBCONF 




























































WwW 
W 
WwW 
W 
W 
W 
W 
W 
W 
W 
WwW 
WwW 
W 
W 
WwW 
W 
W 
W 
W 
W 
W 
W 
W 
W 
W 
WwW 
W 
WwW 


e FM458 modules 


e 7400 technology module 


Configuring ona 
FM458 module 


— block status 

— status display 

— COMBOARD diagnosis 01 
— COMBOARD diagnosis 02 
— COMBOARD diagnosis 03 
— COMBOARD diagnosis 04 
— COMBOARD diagnosis 05 
— COMBOARD diagnosis 06 
— COMBOARD diagnosis 07 
— COMBOARD diagnosis 08 
— COMBOARD diagnosis 09 
— COMBOARD diagnosis 10 
— COMBOARD diagnosis 11 
— COMBOARD diagnosis 12 
— COMBOARD diagnosis 13 
— COMBOARD diagnosis 14 
— COMBOARD diagnosis 15 
— COMBOARD diagnosis 16 
— COMBOARD diagnosis 17 
— COMBOARD diagnosis 18 
— COMBOARD diagnosis 19 
— COMBOARD diagnosis 20 
— COMBOARD diagnosis 21 
— COMBOARD diagnosis 22 
— COMBOARD diagnosis 23 
— COMBOARD diagnosis 24 
— COMBOARD diagnosis 25 
— COMBOARD diagnosis 26 
— COMBOARD diagnosis 27 
— COMBOARD diagnosis 28 


FB CBCONF can be configured on the following modules: 


The function block CBCONF may only be configured once on a FM458 
module per COMBOARD. It is configured on the FM458 module on 


which the function block @FMPAR was configured for the appropriate 
COMBOARD. 


2-32 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


The block saves the configured configuration data in the admin. area of 
the COMBOARD. It executes this once after run-up and user-controlled 
in the RUN mode. In the RUN mode, it outputs diagnostics data from the 
COMBOARD at its outputs. 


Mode of operation 


New configuration data can be transferred online to COMBOARD with a 
positive edge at input SET. 


I/O 





CTR Configured name of the "righthand" adjacent module (initialization connection). The 
following data can be entered: 


e CTR=0if an adjacent module was not configured 

e CTR=<module name> or 

e CTR=<module name>.<connector> if an adjacent board is configured. 
(default value: - ) 


SET The configuration data is transferred online to the COMBOARD with a rising 
edge at this input. 





(Default value: 0) 





MAA The station number should be assigned depending on the particular protocol 
(e.g. USS: 0..30, PROFIBUS DP: 3..125). 


(Default value: 0) 

P01...P28 Max. 28 additional COMBOARD-specific configuration parameters. 
(Default value: 0) 

QTS Block status: 

e QTS = 1: Block is operational. 

e QTS = 0: The block is disabled with an error output at YTS 








(Default value: 0) 





YTS Status display, possible values 
e -0: OK status 
e -7CB3: T400 operates as TECHBOARD and a BASEBOARD is available 


Additional values, refer to: D7-SYS Online Help "Help on events" (press key F1 in the CFC 
and call-up the topic "Help on events" under "CFC for SIMADYN D".) 


(Default value: 0) 
D01...D28 Max. 28 words of diagnostics data of the COMBOARD 
(Default value: 0) 

















Function Blocks - FM 458-1 DP 2-33 
Edition 12.2004 


Communication blocks 


Significance of the 
configuring input 


The "CB-Param" and "SCB-Param" columns establish the assignment to 
the COMBOARD User Manuals. 






















































































for several 
COMBOARDs 
Input CB-Param CB1: CBP: CBP2: CBP2: CB2: 
new/old DP DP DP USS CAN 
MAA P918 Bus address |Bus address |Bus address Bus address |Bus address 
P01 P711/ (not used) Diagnostic Diagnostic - PKW task 
P696 selection selection 
P02 P712/ PPO-Typ PPO-Typ PPO-Typ - PZD 
P697 receive 
P03 P713/ (END) (END) Protocol selection: PZD send 
P698 0: Profibus-DP 
2: USS 
P04 P714/ SIMATIC OP - PZD 
P699 writes in: send length 
0: EEPROM 
1. RAM 
P05 P715/ Slave to slave - PZD 
P700 data transfer send rate 
failed: 
0: Error 
1: Warning 
P06 P716/ (END) - PZD 
P701 receive 
Broadcast 
P07 P717/ - PZD 
P702 receive 
Multicast 
P08 P718/ Baud rate PZD 
P703 6=9,6 receiver 
kBaud cross 
7=19,2 
kBaud 
8 = 38,4 
kBaud 
P09 P719/ PKW: 0:no, PKW task 
P704 127:yes, Broadcast 
3:one word, 
4:one D word 
P10 P720/ PZD: Baud rate 
P705 No. of words 
P11 P706.1 (END) CAN layer 
P12 P706.2 Bus timing 
P13 P706.3 (END) 
P14 P706.4 
P28 
2-34 Function Blocks - FM 458-1 DP 


Edition 12.2004 


Communication blocks 

































































Input SCB- SCB2: SCB2: SCB1: 
Param |USS-Slave Peer CAN 

MAA P683.2 |Bus address | (not used) 

P01 P682 SCB1/SCB2-protocol selection: 
0:CAN, 1:USS 4-wire, 
2:USS-2-wire, 3:Peer 

P02 P685.2 | PKW: 0:no, (not used) 
127:yes, 
3:one word, 
4:one D word 

P03 P686.2 | Process data: | (not used) 

No. of words 

P04 P684.2 | Baud rate 

P05 P687.2 | Telegram failure time 

P06 (END) (END) 

P07 

P08 

P09 

P10 

P11 

P12 

P13 

P14 

P28 























Significance of the Refer to the COMBOARD User Manuals 
diagnostic outputs 





























Configuringdata Computation time [us] FM458-1 DP 3,3 
Can be inserted online -- 
Can be configured in Cyclic tasks 
Executed in Initialization mode 
Normal mode 
Special features e The block can only be configured once for 
each communications submodule. 
e Additional block required on the CPU 
modules: @FMPAR 
Function Blocks - FM 458-1 DP 2-35 


Edition 12.2004 


Communication blocks 


2.4.3 CBRFAW Receiving warnings from a COMBOARD 


Symbol 









CBRFAW 


EXM448 module name, connector + GV CTS CW W|- COMBOARD alarms 96 - 81 
QTS| BO|- Module status 
YTS W|- Status, COMBOARD alarm 
channel 


Brief description e The block can only be configured on a FM458 module. 


e This block receives warnings A81 to A96 of a COMBOARD 
(communications submodule of SIMOVERT MASTER DRIVES, e.g. 
CBP2 for PROFIBUS DP). 


e Input CTS of the CBRFAW function block is used to define from which 
COMBOARD the warnings are to be received. 


e Function block CBRFAW may only be configured on a FM458 module 
of each COMBOARD. It is configured on the FM458 module, on which 
a @FMPAR function block was also configured for the appropriate 
COMBOARD. 


I/O Initialization inputs: 





CTS Configured name of the EXM448/EXM448-2 module and connector X01 or X02, separated by 








(Default: - ) 
Outputs: 
CW Outputs COMBOARD warnings A81 to A96 
(Default: 0) 





QTS Block status: 
e QTS=1: Block is being processed and is operating error-free. 
e QTS=0: Block is shut down due to a fault with error output at YTS. 


(Default: 0) 


YTS Status of the COMBOARD warning channel: 


YTS=0: OK condition 
For additional values, refer to: D7-SYS online help "Help on events". (press the F1 key in the 
CFC and call-up the topic "Help on events" under "CFC for SIMADYN D".) 


(Default: 0) 

















2-36 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Configuringdata 


Communication blocks 





Computation time [us] 


FM458-1 DP 3,3 





Can be inserted online 





Can be configured in 


Cyclic tasks 





Executed in 


Initialization mode 
Normal mode 








Special features 





e The block can only be configured once for 
each communications submodule. 


e Additionally required block: 
@FMPAR 








Function Blocks - FM 458-1 DP 


Edition 12.2004 


2-37 


Communication blocks 


2.4.4 PNAME Parameter names 


Symbol 


parameter language selection 


Brief description 


Mode of operation 


2-38 


parameter name 1 
parameter name 2 
parameter name 3 
parameter name 4 
parameter name 5 
parameter name 6 
parameter name 7 
parameter name 8 
parameter name 9 
parameter name 10 
parameter name 11 
parameter name 12 
parameter name 13 
parameter name 14 
parameter name 15 
parameter name 16 
parameter name 17 
parameter name 18 
parameter name 19 
parameter name 20 


l 

S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 
S 





— status output 


The block is required to configure names for parameters. 


The PNAME function block can be configured on the following modules: 


e T400 technology module (@DRIVE function block is required) 


e FM module 


(@FMPAR function block is required) 


The block can be configured in the slowest sampling time. 


The block saves the configured names in the parameter list of the 


function block @FMPAR, and then disables itself. 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


I/O 


Communication blocks 


Parameter language selection (parameter langage): The configured parameter names are 
exactly activated when the data coincides with the PLA input at the @FMPAR block. 
(Initialization input) 

(Default value: 0) 


The parameter number and the parameter name, separated by a colon are specified 
at the Nnn inputs. Example: "H123: parameter name". The parameter number must 
always consists of a letter (H or L) and three digits. The parameter name should be 
a maximum of 16 characters long; longer names will be cut-off and shorter names, 
filled with blanks. . 


(Initialization input) 
(Default value: Empty string) 


Status display, possible values 
- 0: OK status (all of the names are activated). 
Alarms: 


- 1: The names are not activated, as another language is set at function block @FMPAR 

- 2: For at least one parameter number, there is no parameter (the name is ignored) 
Additional values, refer to: D7-SYS Online Help "Help on events" (press key F1 in the CFC 
and call-up the topic "Help on events" under "CFC for SIMADYN D") 


(Default value: 0) 





Configuringdata Computation time [us] FM 458-1 DP 3,3 


Can be configured in Cyclic tasks 


Executed in Initialization mode 
Normal mode 





Special features additionally required block on the FM 
modules: @FMPAR 


Function Blocks - FM 458-1 DP 2-39 
Edition 12.2004 


Communication blocks 


2.4.5 PSTAT Change enable for parameters 





Symbol 
Password W |- Access level 
Level 1 — Device status 
Level 2 — Status display 
Level 3 
Level 4 
Level 5 
Level 6 
Level 7 
Level 8 
Device status 
Brief description Using the function block, the following can be realized 
e a current device status can be configured, 
e the access level can be defined by entering a password, 
e the device status and the access level is used to define whether a 
parameter may be changed. 
The statuses and access level, in which a parameter is to be inhibited or 
enabled, are defined using the PLIM function block. 
Function block PSTAT may only be configured once in each FM module. 
I/O 


Current password: 


If password PSW does not coincide with the PWi values, then this corresponds to access level 
0: this does not permit any change. 


If password PSW coincides with a value of PWi, then this corresponds to access level i and all 
lower access levels. 


In access level 8, there are no access authorizations as a result of the access level (all other 
access restrictuions, e.g. using the device status, are retained). 


(Default: 0) 


Appropriate password for access level i (password i): 
(Default: 0) 


Actual "device status": There are 16 statuses. 


Permissible entry range: 1 to 16 
(Default: 1) 





2-40 Function Blocks - FM 458-1 DP 
Edition 12.2004 


Communication blocks 


Actual access stage i (word level): 


The access stage i, determined by the entry at input PSW, is output as binary value. For access 
stage n, bit n is set to 1 and all of the other 15 bits, are set to 0. 


e.g. for access level = 7, WLVcorresponds to 240000000001000000. 
(Default: 240000000000000000) 
Device status (word state): 


The actual device status STE is output as a binary value. For the current device status ST=n, bit 
nis set to 1 and all of the other 15 bits are set to 0. 


e.g. for STE=7, WST corresponds to 24000000001000000. 
(Default: 240000000000000001) 


Status display: 
7C72: Function block is configured several times 
7CA9: no @FMPAR function block configured 
7CC3: one or several incorrect entries were made at input PWi 
7CC4: illegal entry at input STE 
(Default: 0) 


For additional values, refer to: D7-SYS online help "Help on events". (press 
key F1 in the CFC and call-up the topic "Help on events" under 
"CFC for SIMADYN D".) 





Configuringdata Computation time [us] FM 458-1 DP 3,3 


Can be configured in Alarm-Tasks 
Cyclic tasks 

Executed in Initialization mode 
Normal mode 


Special features e Function block may only be configured once 
per FM module 


e Function block additionally required on the 
FM modules: 
@FMPAR and PLIM 





Function Blocks - FM 458-1 DP 2-41 
Edition 12.2004 


3 Logic blocks 


3.1 SAV TR Save FB for NOV RAM 


Symbol 


SAV TR FT SAv IR 


input variable JR X Y R |— output variable 
mode of operation BO |M QF| BOl|- no available memory 


Brief description A REAL type quantity is saved in the NOV-RAM of a technology module. 





Mode of operation The function block is a read/write memory for a REAL value. It is only 
active, if a 0 at output QF indicates that the memory space in the 
NOVRAM is available. The function block operating mode is selected at 
input M: 


Write operating 


e The quantity to be saved is entered at input X. It is transferred to 
mode (M = 1) oer R 


output Y. 


e Further, input quantity X is entered in the NOV-RAM of the module. In 
this case, a value, already contained in the NOV-RAM is overwritten. 


Read operating e The last input quantity, saved in the write operating mode, is output 
mode (M = 0) at Y. 


e The NOV-RAM is deleted from the operating system each time the 
configured software changes (even when the system is configured for 
the first time), i.e. Zeros are written into it. If the NOV-RAM is then 
read, without having previously written a value into the NOV RAM, 
then the initialization value of the NOV RAM (zero) is output at Y. 


INIT Operating In the INIT operating mode of the function block, memory is made 

mode available to accept a REAL value. Output QF is set to 1 if this is not (no 
longer) possible. The function block is then inactive in the RUN operating 
mode. 

I/O 


Input quantity (default: 0.0) 
MM | Operating mode (default: 0) 


Output quantity (default: 0.0) 
Gr No free memory (default: 0) 





Function Blocks - FM 458-1 DP 3-1 
Edition 03.2003 


Logic blocks 


Configuringdata Computation time [us] FM 458-1 DP 0,6 


Can be configured in Interrupt tasks 
Cyclic tasks 


Executed in Initialization mode 
Normal mode 





3-2 Function Blocks - FM 458-1 DP 
Edition 03.2003 


Logic blocks 


3.2 PAS7 Initiate process interrupt at the S7-CPU 


Symbol 


Supplementary interrupt info 
Reset error 

Trigger mode 
Initiate interrupt 


Brief description 


Mode of operation 


NOTE 


I/O 


Configuringdata 


— error output 





This function block, which initiates a process interrupt to the SIMATIC 
S7-CPU, can only run with an FM 458-1 DP application module. 


The function block initiates a process interrupt at the associated S7 CPU. 


The IFO double word is transferred to the S7-CPU as supplementary 
interrupt information. 


A process interrupt is only acknowledged after the process interrupt 
OBs (organization block) has been executed on the S7-CPU. 

The block does not wait for the acknowledgment. The OB is 
parameterized in the HWConfig for the associated S7-CPU. 


The process interrupt is only initiated, if the S7-CPU is not processing a 
process interrupt from the FM 458-1 DP application module. 


Output QF has the value 1, if a new process interrupt is initiated, 
although the last process interrupt was still not acknowledged or the 
block was not configured on FM 458-1 DP. 


Output QF has the value 0, if the acknowledgment from the S7-CPU has 
been received, or if input RES has the value 1. 


The interrupt is initiated as a function of the input TMB: 
e for TMB = 0, if a signal changes from 0 to 1 at input I, or. 
e for TMB = 1, if any signal transition occurs at input I. 


i Supplementary interrupt information (default: 0) 


Res freser o 
1 [rite aninterupt loew 
lar femora feat 


Computation time [us] | FM 458-1 DP 3,3 


Can be configured in Interrupt tasks 
Cyclic tasks 





Function Blocks - FM 458-1 DP 3-3 


Edition 03.2003 


4  Service-/diagnostic blocks 


4.1 FMLED Control FM 458-1 DP diagnostics LED 


Symbol 


LED (user error 

LED (online monitoring 

LED (communications error 
LED (sampling time overflow 


Brief description 


Mode of operation 


— error output 





The function block, which controls the FM 458-1 DP diagnostic LEDs, 
can only run with an FM 458-1 DP application module. 


The LEDs of the FM 458-1 DP application module can be controlled 
using this block. 


The LED display is canceled for a value of 0 at the appropriate input; for 
a value of 1, it is set and for a value of -1, its status is retained, 
unchanged. The value of -1 is required, as this block has been configured 
a multiple number of times. 


Output QF has the value 1, if the inputs have invalid values, or if the 
block is not configured on the FM 458-1 DP application module. 





vo AW 
far T 
Configuringdata FM 458-1DP 1,0 
Cyclic tasks 
Initialization mode 
Ee 
Function Blocks - FM 458-1 DP 4-1 


Edition 03.2003 


5  SIMOLINK drive coupling 


5.1 (OSL SIMOLINK central block 





Symbol 
Hardware address SLB I |- Error status of the block 
Operating mode I | No. of nodes 
Node address DI |- No. of cycles 
Send power DI |- No. of overruns 
Filling-up the telegram gaps DI |- No. of timeouts 
Use PCI Copy DI |- No. of CRC errors 
Max. blocksize DI |- No. of the defective module 


Enable the drive interface DI |-- No. of waiting cycles 


Brief description 


Mode of operation 





DI |- No. of CO1 overruns 
BO |-- Group error bit 


The @SL central block allows the initialization and monitoring of 
communications with an SLB module. 


An SLB module is a system hardware component, which can be an ITSL- 
, an EXM 448-1 module or an optional SLB (SIMOLINK Board) of the 
ITSL module. 


The @SL central block may only be configured in a cyclic task and once 
per SIMOLINK ring. 


The following parameters must be set for an SLB module: 


Function Blocks - FM 458-1 DP 


Edition 12.2004 


Hardware address SLB (TAD) 


Operating mode (MOD) 


Node address (ASL), only relevant when operating mode 0 is selected 


Send power (POW) for the SLB module 


The @SL central block executes the following steps while the system 
is being initialized: 


Checks the validity of the value ranges at the input connections 


Checks whether additional @SL central blocks have been 
configured at the same hardware address (input TAD) 


Initializes the SLB module corresponding to the data at the 
initialization connections 


SIMOLINK drive coupling 


— Sends an initialization sequence (SIMOLINK) and monitors the 
starting sequence 


2. The @SL central block executes, in the standard mode ("RUN“ 
operating status) of the system, the following operating steps: 


— Monitors communications of the SIMOLINK drive interface 


— Outputs fault messages when communication faults occur at the 
outputs 


— Outputs information about the drive coupling 


— New values for the node address (ASL) and send power (POW) 
are only transferred after the SIMOLINK drive coupling restarts. 


Operating mode An SLB module can be initialized and can operate in 6 different operating 





modes. 


When configuring, the different time characteristics of the SIMOLINK 
blocks for the selected operating modes at input MOD. 


Slave mode 


The SLB module operates as slave. The SIMOLINK blocks in the CFC chart must be configured 
in an interrupt task Ix (x=1 . . . 8). 


Timing: an interrupt is initiated each time a SYNC telegram is received, and therefore starts 
execution of interrupt task Ix. The received values are read and the values to be sent are written 
into the write buffer of the SLB module. 

SYNC telegram SYNC telegram SYNC telegram 


SIMOLINK cycle SIMOLINK cycle 


Processing time of the Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks SIMOLINK blocks 


Interrupt task Ix 












































Asynchronous mode 


The SLB module operates as master. The SIMOLINK blocks in the CFC chart must be 
configured in a cyclic task Tx (x=1... 5). 


Timing: The blocks are executed each time cyclic task Tx starts. The SIMOLINK telegrams are 
sent after the last SIMOLINK block has been calculated. 























SIMOLINK cycle SIMOLINK cycle 


Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks 

















Cyclic task Tx 


Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


Timer mode 
The SLB module operates as master. The SIMOLINK blocks in the CFC chart must be 
configured in an interrupt task Ix (x=1 . . . 8). 


Timing: A timer of the ITSL/EXM 448-1 module initiates, corresponding to the equivalent 
sampling time, an interrupt, and therefore execution of interrupt task Ix. The SIMOLINK 
telegrams are sent after the last SIMOLINK block has been calculated. 

Timer interrupt Timer interrupt 


Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks 


Interrupt task Ix 


























Automatic mode 


The SLB module operates as master. The SIMOLINK blocks in the CFC chart must be 
configured in an interrupt task Ix (x=1.. . 8). 


Timing: Each SYNC telegram which is received, initiates an interrupt, and therefore execution of 
the interrupt task Ix. The SIMOLINK bus cycle is automatically re-initiated each time a SYNC 
telegram is received. SIMOLINK telegrams are sent and received in parallel with the signal 
processing (internal calculations). 

SYNC telegram SYNC telegram 


ý 


Processing time of the Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks SIMOLINK blocks 


Interrupt task 











External mode 


The SLB module operates as master. The SIMOLINK blocks in the CFC chart must be 
configured in an interrupt task Ix (x=1.. . 8). 


Timing: The bask clock cycle TO from the system initiates that telegrams are sent, and therefore 
the start of the SIMOLINK cycle. A subsequently received SYNC telegram initiates an interrupt 
and therefore execution of interrupt task Ix. The signal processing (internal calculations) are 
realized after the SIMOLINK telegram has been sent and received. 

TO interrupt SYNC telegram TO interrupt SYNC telegram 








Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks 


Interrupt task Ix 

















Basic clock cycle TO 


External cyclic mode 


The SLB module operates as master. The SIMOLINK blocks in the CFC chart must be 
configured in a cyclic task T1=T0. 

Timing: The basic clock cycle TO initiates that telegrams are sent (starts the SIMOLINK cycle) 
and the SIMOLINK blocks are processed in T1=T0. The signals are processed (internal 
calculation) at the same time as sending and receiving SIMOLINK telegrams. 

TO interrupt TO interrupt TO interrupt 


7 


Processing time of the Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks SIMOLINK blocks 


Cyclic task T1 = TO 














Function Blocks - FM 458-1 DP 5-3 
Edition 12.2004 


SIMOLINK drive coupling 


Cyclic-automatic-mode 10 


The cyclic-automatic-mode 10 offers the advantage to place the function block configuration in 
cyklic tasks, in opposed to mode 3. 
SYNC Telegram SYNC Telegram 








SIMOLINK cycle SIMOLINK cycle SIMOLINK cycle 


Processing time of the Processing time of the Processing time of the 
SIMOLINK blocks SIMOLINK blocks SIMOLINK blocks 


cyclic Task Tx 



































NOTE It is necessary to set interrupt task sources for operating modes 
0, 2, 3, 4 and 10, in order to initiate the configured interrupt tasks. 
The settings must be made in the HWConfig in the properties 
window under the "Interrupt tasks" tab. They are dependent on 
the configured hardware components. 


interrupt task 
settings 


Interrupt source to be set for the interrupt task Ix of the SIMOLINK blocks, if: 


Operating first SLB module at | first SLB module at second SLB second SLB 
mode slot 1 slot 2 module at slot 1 module at slot 2 


| o | LE bus interrupt 1 LE bus interrupt 3 LE bus interrupt 2 | LE bus interrupt 4 
LE bus interrupt 5 LE bus interrupt 6 LE bus interrupt 7 | LE bus interrupt 8 
LE bus interrupt 1 LE bus interrupt 3 LE bus interrupt 2 | LE bus interrupt 4 


4 LE bus interrupt 1 LE bus interrupt 3 LE bus interrupt 2 | LE bus interrupt 4 





NOTE The first SLB module can be an EXM 448-1- or an ITSL module 
without optional SLB. The settings for the second SLB module 
are only relevant for an ITSL module with optional SLB. 


5-4 Function Blocks - FM 458-1 DP 
Edition 12.2004 


1/0 





SIMOLINK drive coupling 


Hardware address SLB (name of the SLB module), which can be 
configured in HWConfig. 
Operating mode (default: 0) 
Sets the required operating mode 
(initialization connection) 
) 


Node address (default: 0 
Address of the slave (1 . . . 200) in the SIMOLINK ring (this is only 

relevant, if operating mode 0 was selected at MOD) 

(initialization connection) 


Send power (default: 3) 
Send power of the SLB module (if a lower send power is used, the 

aging processing of the fiber-optic cables is slowed down and errors in 

the medium can be more easily identified at start-up). Value range: 1. . 

. 3 (small, medium large); 

(initialization connection) 

Filling-up the telegram gaps (default: 0) 
For FIL=1, if there is a gap between two bus cycles, then this is 

filled-up with NOP telegrams. 

Note: if the sampling time TO is synchronized, then filling-up only 

operates correctly if the equivalent sampling time is precisely set to 

the value of the cycle time that is used for synchronization. 

(initialization connection) 


Use PCI Copy (default: 0) 
1 = Data with PCI Copy read 
0 = Data normal read 
max. blocksize (default: 15) 
Max. blocksize for a PCI Copy block 
Bus enable (default: 1) 
Start/stop of the SLB module for telegram data transfer 
EN=0 no telegrams are sent 

telegrams are sent corresponding to the selected operating 
Error status of the block (default: 0) 
YF=0 No error, YF > 0 refer to coded error output 
Number of nodes (default: 0) 
Number of nodes in the SIMOLINK ring 
(including SL master) 
Number of cycles (default: 0) 
Number of SIMOLINK cycles which have been executed or the number 
of SIMOLINK telegrams 


Number of overruns (default: 0) 
The number of statuses, where the configured function blocks have not 

be able to provide the data or retrieve the data up to the start of the 

next SIMOLINK cycle. The data remains consistent, even for errors 

such as these and the SIMOLINK cycle is started with old data. 

In order to resolve this problem, the interrupt tasks, in which the 

SIMOLINK blocks were configured, must be relieved. 


No. of timeouts on the SIMOLINK ring (default: 0) 
A timeout means that a telegram has failed (not been received). 
Number of CRC errors in the SIMOLINK ring (default: 0) 

A node sends a telegram with a CRC error. 


Function Blocks - FM 458-1 DP 5-5 


Edition 12.2004 


SIMOLINK drive coupling 


Me | Number of the defective module and/or node that detected the fault in | (default: 0) 
the line. 


No. of waiting cycles (default: 0) 
The number of the processor cycles specifies while the values by PCI 


Copy are being waited for. 


No. of CO1 Overruns (default: 0) 


Group error bit (default: 0) 
QF=0 No error, QF=1 for error (if YF+0) 





5-6 Function Blocks - FM 458-1 DP 
Edition 12.2004 


coded error output 


SIMOLINK drive coupling 


Error statuses which occur for the appropriate block are output in a 
coded form at outputs YF of the SIMOLINK blocks. Only the last error 


event is displayed. 


Value 


19 


20 
21 
22 
23 


30 


31 


32 
33 


Function Blocks - FM 458-1 DP 
Edition 12.2004 





Significance 

TAD input is incorrectly connected 

SLB module not inserted or hardware defective 

SLB module is already being used by another central block @SL 
Memory problem 

Central block @SL not configured 

No SIMOLINK block available 

Memory register was not set-up 

Software does not support the hardware combination 
Block must be configured in an interrupt task 

Block must be configured in a cyclic task 

Block must be configured in a cyclic task with TX=TO 


Equivalent sampling time must be equal to TO 


Interrupt source for the alarm task is incorrect 


Blocks must be configured in the same sampling time 
Operating mode is (still) not supported 
Node address at input ASL is too high 
No send- and receive blocks available 


Note: However, if send and receive blocks are configured, then the 
fault messages at these blocks should be carefully observed! 


Maximum number of SIMOLINK telegrams (max. 1021 net 
telegrams) exceeded — increase SIMOLINK cycle time or configure 
fewer SIMOLINK blocks 


Slave address too high 
Channel number too high 
Slave attempts to write to the incorrect address 


Cross-data transfer is only possible in one direction per slave 
(sending or receiving) 


Physical data transfer along the SIMOLINK ring is faulted 
— increase the send power at one of the partial segments, or the 
fiber-optic cable medium or connector is defective 


CRC error (check sum error) 
Timeout error in the SIMOLINK ring 


Only for MOD=0: signaled SIMOLINK cycle time (in the special 
telegram from the SL master) does not correspond to the configured 
equivalent sampling time 


5-7 


SIMOLINK drive coupling 


Configuringdata Computation time [us] FM 458-1 DP 69,3 
Can be configured in Cyclic task 


Executed in Initialization mode 
Normal mode 





5-8 Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


5.2 SLAV, SLAVE R SIMOLINK receive block for one actual 
value 


Symbol 


— Actual value from slave 0 
— Actual value from slave 1 
— Actual value from slave 2 
— Actual value from slave 3 
— Actual value from slave 4 
— Actual value from slave 5 
— Actual value from slave 6 
— Actual value from slave 7 
I |- Sequence number 

I |-- Block error status 

BO |-- Group error bit 


Hardware address SLB 

Address of the first slave 

Number of slaves 

Channel number for the actual value 
Enable cross-data transfer 







Brief description A max. of 8 actual values can be transferred from max. 8 slaves using 
the SLAV receive block. Each slave can only receive one actual value, 
and for all of the slaves, only the same channel number is addressed. 


The SLAVE and SLAVE_R function blocks are functionally identical. The 
only difference is the data type of the actual value connections YAO to 
YAT: 

SLAVE: DINT 

SLAVE R: REAL 


Mode of operation 1. The SLAV function block executes the following steps while the 
system is being initialized 
— Checks the task assignment, 


— Initializes the task list of the SLB module corresponding to the data 
configured at the inputs 


2. In the normal system mode ("RUN* operating status), the SLAV 
function block executes the following steps: 


— Checks that the inputs are within the permissible value range 


— Reads-out the actual values to be received from the receive buffer 
of the SLB module# 


Function Blocks - FM 458-1 DP 5-9 
Edition 12.2004 


SIMOLINK drive coupling 






SLB hardware address (name of the SLB module), which can be 
configured in HWConfig 
Address of the first slave from which the actual value YAO should (default: 1) 
be received, value range 1. . . 200 
(initialization connection) 
) 


No. of slaves, from which actual values are to be received, (default: 1 
value range 1...8 
(initialization connection) 


I/O 

NSL 

CSV Channel number on which the actual value is received, (default: 0) 
value range 0...7 
(initialization connection) 

Qv Enable cross-data transfer (default: 0) 
This is used, if data is to be sent to a slave in the same cycle which 
is physically located in front in the SIMOLINK ring (e.g. from slave 4 
to slave 1). 


YAO to Actual value YA from slaves 1 to 8 (default: 0) 
YA7 A maximum of 8 actual values can be received. 


Sequence number (default: 0) 
Number of the block in the SIMOLINK block sequence 

The value supplies info as to whether the block was correctly 

initialized. 


Error status of the block (default: 0) 
no error, YF > 0 refer to coded error output @SL 





Group error bit (default: 0) 
QF=0 no error, QF=1 for error (if YFz0) 


Configuringdata Computation time [us] FM 458-1 DP 34,7 


Can be configured in Interrupt tasks 
Cyclic tasks 


Executed in Initialization mode 
Normal mode 





5-10 Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


5.3 SLD SIMOLINK delta evaluation 


Symbol 


— Delta time 

— Delta time, max. 
— Delta time, min. 
I|- Sequence number 
I |- Block error status 
BO |— Group error bit 


Hardware address SLB 







Brief description A sampling time failure can be detected using function block SLD. The 
counter status is interrogated at each SYNC interrupt (this is generated at 
the end of every telegram cycle). The block can calculate and output the 
difference to the old (previous) value. 


Mode of operation The blocks reads the interrogated value of the counter and generates the 
difference to the value which was saved in the old (previous) cycle. This 
value is output at DT. 

The minimum and maximum values of DT are kept for monitoring 
purposes. 


SLB hardware address (name of the SLB module), which can be 

configured in HWConfig 

Delta time (default: 0) 
Difference to the last SIMOLINK cycle duration 


Delta time, max. (default: 0) 
Maximum value of DT 


Delta time, min. (default: 0) 
Minimum value of DT 


Sequence number (default: 0) 
Number of the block in the SIMOLINK block sequence 

This value provides information as to whether the block was correctly 

initialized. 


YF Error status of the block (default: 0) 

YF=0 no error, YF > 0 refer to coded error output @SL 
Group error bit (default: 0) 
QF=0 no error, QF=1 for error (if YFz=0) 


Configuringdata Computation time [us] FM 458-1 DP 19,8 


Can be configured in Interrupt tasks 
Cyclic tasks 





Executed in Initialization mode 
Normal mode 





Function Blocks - FM 458-1 DP 5-11 
Edition 12.2004 


SIMOLINK drive coupling 


5.4 SLDIS SIMOLINK dispatcher 





Symbol 
Hardware address SLB — Sequence number 
Number of slaves — Block error status 
Number of channels — Group error bit 
Enable cross-data transfer 

Brief description A dispatcher mode is prepared in-line with the SIMOLINK specifications 
(as for MASTERDRIVES drive converters) using the SLDIS function 
block. 

Mode of operation The block registers the telegrams for all NSL slaves and all NCN 
channels. 

I/O 

TAD Hardware address SLB (name of the SLB module), which can be 


configured in HWConfig 


NSL Number of all of the slaves in the SIMOLINK ring (default: 1) 
(initialization connection) 

NCN Number of all of the channels (default: 1) 
(initialization connection) 


Enable cross-data transfer (default: 0) 
This is used, if data are to be sent to a slave in the same cycle, which 

is located physically in front in the SIMOLINK ring (e.g. from slave 4 

to slave 1). 

Sequence number (default: 0) 
Number of the block in the SIMOLINK block sequence 

This value provides information as to whether the block was correctly 

initialized. 


Error status of the block (default: 0) 
no error, YF > 0 refer to coded error output @SL 

Group error bit (default: 0) 

QF=0 no error, QF=1 for error (if YFz0) 


Configuringdata Computation time [us] FM 458-1 DP 14,7 


Can be configured in Interrupt tasks 
Cyclic tasks 





Executed in Initialization mode 
Normal mode 





5-12 Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


5.5 SLSV, SLSV R SIMOLINK send block for one setpoint 


Symbol 


Hardware addresse SLB 
Address of the first slave 
Number of slaves 
Channel number for the setpoint 
Setpoint at slave 0 
Setpoint at slave 1 
Setpoint at slave 2 
Setpoint at slave 3 
Setpoint at slave 4 
Setpoint at slave 5 
Setpoint at slave 6 
Setpoint at slave 7 


— Sequence numbedr 
— Block error status 
— Group error bit 





Brief description A maximum of 8 setpoints can be transferred to a maximum of 8 slaves 
using the SLSV send block. Only one setpoint can be sent to each slave, 
and for all of the slaves, only the same channel number can be 
addressed. 


The SLSV and SLSV_R function blocks are functionally identical. The 
only difference is the data type of the setpoint connections XSO to XS7: 
SLSV: DINT 
SLSV_R: REAL 


Mode of operation 1. The SLSV send block executes the following steps while the system is 
being initialized: 
— Checks the task assignment 


— Initializes the task-list of the SLB module corresponding to the data 
configured at the inputs 


2. In the normal system mode ("RUN" mode), the SLSV send block 
executes the following: 


— Calculates the setpoints 


— Checks that the inputs are within the permissible value ranges 


Enters the setpoints to be sent into the write buffer of the SLB 
module 


Function Blocks - FM 458-1 DP 5-13 
Edition 12.2004 


SIMOLINK drive coupling 


I/O 


Hardware address SLB (name of the SLB module), which can be 
configured in HWConfig 
Address of the first slave to which setpoint XSO should be sent, (default: 1) 
value range 1... 200 
(initialization connection) 
) 


Number of slaves to which the setpoint should be sent, (default: 1 
value range 1... 8 
(initialization connection) 


Number of the channel on which the setpoint is sent, (default: 0) 
value range 0... 7 
(initialization connection) 


Setpoint XS for slaves 1 to 8, (default: 0) 
A maximum of 8 setpoints can be sent. 

Sequence number (default: 0) 
Number of the blocks in the SIMOLINK block sequence 

This value provides information as to whether the block was correctly 

initialized. 


Error status of the block (default: 0) 
YF=0 no error, YF > refer to coded error output @SL 

Group error bit (default: 0) 
QF=0 no error, QF=1 for error (if YFz0) 





Configuringdata Computation time [us] FM 458-1 DP 34,7 


5-14 


Can be configured in Interrupt tasks 
Cyclic tasks 


Executed in Initialization mode 
Normal mode 





Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


5.6 SLSV2, SLSV2R SIMOLINK send block for 2 setpoints 


Symbol 


Hardware addresse SLB 
Address of the first slave 

No. of slaves 

Axix cycle length 

Channel number for setpoint 2 
Channel number for the setpoint 
Common setpoint of the main angle 
Setpoint offset for slave 0 
Setpoint offset for slave 1 
Setpoint offset for slave 2 
Setpoint offset for slave 3 
Setpoint offset for slave 4 
Setpoint offset for slave 5 
Setpoint offset for slave 6 
Setpoint offset for slave 7 


— Sequence number 
— Block group error status 
— Group error bit 





Brief description 2 setpoints can be sent to each slave using the SLSV2 send block. In this 
case, the block can handle a maximum of 8 slaves. The first setpoint is 
transferred to all of the 8 slaves. 


This functionality can be used to implement a virtual shaft, especially if 
the time and the position/angular setpoint must be transferred to the 
slaves. 


The SLSV2 and SLSV2R function blocks are functionally identical. The 
only difference is the data type of the setpoint connections XO0 to XO7: 
SLSV2: DINT 
SLSV2R: REAL 


Mode of operation 1. The SLSV2 send block executes the following steps while the system 
is being initialized: 
— Checks the task assignment 


— Initializes the task list of the SLB module corresponding to the data 
configured at the inputs 


2. In the normal system mode ("RUN" mode), the SLSV2 send block 
executes the following steps: 


— Calculates the setpoints 
— Checks that the inputs are within the permissible value ranges 


— Enters the setpoints to be sent into the write buffer of the SLB 
module 


Function Blocks - FM 458-1 DP 5-15 
Edition 12.2004 


SIMOLINK drive coupling 


I/O 
Hardware address SLB (name of the SLB module), which can be 
configured in HWConfig 
Address of the first slave to which setpoint XOO should be set, value | (default: 1) 
range 1... 200 
(initialization connection) 
) 


Number of slaves to which the setpoint should be sent, value range (default: 1 
1...8 
(initialization connection) 


Axis cycle length (default: 0) 
Upper integrator limit value 

Channel number for setpoint 2, value range 0...7 (default: 0) 
(initialization connection) 


Number of the channel on which the setpoint is sent, (default: 0) 
Value range 0...7 

(initialization connection) 

Common setpoint XS of the main angle/position for all NSL slaves (default: 0) 


Setpoint offset XO for slaves 1 to 8, (default: 0) 
A maximum of 8 setpoint offsets can be sent. 

Sequence number (default: 0) 
Number of the block in the SIMOLINK block sequence 


This value provides information as to whether the block was correctly 
initialized. 


Error status of the block (default: 0) 
YF=0 no error, YF > 0 refer to coded error output @SL 

Group error bit (default: 0) 
QF=0 no error, QF=1 for error (if YF #0) 


Configuringdata Computation time [us] FM 458-1 DP 39,6 


Can be configured in Interrupt tasks 
Cyclic tasks 





Executed in Initialization mode 
Normal mode 





5-16 Function Blocks - FM 458-1 DP 
Edition 12.2004 


SIMOLINK drive coupling 


5.7 SLSVAV SIMOLINK send and receive block for one slave 


Symbol 


Hardware addresse SLB 
addresse of the slave 
Number of send channels 
Number of receive channels 
setpoint at channel 0 
setpoint at channel 1 
setpoint at channel 2 
setpoint at channel 3 
setpoint at channel 4 
setpoint at channel 5 
setpoint at channel 6 
setpoint at channel 7 


Brief description 


Mode of operation 


SLSVAV 


Actual value from slave 0 
Actual value from slave 1 
Actual value from slave 2 
Actual value from slave 3 
Actual value from slave 4 
Actual value from slave 5 
Actual value from slave 6 
Actual value from slave 7 
Sequence number 

Block error status 

Group error bit 





A maximum of 


e 8 setpoints and 


e 8 actual values 


can be transfered to and from one slave. The number of addressed 
channels for the setpoints and the actual values is configured at the 
inputs. 


1. 


Function Blocks - FM 458-1 DP 


Edition 12.2004 


The SLSVAV send and receive block executes the following steps 
while the system is being initialized: 


e Checks the task assignment 


e Initializes the task-list of the SLB module corresponding to the 
data configured at the inputs 


In the normal system mode ("RUN" mode), the SLSVAV send and 
receive block executes the following: 


e Checks that the inputs are within the permissible value range 


e Enters the setpoints to be sent into the write buffer of the SLB 
module 


e Reads-out the actual values to be received from the receive 
buffer of the SLB module 


5-17 


SIMOLINK drive coupling 

































































I/O 
TAD Hardware address SLB (name of the SLB module), which can be 
configured in HWConfig 
ASL Address of the slave for dataexchange, (default: 1) 
value range 1... 200 
(initialization connection) 
NSV Number of channels for the setpoint to be sent, (default: 0) 
value range 0... 8 
(initialization connection) 
NAV Number of channels for the actual values to be received, (default: 0) 
value range 0... 8 
(initialization connection) 
XS0 Setpoint XS for channel 0 to 7, (default: 0) 
to A maximum of 8 setpoints can be sent. 
XS7 
YSO Actual values YS from channel 0 to 7, (default: 0) 
to A maximum of 8 actual values can be received. 
YS7 
SEQ Sequence number (default: 0) 
Number of the blocks in the SIMOLINK block sequence 
This value provides information as to whether the block was 
correctly initialized. 
YF Error status of the block (default: 0) 
YF=0 = noerror, YF > 0 
QF Group error bit (default: 0) 
QF=0 no error, QF=1 for error (if YFz0) 
Configuringdata Computation time [us] FM458 / PM6 34,7 
Can be inserted online no 
Can be configured in Interrupt tasks 
Cyclic tasks 
Executed in Initialization mode 
Normal mode 
Special features - 
5-18 Function Blocks - FM 458-1 DP 


Edition 12.2004 


6 Closed-loop control blocks 


6.1.1 INT M Modulo integrator for axis cycle correct integration 


Symbol 


Modulo value 
Input 

Numerator, ratio 
Denominator, ratio 
Setting value 
Reset 

Set 

Hold 


— Output 

— Positive oberflow 

— Negative overflow 
— Block error status 





Brief description the virtual master block INT_M is used to generate position reference 
values in angular synchronism. 
Mode of operation The block sums the input values X, weighted with ratio NM and DN. 


If the sum of the modulo value MOD exceeds or falls below 0, the modulo 
value is subtracted or added, and an overflow bit QP or QN is set for the 
duration of the sampling time. 


Modulo value, value range 1... 230 (default: 0) 
Input quantity of the integrator (default: 0) 
e.g. velocity (ramp-function generator output) 


Numerator value for the ratio (gearbox factor) (default: 1) 

NM * X may not exceed 231, 

value range: — 230 to + 230 

Denominator value for the ratio (gearbox factor), (default: 1) 

value range: — 229 to + 230 Gull 


Setting value (default: 0) 
Is the value which is set to the output Y with S=1. 
Reset (default: 0) 


(default: 0) 
Bit to set the output value Y to the setting value SV 
S=1 > Y=SV (initial offset) 

(default: 0) 
Holds the instantaneous value at output Y 
H=1 > Y=Yold 





Function Blocks - FM 458-1 DP 6-1 
Edition 12.2003 


Closed-loop control blocks 


Y Output quantity of the integrator (default: 0) 
R=S=H=0 > Y=Yold+X+NM/DN 


Positive overflow (default: 0) 
QP=1 3 Y + X > MOD (Y=Y-MOD) 


Negative overflow (default: 0) 
QN=1 > Y+X < 0 (Y=Y+MOD) 

Error status of the block (default: 0) 
YF=0 no error, YF > 0 coded error output 


Coded error output The error status is output in a coded form at output YF of the modulo 
integrator INT M. The last error event is always displayed. 


MOD > 230 or<1 


Soa aa Āā Io 
e Division overtow negative — | 


Configuringdata Computation time [us] FM 458-1 DP 19,8 


Can be configured in Interrupt tasks 
Cyclic tasks 

Executed in Initialization mode 
Normal mode 








Special features 


6-2 Function Blocks - FM 458-1 DP 
Edition 12.2003 


Index 


@CPB F bus, central coupling block retar n a E E AEA 2-15 
@CSL2F PROFIBUS FMS coupling central block...........rrrrrnnnnnnvrnnnnnnvrnnnnnrnvrnnnersrrnnnersrrrnnerrrrnnnen 2-1 
@CSL2L PROFIBUS FDL central block- ire aa a a ara a eaa tae aaae a e a eaaa adia aeit 2-1 
@CSPRO Central block, PROFIBUS DP coupling.....-++mrrrrrnnrrnnrrnrrnrrrrrnnrnnrrrrrnnnnnnrnrerrrrnnrnnnnnn 2-1, 2-2 
@FMPAR Parameter processing on FM458 modules.......rrrrrrrarvvvrnnnvvvvrnnnnvonnrrnnrrnnrrnnrennrrenrennnnn 2-29 
@SLSIMOLINK central block. aa aiaa reran daa ak eee 5-1 
B 

BRCV Block-oriented data reception via an S7 coupling.....-.-.rnrrrrrnrnnnrrnnn nr nr rnnrnrrrrnrnrnnnrnrennnnn 2-20 
C 

CBCONF COMBOARD configuration ......rwrsrrrnnannvvrnnnnavvrnnnnnvnrrnnnnrrnrnnnrennrneerennrnesrsnnnrnessennrressennnne 2-32 
CBRFAW Receiving warnings from a COMBOARD ......rannnnnnnnnnnnnnnnrennrnrnnrennrnnerrrrnnrrrrnnrenrrrrrnnnnnn 2-36 
D 

DPDIAG Diagnostics overview, PROFIBUS DP ..............:ccccccceeececeeneeceeeeeeeeeeteceaeaeeeeeeesessnnisaeeeeeees 2-3 
DPEVT Alarm information, PROFIBUS DP.......rrrarannrnrnnnrrnnnnnnarernrrnnransnersvnrvnrrnnsnnrenernernnsnnrenernesennn 2-9 
DPPEVT Process alarm information, PROFIBUS DP Symbol .......0.........:cc:ccecceceeeeeeeeteeteeeeeeeeees 2-12 
DPSLDG Slave diagnostics, PROFIBUS DP ..............ecccccccccceceeeeeeeeeeceeeeeeeeecceeaeceeeeeeesecssenieaeeeeeess 2-6 
F 

FMLED Control FM 458 diagnostics LED ...0............ccecececeeceeeeeeeeeeeeeaeceeeeeeeeseecaaeaeeeeeeesesensieaeeeeeees 4-1 
| 

INT M Modulo integrator for axis cycle-correct integration .........arsrrraronnrrnnnnonnrrnnnonnrrnnrrnnrrnnrnennnnn 6-1 
P 

PAS7 Initiate process interrupt at the S7-CPU ............eccccecccceceeeeeceenne cee ceeeeeseseceaeaeeeeeeeseteenaeeaeeeeees 3-3 
PNAME Parameter names on the T400............:::ccccceeeeeeeeeeeceeceeeeeeeeecencaeceeeeeeeseccueaeeeeeeeseeeensnaeees 2-38 
PSTAT Change enable for parameters ...........ccccceeeceeeeeneeeeeeneeeeeeeeaeeeeeeaaeeeseeaeeeeeeaeeeseeneeeeeenas 2-40 
S 

S7RD, S7RD B, S7RD |, S7RD_D Read from the peripheral area of the S7-CPU .................. 2-25 
S7RD P Reading data from a SIMATIC-CPU (P Bus) ......ornnrvrnronnrrvnrennrrvnnrennrrnnrrnnrrenrrnnrrensrnnnnne 2-16 
S7STAT S7 CPU operating state.........rrrmnnrnnrrrnrrnnnr vennen nrrvnrennrrrnrennrrenrrnnrrrenrennrrenernnrresrennnreseennnnne 2-23 
S7WR, S7WR B, S7WR |, S7WR D Write into the peripheral area of the S7-CPU................. 2-27 
S7WR P Sending data to a SIMATIC-CPU (P Bus).........rnnnnrrnonnnornvonrrnrrnrennnrnnrrrrnnnnrnnnrenrrrrrnnnnnn 2-18 
SAV- TR Save FB for NOVGRAM thee nen acetates ita nb anal 3-1 
Function Blocks - FM 458-1 DP |-1 


Edition 12.2004 


Index 


SBM Rotary encoder block. .unisrnmdasrkimmstørkrkide ikek i nheeventeadedel e i bd dd år bt 1-2 
SLAV, SLAVE R SIMOLINK receive block for one actual value ...............ccccccccceeeceeeeeeeseeeeeeeeeeenes 5-9 
SLD SIMOLINK delta evaluation ...........»rrrrrrrrrnrannrorovvrrrrrnnnnnrsvernrrannnnrsrernrrrnranesanssnevnrransnsnssesnesenne 5-11 
SEDIS SIMOEINK dispatther:raauuannagunutdrsnn eee lee ie ela ries neta hadde 5-12 
SLSV, SLSV R SIMOLINK send block for one Setpoint ...............ccceccceeeeeceeceeeeeeeeeeeeeeeeeeeeeeeeeeees 5-13 
SLSV2, SLSV2R SIMOLINK send block for 2 setpoints ................ccccccceseseeeeeeeeeeeeeeeeeeeseneeeeesenees 5-15 
SLSVAV SIMOLINK send and receive block for one SIAVE.............cccccceseseeeeeeeeeeeeaeeeeeeeeeeeeanenenes 5-17 
|-2 Function Blocks - FM 458-1 DP 


Edition 12.2004