Document text
Operating Instructions
FM/1/2 digi 42
WA-EKF 2738/07.95/S:MMS/D:Bau/80.10.0679.7
Connection
see appliance stamp/sticker/rating plate
Grässlin time switch modules are largely protected against
„spike“ or interference voltages. If faults still occur, counter-
measures against foltage peaks can be taken with familiar
elements (varistors, suppressor diodes etc.). Particular
attention must be paid to this when inductive loads are
connected.
1. Putting into operation
The steps marked with the symbol w are necessary to
carry out a switching program.
>= 1.1 Reset
Press the "Reset" key with a pencil or similar
object. This sets the time switch to its basic setting.
- before every restart
— to delete al syikching times and the time
(with the exception of the standard program)
The following appears after approximately
2 seconds:
Summer time
Hand switch and winter
time
Reset
changeover
Enter Enter
switching Foire
time
Days of
the week
flash
Enter
Enter minutes
time
Holiday
brogram Select days
Deselect days of the week
of the week
1.2 Standard program (available on request)
Modules supplied with an integrated standard program
can be activated without programming on Mondays —
on time — at 20:00. The senda program contains
the following preset switching times which, however,
can also be changed.
Monday - Friday
6:00 © = ON
22:00 © = OFF
Saturday + Sunday
7:00 ® = ON
23:00 O = OFF
Activation of the standard program:
@ After pressing the "Reset" key (see 1.1):
@ Press the "©" key on Mondays at 20:00:
The standard program is activated and
runs on time.
® 1.3 Entering the time and current day
of the week
@ After pressing the "Res" key (see 1.1):
@ During the summer time period:
press the "1h" key once.
and O.
© With the "h" key:
© With the "m" key:
© With the "Day" key: enter the current day
1=Mo...7=Su
© Keep he "©" key pressed during steps
enter the hours
enter the minutes
@ Release the "©" key
The colon now flashes at one second intervals.
Note:
If the "h/m" keys are pressed for longer than
2 seconds, the display will enter fast-forward
scroll mode.
> 1.4 Entering switching times
42 ney locations are available
Each switching time occupies 1 memory location.
© Keep pressing the "Prog." key until a free
memory location "= = : = =" is shown in the
display.
@ Select the switching functions "©" (ON) or
"O" (OFF) with the "S" key for channel
1 or 2 (depending on the version).
© With the "h" key:
© With the "m" key:
If a switching command is to be executed every
day, proceed with step @. If 1 switching command
is to be executed only on one day or on certain
days skip step @ and continue with step ©.
enter the hours
enter the minutes
© Save with the "Prog." key or
O With the "Day" key, select 1 day on which the
ete command is not to be carried out
(cursor flashes).
@ Confirm this day with the "Sel." key
(day of the week and cursor flash)
© Press the "Day" key (day is deselected).
Repeat steps @, @ and @ for every day to be
deselected.
O Save with the "Prog." key (the next free
memory location is displayed)
or
® Save with the "©" key.
The time switch goes over to automatic mode
and displays the current time.
Begin every additional switching time and the
associated switching state © = ON or O = OFF
again with 1.4.
Note:
If an input is incomplete, the segments still not
selected are displayed flashing.
If you have deselected a day on which the
switching command should be carried out,
@ Reselect the deselected day with the "Day"
key (day of the week and cursor flash).
@ Confirm this day with "Sel." (cursor flashes).
© Press the "Day" key (day is reselected).
© Save with the "Prog." key
(the next free memory location is displayed)
or
© Save with the "o" key.
1.5 Free channel block formation
On the two channel version, one timed instruction
space can be used to enter a switching command
(ON or OFF) for either channel 1 or Sanel 2,
or both channels if required.
2. Additional functions
2.7 Holiday program®-
2.1 Summer time and winter time setting
@ Press the "1h" key once.
2.2 Manual switch "o"
The current switching state can be changed at any
time with the "4&" key for channel 1 or 2 (depending
on the version). Use of this manual override facility
does not alter any of the programmed information.
Automatic Mode Manual Mode | Continuous Operation
© S [9] of
© © =ON ON = OFF [©] = Continuous ON
© O = OFF @®® =ON [O] = Continuous OFF
The switching
times correspond
to the entered
program.
If the current
switching state is
changed manually,
the next switching
command is
again executed
automatically
according to the
The output will
remain fixed ON
[©], or fixed OFF
[O] as selected
indefinitely until the
"AQ" key is used
to restore the timed
function.
entered switching
program
2.3 Reading the programmed switching times
@ Press the "Prog." key several times:
- displays all entered switching times starting
with the first memory location.
— the first free memory location
n "is then displayed.
— the number of memory locations still free is then
displayed.
If the memory locations are occupied, the following
appears in the display: "FR 22"
@ Press the "©" key:
The time switch changes to automatic mode and
displays the current time.
2.4 Changing the programmed switching times
@ Keep pressing the "Prog." key until the switching
time to be changed is displayed.
@ The new data can then be entered as described in
Point 1.4.
Note on saving switching times:
If programming is not completed with the "©" key
atter the switching time is entered (1.4), the
complete switching command is still automatically
saved after approximately 90 seconds. The time
switch then daha to automatic mode and shows
the current time again.
2.5 Deleting individual switching times
@ Keep pressing the "Prog." key until the switching
time to be deleted is displayed.
@ Set to "- -" with the "h" or "m" key and keep
the "©" key pressed for about 3 seconds.
The switching time is deleted and the current time is
displayed after the key is released. 3.
2.6 AM/PM time display
If the "£1" key and the "h" key are pressed
simultaneously, the time display is switched to AM/PM
mode (used mainly in English-speaking countries).
Note:
The holiday program has priority over the standard
week program. The holiday program can only be
entered if all seven days o! fe week (1234567)
are selected.
Entering switching times as described under
The "B-" key must be pressed for each switching time.
Next, save the holiday switching times with the
"Prog." or "©" key.
Entering the start and duration
of the holiday program
@ After entering the switching times for the
holiday program
@ Press the "Q." key once. the following image
appears:
Cursor of
the current | 1 a-
day of the oll
week flashes "ILI —— Ho = Holiday
Image I
© If the holiday program is to start on a different day
to the current one — max. 6 days ahead — use the
"Day" key to select the day on which the holiday
program is to commence.
If the holiday program is to be executed for up to
max. 99 days, continue with steps @+@.
If the holiday program is to be executed for an
unlimited giad leave out step @ and continue
with step ©.
© Enter the required number of holiday days with
the "Sel." key (1 to max. 99).
© Press the "©" key to save the entries.
If the current day of the week was entered as the
holiday program start, the following appears:
a
f (Lf
ok an alin hl
oO o holiday days
Image II
Image II remains until the holiday days have passed,
for example d:10, d:09, d:08 .......... etc.
Pressing the "©" key again and holding it down now
allows the day of the week, the time and the current
switching state - "@" = ON or "O" = OFF -
to be checked.
If a day of the week other than the current day was
entered as the holiday program start, the current time
is displayed after the "©" key is pressed. The holiday
program is then started at midnight at the start of the
selected day of the week and its duration is displayed
(Figure Il).
After the programmed holiday days have expired,
the current time appears in the display.
Aborting the holiday program prematurely
If the holiday program has already started:
@ Press the " B" key once
If the holiday program has not yet started:
@ Press the " B" key twice
Technical data
Connection
Switching capacity
Ambient temperature
Running reserve
Memory locations
Shortest switching time
Programmable
see unit stamp
see unit stamp
-10°C to +55 °C
see unit stamp
42
1 minute
every minute