LH 128A, LH128A-FM, LH128A-S

Survival, Water, Medical Field Manuals

Military Manuals

Lambda Electronics Corp.

Document text

An Bor -15 
INSTRUCTION 
MANUAL 


REGULATED POWER SUPPLIES 


| MODELS LH 128A, LH128A-FM, LH128A-S 


MODELS LH 128, LH 128FM, LH 1285 


BEARING SERIAL NO. 


PREFIXES A-C | 


_ AR 


LAMBDA ELECTRONICS CORP.-MELVILLE, Li І., М. Y. 


шы» 


INSTRUCTION MANUAL 
FOR 


REGULATED POWER SUPPLIES 


MODELS LH 128A, LH128A-FM, LH128A-S 
MODELS LH 128, LH 128FM, LH 1288 
BEARING SERIAL NO. 


PREFIXES A-C 


manual provides instructions intended for the 
operation of Lambda power supplies, and is not to 
be reproduced without the written consent of Lambda 
ВЕС Corp, - All information contained herein 
applies to metered, non-metered, and chassis-mount- 
ШЕ models unless otherwise specified. 


LAMBDA ELECTRONICS CORP. ШАЛТ, L. Lo 


11. 
MAIN PLANT TELEPHONE: 516 MYrtle 4-4200 


IM LH 128 


TABLE OF CONTENTS 
SECTION 


SPECIFICATIONS AND FEATURES 


MOUNTING 


THEORY OF OPERATION 


GENERAL 
FUNCTIONAL DESCRIPTION 


OPERATING INSTRUCTIONS 


CONTROLS, INSTRUMENTS AND FUSES 

GROUND CONNECTIONS 

BASIC MODES OF OPERATION 

SUPPLY-LOAD CONNECTIONS 

DETAILED OPERATING PROCEDURES 

OPERATION AFTER PROTECTIVE DEVICE SHUTDOWN 


MAINTENANCE 


GENERAL 

TROUBLE ANALYSIS 

CHECKING TRANSISTORS AND CAPACITORS 

PRINTED CIRCUIT BOARD MAINTENANCE TECHNIQUES 
TROUBLE CHART 

ADJUSTMENT OF CALIBRATION CONTROLS 
PERFORMANCE CHECKS 


SERVICE 


PARTS ORDERING 


PARTS LIST 


USE OF RACK ADAPTERS (FIG. 18) 


INSTALLATION OF 1/2 RACK UNITS INTO LRA-1 ult 18) 
T 


SHIPMENT OF UNITS MOUNTED IN LRA-1 (FIG. 
USING BLANK PANELS AND BLANK CHASSIS (FIG. 18) 


EE 


PAGE 


09 GO COST OT SIN FER 


PO TO [Ó TO rO TO E 
al e» O'Or АХ) 


m mM mp 
ON dude 


no 
~ 


SPECIFICATIONS AND FEATURES 


Specifications apply for the non-metered LH 128, metered LH 128FM 
and chassis-mounting LH 128S models. 


DC OUTPUT--Voltage regulated for line and load 
voltage hanee LI... eere... 0-60 volts DC 


liar s Current Ranges......... Current range must be chosen to suit 
the appropriate maximum ambient temp- 
erature. Current ratings apply for 
entire voltage range 


Ambient Temperature......30°C 50°C 60% ALAS 


Current Е. SM 0-21٨ ОА O-1.5A 


REGULATED VOLTAGE OUTPUT 


Шо Япе).............ІТевв than 0.015 percent or 1.0 milli- 
volt, whichever is greater for input 
variations from 105-135 or 135-105 
volts AC 


Regulation AO همو‎ we LOSS than 0.015 percent or 1.0 milli- 
volt, whichever is greater for load 
variations from О to full Тода OF full 


0930 to O 
Transient в ............ 2 Output voltage is constant within reg- 
(line ) ulation specifications for any 15-volt 
line voltage change within 105-135 
volts AC 


Ent Песропве............Олірав voltage is constant within 50 

(load) millivolts for load changes full load 
to O, within 50 microseconds after 
appdieation;-is constant within 14 milli- 
volts for load changes from O to full 
load within 50 microseconds after appli- 
cation and is constant within 10 milli- 
volts for load changes full load to 10% 
of load within 120 microseconds after 
application 


Remote Programming Constant...200 ohms/volt output 


Internal Impedanee............Less than ОРЕ DO Бо 1 kiloz 
cycle 


LH 128 Page 1 


Kipplerand- Noise, SO ISENE Less than 250 microvolts ШӘ 
millivolt peak to peak with either 
positive or negative terminal grounded 


Temperature, Coefficient 2527) Output change in voltage less than 


0.015%/°C 


DC_OUTPUT--Current regulated for line and load; Automatic Crossover 
MTS with voltage limit 


Multi =Current Ranges e Current range must be chosen to suit 
the appropriate maximum ambient temp- 
erature. Current ratings 201 or 
entire voltage range 


Ambient Temperature... 300 50°C 60°C EC 


Current Range VP 0.48-2.4А 0.48-2 ЛА 0.48-1 САИ ЕА 
Voltage Rangel 2. ие 0-60 volts DC, for entire current 
range 


REGULATED CURRENT OUTPUT; AUTOMATIC CROSSOVER 


Regulation (Line lb pe as: Less than 15 milliamperes Tor ٢٢ | ٢ 
variations from 105-135 а 
volts AC 


Regulation (load).............less than 15 milliamperes E 
voltage changes from O to 60 or 60 
to O volts DC 


Ripple and Noise... i. N ee Less than 1 ma at 55-480 eps; 
Less than 3 ma at 45-55 eps; both with 
either neg. or pos. terminal grounded | 


DC OUTPUT--Current regulated for line and load; Barrier strip recon- 
ANS nection for Precision Current Regu- 
lated Output with no voltage limiting 


Multi-Current Ranges....... ...Current range must be chosen bot 
the appropriate maximum ambient temp- 
erature. Current ratings apply for 
entire voltage range 


Ambient Temperature... 3058 r Ub GORG TEC 
Current Rance an 0.12-2.4А 0,105-2.1A 0.09-1 -321 а 
voltage Range oe. ens Jam pipe HAT 0-60 volts DC, for entire current range 


Page 2 LH 128 


REGULATED CURRENT OUTPUT; PRECISION CURRENT REGULATED 


Re mac ion (line)...... Ben 0.052 or 0.5 milliampere, 
whichever is greater, for input vari- 
ӘЛ ШОП Of 105—135 or 135-105) volts АС 


Regulation (toad), A CA +... «| Less than 0.05% or 0.5 milliampere, 
whichever is greater, for load changes 
from 0-60 or 60-0 volts DC 


Es: odNoise......... eco Less than O.5 ma at 55-480 eps; 
Less than 1.0 ms at 45-55 eps; both 
wichr either neg. or ров. terminal 
grounded 


Remote Programming...... ЛК. 100 ohms, 2-watt resistance for maxi- 


mum rated current; adjustable over 
range by decreasing resistance 


AC IUUD. 205-135 omn 205-265 ( opt ton) volts АС at 45-480 cps; 
290 watts* 


ПН output loaded to full 30°C rating and input voltage 
Mo volts AC 


OVERLOAD PROTECTION 


dO] 295.55 РОНА Thermostat, resets automatically when 
over-temperature condition is elimin- 
ated 
Electrical 
See еее وود ده‎ Adjustable, automatic, electronic 


eurrent-liniting circuit, settable 

to 105 percent of rated current; 
Limits output, current to preset limit 
for protection of load and power 
Supply when external overloads and 
direct Shorts occur 


Tumi e ea l зан. HN UE Puse provides protection against in- 
zernal CTACTA T fallure 


INPUT AND OUTPUT CONNECTIONS--Heavy duty terminal block on rear of 
chassis with 5-foot, 3-wire detachable 
ine cord tor all models; Dive-way 
banding posts provide for additional 
positive (+), ground, and negative (- 
DC output connections on front panel 
of FM models 


LH 128 Page 3 


‘OPERATING AMBIENT TEMPERATURE RANGE AND DUTY CYCLE--Continuous duty 
from 0°C to 71°C ambient with corres- 
ponding load current ratings for all 
modes of operation 


STORAGE TEMPERATURE-- 2550 bombo О 
(non-operating ) 


METERS--Voltmeter and ammeter on metered (FM) models 
CONTROLS 
DC output controls: ED Coarse and fine voltage controls and 
current control permit adjustment of 
DC output; located on front panel of 
all models 


Test Jacks (+) (-)...Test jacks for non-metered model permit check- 
ing DC output with external meters 


Remote Sensing.......Provision is made for remote sensing to elimi- 
nate effect of power output lead resistance on 
DC regulation 


Dower sn ol Um MINUM ....Panel mounted switch and indicator light for all 
units except models with suffix (S) 


hb S HU Ma. Digs eer ha 5-3/16"H x 8-3/8"W x 15-5/8"D (LH 128, ВВ 
4-5/]16"H x SW x 15-57 МВ 1995) 

We LON ое ТАТҮ: Л С 25 lbs. nets. 30 lbs. sipping wv. 

Panel, Paves در‎ Brushed aluminum clear anodized panels with grey 


inlay (standard); special finishes available to 
customer's specifications at moderate surcharge 


MOUNTING: 
Laboratory beneh, table top...LH 128, LH 128FM 
CHASSIS MOURA GE Е LH 12885 
NOTE: Bumpers secured to the base of LH 1285 units permit 
circulation of air through the unit. Do not remove bumpers 


unless the chassis-mounting is provided with a cutout to 
permit free-flow of air through the unit. 


Standard TO reacio rl D LH 128, LH 128FM; used with rack adapt- 
ers: LRA-1 (slide accomodation provided 
LRA-2 (conventional mount) 
See figure 18. 


Page 4 LH 128 


ACCESSORIES 


КООШО ес ... Rack adapter LRA-1 used for ruggedized mounting, 
wich Or without chassis slides is available, as well as rack 
adapter LRA-2 which is used for simple rack installations where 
chassis slides are not required. 


Overvoltage Protector ... Externally mounted, Overvoltage Protector 
LH-OV-6, is available. 
MODEL OPTIONS 
Suffix "R" Fungus Proofing Option ... Standard LH power supplies 


сап Бе Obtained with fungus proofing treatment with MIL V 173 
1 17 Тот all fungi nutrient components. 


١ ھت‎ Input Option ... Standard LH power supplies are avail- 
able for operation with 205-265 volt, 45-480 cps input. 


LH 128 Page 4a 


THEORY OF OPERATION 


GENERAL 


Ша Тапрдаа power supply circuitry consists of an AC input circuit 
s upero, a reference supply circuit consisting of an auxil- 
lary rectifier and filter, zener diode pre-regulator, reference ele- 
LER regulator; a main regulator circuit consisting of the 
main rectifier and filter, a series regulator, two emitter follower 
(РЕТТЕ current limit amplifier, a voltage amplifier, the comple- 
mentary differential amplifier circuit, and an output sensing circuit. 


The circuit arrangement is shown in block diagram form in figure 14. 
The circuitry is discussed with reference to the block diagram and the 
Schematic diagram. 


FUNCTIONAL DESCRIPTION 


single phase input power is applied to transformer T1 through the 
input circuit containing thermostat S2 and fuse Fl, which protect the 
Supply against overheating and internal faults. 


The main rectifier, a full-wave bridge rectifier, comprised of diodes, 
СВ14-17, provides the power which is filtered by capacitor C12 and then 
regulated via a series regulator and delivered to the output. The full- 
wave auxiliary rectifier CR10 and CR11, provides voltage filtered by 
capacitor C8 for reference series regulator Q6 and reference element Q5 
of the reference supply as well аз for pre-regulator CRS and CRI. The 
reference supply output provides a regulated, temperature compensated 
reference voltage which is used to determine the output voltage of the 
unit. Cascade connected pre-regulator CR8, CRY, R24 and R23, provides 
Stabilized bias voltage for current limit amplifier Q4, voltage ampli- 
fier Q3, "OR" gate CR4 and CR3, and for complementary differential 
amplifier Ql and Q2. 


Reference element Q5 contains a zener diode and transistor in one 
unit which act to reduce the effect of temperature changes and to pro- 
vide a stable reference voltage for series regulator Q6. 


Constant voltage or constant current crossover circuit operation is 
determined by changes in the load. A change in the load is sensed by 
sensing divider R5, ВД, CR2 and RIA, B, which has a fixed current flow- 
ing in the divider elements as determined by the setting of calibration 
FI oj This variation causes a change to 01 input of the comple- 
mentary differential amplifier, which compares it with the reference 
voltage through the sensing divider, causing an error signal at the out- 
put of Q2. Simultaneously current limit amplifier Q4 samples the load 
current through current sensing resistor R43. When the current reaches 
a preset limit, Q4 will generate an error signal. 


ИШИ 128 | Page 5 


The error outputs from Q2 and Q4 are fed through "OR" gate CR3, 
CR4 to voltage amplifier Q3, and one signal is amplified by Q3 and 
emitter followers Q8 and Q9. The amplified signal from the emitter 
followers determines the impedance value of series regulator Q10- 
Q15 which acts as a varying impedance in series with the output. 
These power transistors function as the active series regulating 
element. 


Under constant voltage operation Q4 is in saturation, CR3 conducts 
and СЕД in the "OR" gate is turned off, and all of the сике 2.049 
flows through Q4. When load current increases, the voltage drop 
across current sensing resistor R43 increases, biasing Q4 toward cut 
off. When Q4 cuts off, CR4 is forward biased and conducts while CR3 
ceases to conduct. The signal is amplified via voltage amplifier Q3 
and emitter followers Q8 and Q9, increasing the impedance of series 
regulator Q10-Q15, causing the output voltage to decrease toward zero 
and the unit to function at the fixed current limit. 


Voltage amplifier Q3 operates at all times from the output of "OR" 
gate CR3, CR4, its action depending upon which signal the "OR" gate 
conducts. When Q4 is turned off due to an excessive load, Q3 will 
saturate, causing main series regulator Q10-Q15 to turn off. When 
load current limit is not reached or exceeded, Q4 is in saturation 
and Q3 will operate with the error signal derived from Q2 of the 
complementary differential amplifier, causing the series regulator 
to echange the output voltage for the preset voltage limit. 


When connected for precision current operation, the complementary 
differential amplifier is referenced to, the current sensing resistor, 
with a fixed current flowing from the sensing divider through poten- 
tiometer RIA, B. Any change in load will cause an error ЕЛЕ 
the complementary differential amplifier and the circuit funetions as 
explained previously. 


Page 6 LH 128 


OPERATING INSTRUCTIONS 
CONTROLS, INSTRUMENTS AND FUSES 


POWER ON Switch, The POWER ON switch, located on the front panel, 
controls application of input power to the supply. When the switch 
Eu position, the red POWER ON indicator glows. 


В СЕ Control, The OUTPUT VOLTAGE control is a dual con- 
ED unge of a coarse adjustment potentiometer, which varies 
the DC voltage over a range of 0-59 volts and a fine adjustment po- 
tentiometer, which varies the DC voltage over a one-volt range. 
Clockwise rotation results in increasing voltage. The total DC volt- 
АО voltage regulated operation, is equal to the sum of 
А СЫ те; for current regulated operation the maximum volt- 
Ep. usual. со the sum of each shaft setting. The control is 
Е бое front panel of all units. 


CURRENT LIMITER Control. This potentiometer varies the maximum DC 
Current over the rated *current range and, for current or voltage 
ВЕ Ой, limits the DC current output to the setting on 
the control. Clockwise rotation results in increasing current. This 
aOR po located on the front panel. 


*Operation for output current below rated limits can result 
output or no regulation. 


Output Voltage Meter. A O-60 volt DC voltmeter monitors the voltage 
at the output terminals of metered (FM) units. 


Output Current Meter, А 0-1.0 ampere DC ammeter monitors the load out- 
put current of metered (FM) units. 


Buse. Fuse Fl, internally located, is a 3 ampere, ЗАС "SLO-BLO" fuse 
совой = in the AC input circuit. 


Connection Terminals. Make all connections to the supply at the ter- 
minal block on the rear of the supply. On FM suffixed models, DC out- 
put connections can also be made at the five-way binding posts located 
on the front panel. Apply input power through the line cord or dir- 
ectly to terminals 1 and 2 if the line cord is removed. Always connect 
the ungrounded (hot) power lead to terminal 1. 


The supply positive terminal is brought out to terminal 6. The sup- 
ply negative terminal is brought out to terminal 4.. Recommended. 
wiring of the power supply to the load and selection of wiring is 
shown in figures 1 through 13. Selection of proper wiring is made on 
the basis of load requirements. Make all performance cheeks and 
measurements of current or voltage at the rear output terminals.  Con- 
nect measuring devices directly to terminals or use the shortest leads 
possible. 


Page 7 
LH 128 s 


GROUND CONNECTIONS 


The Lambda power supply can be operated either with negative or posi- 
tive output terminal grounded or with no terminal grounded. Both posi- 
tive and negative ground connections are shown in the diagrams for all 
suggested output connections illustrated in this manual. 


NOTE: When operating the supply with neither term- 
inal grounded, high impedance leakage resistance 
and capacitance paths can exist between the power 
Supply circuitry and chassis ground. 


BASIC MODES OF OPERATION 


This power supply is designed to operate as a constant voltage source 
or as a constant current source. Except when used for a precision con- 
stant current source, automatic crossover to either mode of operation 
occurs when load conditions change as follows: 


Constant Voltage. The power supply will function as a constant voltage 

source while the load current does not equal the current value 5-57 

set by the CURRENT LIMITER control. When load current Ip, = М = ILIM> 
hr, 

the supply will cross over automatically and will operate as a constant 

current source, Further decrease in value of load resistance SUS 

in decrease of voltage across the load while current remains regulated 


to IpIM. 


Constant Current (Automatic Crossover), The power supply will function 
аз a constant current source while the load voltage Ут, does not equal 
the voltage value set by the OUTPUT VOLTAGE control. When load voltage 


VL equals the value set by the OUTPUT VOLTAGE control, the suppl LL 
automatically cross over and operate as a constant voltage source. 


Constant Current (Precision), The power supply will function within 


rated specifications as a conventional constant current source without 
automatic crossover. When load voltage demand exceeds the rated volt- 
age of the power supply, the unit output current regulation wilt not 
be within specification. 


SUPPLY-LOAD CONNECTIONS 


NOTE: Refer to DETAILED OPERATING PROCEDURES for 
step-by-step instructions for operation of power 
supply. 


Page 8 LH 128 


CONNECTIONS FOR OPERATION AS A CONSTANT VOLTAGE SOURCE 


The output impedance, regulation, and transient response of the 
power supply at the load may change when using the supply as a con- 
Stance voltage source and connecting leads of practical length are 
used. To minimize the effect of the output leads on these character- 
istics, remote sensing is used. Recommended types of supply load 
ponneetions with local or remote sensing are described in the follow- 
ing paragraphs. 


11 Nu 1۱71768 1 and 2 to determine voltage drop for particular 
cable length, wire size and current conditions. Lead lengths must be 
measured from supply terminals to load terminals as shown in figure 3. 


Two-Wire Connection, Figure 4, The two-wire connection, with local 


Sensing, is the connection suitable for application with relatively 
constant load where extremely close load regulation and fast transient 
ESpDonse over Tull-rated current excursion are not required at the load. 


Improved Two-Wire Connection, Figure 5. The improved two-wire connec- 


ШОП, Weed local sensing, is suitable for applications where excess- 
ively 1002 connecting leads are not used. Using multiple paralleled 
leads in this type of connection reduces the supply-load lead voltage 
drop and permits improved regulation and transient response. 


Four-Wire Connection, Figure 6. The four-wire connection with remote 


sensing, provides complete compensation for the. DC voltage drops in 
те ٢71717 Me cables. Compensation for lead drop is also valid for 
gradual changes of load current. 


Programmed Voltage Connections, Using External Resistor, Figure 7. Dis- 


cr Cod; s steps сап be programmed with a resistance voltage divider 
valued at 200 ohms/volt output and a shorting-type switch as shown in 
БОЕО When continuous voltage variations are required, use vari- 
able resistor with the same 200 ohms/volt ratio in place of the resis- 
tive voltage divider and shorting-type switch. Use a low temperature 
coefficient resistor to assure most stable operation. 


As Shown in figure 7, voltages can be programmed utilizing either 
шалар remove sensing connections, as desired. 


Programmed Voltage Connections Using Programming Voltage, Figure So ine 


power supply voltage output can be programmed with an externally con- 
nected programming power supply. 4 

Тһе output voltage of the programmed supply will maintain а one-to-one 
ratio with the voltage of the programming supply. 


CONNECTIONS FOR OPERATION AS A CONSTANT CURRENT SOURCE 


Automatic Crossover Constant Current Connections, Figure 4, Figure 4 
Shows the connections which are used when operating the power supply as 


a constant current source with automatic crossover, using local setting 
or current eöntrol.* 


*Setting control, for output currents below rated limits can 
result in no output or no regulation. 


ИН 128 Page 9 


In this mode of operation, when the load voltage increases, due to 
changing load resistance, to the limit of the OUTPUT УО conte 
setting, the power supply crossover circuit will cause ٢ ٢ ٢ ٢ vo | 


operate as а constant voltage supply. | 
| 


Precision Regulated Constant Current Connections, Figure 9. Figure 9 | 
Shows the connections which are used when operating the power supply | 
as a precision constant current source, using local settene 
control“ 


In this mode of operation, the power supply functions аб 8 сопчуейе 
tional constant current supply with crossover circuit 1 те 
The load voltage limit is fixed to the maximum voltage rating of the 
power supply. 


Programmed Precision Regulated Current Connections, Figure 10. To pro 
vide discrete current steps from 5% to 100% of rated current, use any 
combination of separate 2-watt resistors totalling 100 ohms together 

with а shorting-type switch connected as shown in figure 10. Use re- 
sistors with low temperature coefficients to assure most stable operas 


TONI 


When continuous current variations are required, use а 150 опт, 2-wa 
variable resistor in place of the separate resistors) апа sern та 
switch, 


CONNECTIONS FOR SERIES OPERATION 


The voltage capability of LH power supplies can be extended by serie 
operation of two LH power supplies of equal* voltage тасш А maxdc 
mum of 200 volts can be connected between either the +DC or -DC term- 
inal and chassis ground. | 


*For applications using supplies of unequal ratings, con- 
sult factory for details of operagion,. 


The two units are shown connected for series operation aure: 
11 and 12. Figure 11 shows the series connection dir 
be suitable for use in all applications where exact one-to-one voltage 
tracking of the "master" (M) unit by the "slave" ($) در‎ ce 
quired. The slight offset in tracking 18 easily compensar by 
adjusting the, OUTPUT VOLTAGE controls 60 the (SS) "unite 


Figure 12 shows the series connection diagram suitable Тор аррі1са-% 
tions where exact one-to-one voltage tracking is required. In this 
series configuration, resistor RBAL permits the (S) unit 50 track the 
(M) unit on an exact one-to-one basis, thereby eliminating the possi- 
bility of an offset voltage existing between the two units 


Resistor Rpar, should be a one-watt, 10-20 kilohm resistor. This val 
would permit wide-range compensation for manufacturing differences in- 
herent in the components used in each unit. Resistors RS and Ry func 
in the voltage sensing circuits of both units, enabling the (S) unit ti 
reference its output voltage to that of the (M) unit. In figure 11, R 
performs a similar function. Capacitor Cs, used to eliminate stray AM 
pickup, Le, rated.aule. HNE EO NV 


Page 10 LH 128 


For either series mode of operation, select RS and RM on the basis 
ВА OMS per volt of (My mit 5 voltage. Re must equal RM. 


Diodes CRM and Cha, which protect the units against reverse voltage, 
must be capable of withstanding the maximum rated current of the (M 
DEL. 


F or 11577: permit operation for either constant voltage or con- 
Е ое with automatic crossover to either mode of operation 
иси ПС respective limiting operating current or voltage is 
В Уон in figures 11 and 12, each method permits connec- 
ШОП tor either local or remote sensing. 


CONNECTIONS FOR PARALLEL OPERATION 


B Xr Ее 0022111577 of LH power supplies can be extended by para- 
ЖЕСІ Operacion of two LH power supplies of equal* voltage capacities. 
E woes are shown connected for parallel operation in figure 13. 
One power supply designated the "master" or (M) unit controls its own 
NN the output of the second power supply, designated the 
"siave oor) (Ss) unit. 


Dx ons using supplies of unequal voltage 
px consult factory for details of operation. 


"11010 es to regulate its current in a ratio to that of the 
(M) Ux ring the current in its internal sampling resistor 
о НОС sampled by the master internal sampling resistor. 

When power supplies of unequal current capacities are parallel connected 
Pie Om ton or current supplied will be approximately equal to the 
Ao -cubpPent ratings of the supplies. 


Parallel connected units can be operated for constant voltage with 
ЕЕ well as for constant current with automatic crossover. 


When operating for constant voltage, the (M) unit can automatically 
ВЕ О constant current operation. 


DETATLED OPERATING PROCEDURES 


SAFETY NOTTCE 
DANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT, OBSERVE 
THE USUAL SAFETY PRECAUTIONS WHEN OPERATING OR SER- 
VICING THE EQUIPMENT TO AVOID SHOCK OR INJURY, 
CONSTANT VOLTAGE OPERATION, ADJUSTABLE CURRENT LIMIT 


1. Remove AC power input to the supply and place POWER ON 
switeh in OFF position before connecting load to the supply. 


LH 128 Page il 


2. Determine load requirements, select wire Гром 1 ګل‎ 


1-3 and choose desired type of supply-load connection from figures 
4-6, 


3. Connect supply to load as shown on the selected con- 
nection diagram. 


NOTE: When shipped from the factory, the supply 

is ready for use as a constant current source with 
automatic crossover or as a local-sensing constant 
voltage source. Jumpers are connected at the fac- 
tory as shown in figure 4. Take care to remove the 
appropriate jumpers for load requirements that need 
different supply-load connections. Refer to the 
appropriate connection diagram. 


4, Turn OUTPUT VOLTAGE control knobs to the qes u QR s 
age setting. 


5. When current to the load must be limited to an inter- 
mediate value within the current rating of the supply, turn the CUR- 
RENT LIMITER control to the desired current limit setting. If no 
intermediate current limit is required, turn the control CW to The 
position for full current rating for the maximum ambient temperature 
of operation. Refer to section on specifications. 


6. Apply AC power to the supply. 


7. Place POWER ON-OFF switch in ON position and check that 
red POWER ON indicator is lit. 


8. Check that output current and output voltage meters in- 
dicate desired values; as required, adjust OUTPUT VOLTAGE control knobs 
and CURRENT LIMITER control to obtain correct meter indications. For 
non-metered models use externally connected meters and check that cor- 
rect meter indications exist at output terminals 6 and 4, or at front 
panel test jacks (+) and (-); for remote sensing connections, check at 
the load terminations of sensing leads on terminals 3 and T. 


9. Power supply is now in proper operation. 


PROGRAMMED CONSTANT VOLTAGE OPERATION, ADJUSTABLE CURRENT LIMIT 


1. Remove AC power input to the supply and place POWER ON 
switch in OFF position before connecting load to the supply. 


2. Determine load requirements, select wire size 217 لل‎ ٢٢٢ 
from figures 1, 2 and 3 and choose desired type of supply-load con- 
nection from figures T or 8. Refer to paragraph on Programmed Voltage 
Connections. 


Page 12 LH 128 


3. Connect supply to load as shown on the selected connec- 
Бара. As shown in figure 7, take care to use a shorting-type 
Switch for the external programming control when several voltages are 
desired and the programming voltage method is not used. 


4, Turn OUTPUT VOLTAGE control knobs to the extreme CCW 
position. Adjust external programming voltage control to desired 
voltage setting. 


5. When current to the load must be limited to an intermed- 
late value within the current rating of the supply, turn the CURRENT 
LIMITER knob to the desired current limit setting. If no intermediate 
егеп limi o is desired, turn the control CW to the position for full 
rated current for the ambient temperature of operation. Refer to sec- 
tion on specifications. 


6. Apply AC power to the supply. 


7. Place POWER ON switch in ON position and check that red 
Bowen ON 71102601 is lit. 


6, Check that output current and output voltage meters in- 
G@icate desired values; as required, adjust CURRENT LIMITER knob and 
external programming voltage control to obtain correct meter indica- 
tions. For non-metered models use externally connected meters and 
check that correct meter indications exist at output terminals 4 and 
6, or at front panel test jacks (+) and (-); for remote sensing con- 
nections check at the load terminations of sensing leads on terminals 
Sand Te 


9, Power supply is now operating properly. 


CONSTANT CURRENT OPERATION WITH CROSSOVER, ADJUSTABLE VOLTAGE LIMIT 


1. Remove AC power input to the supply and place POWER ON 
See Chee Mu nPosTolon before connecting load to the supply. 


2. Determine load requirements and connect load to the 
supply as shown in figure 4 


ага the CURRENT LIMITER knob to the desired current 
setting. 


4. When load voltage must be limited to an intermediate value 
шешіп ле voltage rating of the supply, turn OUTPUT VOLTAGE control 
knobs to the desired voltage limit setting. If no intermediate voltage 
ИІП raving of supply 18 desired, turn controls to the full 
CW pOsivszon to obtain voltage limit at maximum voltage rating of the 


supply. 
5. Apply AC power to the supply. 


6. Place POWER ON switch in ON position and check that red 
POWER ON indicator is lit. 


LH 128 Page 13 


7. Check that output current and output voltage meters 
indicate desired values; adjust OUTPUT VOLTAGE control knobs and 
CURRENT LIMITER control as required to obtain correct indications. 
For non-metered models use externally connected meters and check 
that correct meter indications exist at output terminals 4 and 6, 
or at front panel test jacks (+) and (-). 


8. Power supply is now in proper operation. 


PRECISION REGULATED CONSTANT CURRENT OPERATION 


1. Remove AC power input to the supply and place POWER 
ON switch in OFF position before connecting load to the supply. 


2. Determine load requirements and connect load to the 
Supply as shown in figure 9. 


3. Turn the CURRENT LIMITER knob to the maximum desired 
current setting. 


4. Turn both OUTPUT VOLTAGE control knobs to extreme CCW 
position. 


5. Apply AC power to the supply. Place POWER ON switch 
in ON position and check that red POWER ON indicator is lit. 


6. Turn fine OUTPUT VOLTAGE control knob CW until the de- 
sired current setting as indicated by output current meter is reached. 


7. Check that output current\meter indicates desired value 
and that output voltage meter does not indicate OFF scale. Adjust 
fine OUTPUT VOLTAGE control knob as required, to obtain correct in- 
dication. For non-metered models use extremely connected meters and 
check that correct meter indications exist at output terminals 4 and 9. 


8. Power supply is now in proper operation. 


PROGRAMMED PRECISION REGULATED CONSTANT CURRENT OPERATION 


1. Remove AC power input to the supply and place the POWER 
ON switch in OFF position before connecting load to the supply: 


2. Determine load requirements. Connect load to the supply 
as shown in figure 10. Refer to paragraph on Programmed Current Con- 
nections. 


3. Turn the CURRENT LIMITER knob to the maximum desired set- 
ting. . 


4. Turn OUTPUT VOLTAGE control knobs to extreme CCW position. 


5. Apply AC power to the supply. Place POWER ON switch in | 
ON position and check that red POWER ON indicator is lit. 7 


6. Turn fine OUTPUT VOLTAGE control knob CW until the desired 
current setting is reached, as indicated by output current meter. 


Page 14 | LH 128 


Т. Check that output current meter indicates desired 
Value and that output voltage meter does not indicate OFF scale. 
ШЕ -геййігей, adjust external current programming control to ob- 
tain correct indication. For non-metered models use externally 
connected meters and check that correct meter indications exist 
ЕЕ output terminals 4 and о. 


8. Power supply is now in proper operation. 


SERIES CONNECTION CONSTANT VOLTAGE OPERATION, WITH CURRENT LIMIT 


AC power input to the "slave" (8) and "master"‏ 10975 رل 
(M) units and place POWER ON switches in OFF position before con-‏ 
пессіпе load to the supplies.‏ 


E с ле load requirements, select wire size from fig- 
ures 1-3 and choose correct type of series supply-load connections 
шоп ав ll ао 12. Refer to paragraph on CONNECTIONS FOR SER- 
IES OPERATION. 


3. Connect supply to load as shown on the selected connec- 
Eme required, select resistors Rpır, Rs and Rm, and 
diodes CRS and CRM in accordance with instructions contained in CON- 
NECTIONS FOR SERIES OPERATION. 


4, Turn (M) unit OUTPUT VOLTAGE control knobs to the de- 
Sired voltage setting. This setting will be approximately one-half 
ӨР ene COMME (M) and (S) unit output voltage. 


Б, Turn (S) unit OUTPUT VOLTAGE control knobs and CURRENT 
LIMITER control to extreme CW position. 


6. When current to the load must be limited to an intermed- 
late value within current rating of the unit with lower current cap- 
acity (M unit) turn the (M) unit CURRENT LIMITER control to the desired 
n c sc mbeprmediate current limit is required, turn the con- 
Urol CW bo che position for full current rating for the maximum am- 
bient temperature of operation. Refer to section on specifications. 


Hohen units of equal current rating are series 
connected, the (M) unit CURRENT LIMITER control must 
Beer ас å position slightly less than that of the 
W unit. 


Tf. Apply AC power to the supplies. 


8. Place POWER ON switches of both units in ON position and 
check that red POWER ON indicators are lit. 


A LH 128 Page. 15 


9. Check that output current and output voltage meters 
indicate desired values; total voltage is equal to sum of (S) and 
(M) units. As required, adjust OUTPUT VOLTAGE control knobs and 
CURRENT LIMITER control of (M) unit to obtain correct indications. 
For non-metered models use externally connected meters and check 
that correct meter indications exist at output terminals of the (S) 
and (M) units; positive (+) terminal of (M) unit and minus (-) term- 
inal of the (S) unit are the output terminals of the series combina- 
tion. 


Use front panel jacks (+) of (M) unit and (-) of (S) unit to make 
current and voltage cheeks for the appropriate units. For remote 
sensing connection, make cheeks at the load terminations of sensing 
leads from terminals 7 of (M) unit and from Rg connection of ME) uniti 


10. Power supplies are now in proper operation. 


SERIES CONNECTION CONSTANT CURRENT OPERATION, WITH VOLTAGE LIMIT 


1. Remove AC power input to the (S) and (M) units and place 
POWER ON switches in OFF position before connecting load to the sup- 
рее. 


2. Determine load requirements, select wire size arom res 
ures 1-3 and choose correct type of series supply-load connections 
from figures 11 and 12. Refer to paragraph on Connections Төр срез 
Operation. 


3. Connect supply to load as shown on the selected connec- 
tion diagram. As required, select resistors hpap, RS se 
diodes CRs and CRM as instructed in Connections for Series Operation 
paragraph. 


4, Turn (M) unit CURRENT LIMITER control to the desired set- 
ting. 


NOTE: When units of equal current rating are series 
connected, the (M) unit CURRENT LIMITER control must 
be set at a position slightly less than that of the 
(Spa xui b. 


5. Turn (S) unit OUTPUT VOLTAGE control knobs and CURRENT 
LIMITER control to extreme CW position. 


6. When load voltage must be limited to an intermediate 
value within the voltage rating of the series combination, turn the 
(M) unit OUTPUT VOLTAGE control knobs to a position approximately 
one-half the total voltage rating for the combination. 


If no intermediate voltage limit is required, turn the contralto 
the full CW position to obtain voltage limit at the maximum combined 
ratings of the supplies. 


Т. Apply AC power to the supplies. 


Page 16 LH 128 


8. Place POWER ON switches of both units to ON position and 
check that red POWER ON indicators are lit. 


ol that output current and output voltage meters indi-‏ یر 
cate desired values; total voltage is the sum of (S) and (M) unit volt-‏ 
Em s КОСЫ тей, adjust OUTPUT VOLTAGE control knobs and CURRENT‏ 
LIMITER control of (M) unit to obtain correct indications. For non-‏ 
metered models, use externally connected meters and check that correct‏ 
meter indications exist at output terminals of the (S) and (M) units;‏ 
positive (+) terminal of (M) unit and minus (-) terminal of the (S)‏ 
nit are the output terminals of the series combination.‏ 


Use front panel jacks (+) of (M) unit and (-) of (S) unit to make 
Gurrenv and voltage checks for the appropriate units. For remote sens- 
ШІР connections make checks at the load terminations of sensing leads 
from terminal 7 of (M) unit and from Rev connection of (8) unit, 


TO, Power supplies are now in proper operation. 


PARALLEL CONNECTION CONSTANT VOLTAGE OPERATION, WITH CURRENT LIMIT 


1, Remove AC power input to each supply and place POWER ON 
switch on both (M) and (S) units in OFF position before connecting 
load! to the supplies. 


Determine load requirements, select wire size from fig- 
Dres He manual. Refer to paragraph on Connections for Para- 
llel Operation. 


FS Гесс Supplies to load as shown in connection diagram, 
figure 155 


NOTE: When shipped from the factory, each supply 
Е Tor use as a constant current source or 
о 1-sensing constant voltage source. Jumpers 
are connected at the factory. Take care to remove 
the appropriate jumpers for load requirements that 
need different supply-load connections. Refer to 
the appropriate connection diagram. 


ША turn OUTPUT VOLTAGE control knobs on the 
deoi re (Әсе setting, and turn the controls on the 
CCW position. 


a unde со сае 
И CO LLY 


5. When current to the load must be limited to an intermed- 
Pave 0 turn the CURRENT LIMITER control on both the (M) and (5) 
Bp cs red current limit setting. Set current limit control 
Sache end (3) units to the position indicating the current value 
po be delivered by the respective unit. If no intermediate current 
ШОО en the control CW on both (M) and (S) units to the 
ревітісіп Tor full rated current for the maximum ambient temperature of 
Operation. Refer to section on specifications. 


6. Apply AC power to each supply. 


ШЕН 128 Pages ky 


7. Place POWER ON switches on (M) and (S) units in ON 
position and check that red POWER ON indicators are lit. 


8. Check that output current and output voltage meters 
on Doch (M) and (S) units indicate desired values; as required, ad- 
just OUTPUT VOLTAGE control amd CURRENT LIMITER control om (M) unit 
to obtain correct meter indications. For non-metered models е 
externally connected meters and check that correct meter indications 
exist at output terminals 4 and 6 of the (M) unit, or at front panel 
jacks (+) and (-) of the (M) unit; for remote sensing connection, 
check at the load termination of sensing leads on terminals ٢ ٢ ٢ 
or the MO ue ie. 


9. Power supplies are now in proper operation, 


PARALLEL CONNECTION CONSTANT CURRENT OPERATION, WITH VOLTAGE LIMIT 


1. Remove AC power input to each supply and place POWER ON 
switch on both (M) and (S) units in OFF position before connecting 
load to the supplies. 


о. Determine load requirements and connect 1027 ٢ a po n s 
plies as shown in figure 13. Refer to paragraph on Connection Ток 
Parallel Operation. 


3. Turn the CURRENT LIMITER knob on (M) unit to the desired 
current setting. Turn OUTPUT VOLTAGE control knobs on the (8) unit 
vo Tull CCW position, 


NOTE: When setting the CURRENT LIMITER knob on the 
(M) and (53 units take care to set the control o 
that each unit indicates the proportion of total 
current that the unio must supply, 


4. When load voltage must be limited, turn OUTPUT VOLTAGE 
control knobs on the (M) unit to the desired voltage limit Setting. 
If no voltage limit, within rating of the supply is desire cn 
controls onthe (M) unit to the full OW расся. 


5. “Apply AC power to esco supply. 


6. Place POWER ON switches on (M) and (S) units in ON posi- 
tion and check that red POWER ON indicators are lit, 


7. Check that output current and output voltage Mo Оп 
both units indicate desired values; adjust OUTPUT VOLTAGE control and 
CURRENT LIMITER control, as required, to obtain correct 11916307608. 
For non-metered models use externally connected meters and check that 
correct meter indications exist at output terminals 4 and 6 of the (M) 
unit, or at front panel jacks (+) аға (-) 97 the (M) uname 


8. Power supply is now in proper operation. 


Page 18 LH 128 


OPERATION AFTER PROTECTIVE DEVICE SHUTDOWN 


| Thermostat Shutdown 


The thermostat opens the input circuit only when the temperatures 
of the transistor heat radiator exceeds a maximum safe value. The 
thermostat will automatically reset when the temperature of the rad- 
lator decreases to safe operating value. After eliminating the cause(s) 
Dor overneatine and allowing time for the power supply to cool to a 
Proper temperature, resume operation of the supply. Refer to approp- 
riate operation paragraph in DETAILED OPERATING PROCEDURES. 


| Fuse Shutdown 


Internal component failure is prevented by fuses which protect the 


Weomponents rom damage caused by excessive currents. Fuses will blow 


n CE uu raved) current value for the fuse is exceeded. Fatigue 


| failure of fuses can occur when mechanical vibrations from the installa- 


tion combine with thermally induced stresses to weaken the fuse metal. 
‘Many fuse failures are caused by a temporary condition, and replacing 
the blown fuse will make the fuse protected circuit operative. 


ILH 128 Page 19 


MAINTENANCE 


GENERAL 


This section describes trouble analysis routine, replacement pro- 
cedures, calibration and test procedures that are useful for servie- 
ing the Lambda power supply. A trouble chart is provided as an aid 
for the troubleshooter. Refer to the section on specifications and 
features for the minimum performance standards. 


TROUBLE ANALYSIS 


Whenever trouble occurs, systematically check all fuses, primary 
power lines, external circuit elements, and external wiring for mal- 
function before trouble shooting the equipment. Failures and mal- 
functions often can be traced to simple causes such as іпргорег (птрегв 
and supply-load connections or fuse failure due to metal fatigue, 


Use the electrical schematic diagram and block diagram, figure 14, 
as an aid to locating trouble causes. The schematic dlagram contains 
various circuit voltages that are averages for normal operation. Meas- 
ure these voltages using the conditions for measurement specified on 
the schematic diagram. Use measuring probes carefully to 71 ٢ 1-٢٢٣ 
ing short circuits and damaging circuit components. 


CHECKING TRANSISTORS AND CAPACITORS 


Check transistors with an instrument that has a highly limited cur- 
rent capability. Observe proper polarity for PNP or NPN ON 
ror in measurement. The forward transistor resistance is low but never 
ZERO; backward resistance is always higher than the forward resistance, 
Resistance between transistor collector and emitter, in either direc- 
tion, varies with temperature; variation is greater for the вова 
direction resistance. 


For good transistors, the forward resistance for any JMN 
always greater than zero. 


Do not assume trouble is eliminated when only one part 18 replaced. 
This is especially true when one transistor fails, causing other trans- 
istors to fail. Replacing only one transistor and turning power on, 
before checking for additional defective components could damage the 
replace d component. 


When soldering semi-conductor devices, hold the lead being soldered 


with a pair of pliers placed between the component and the solder joint 
to provide an effective heat sink. 


Page 20 LH 128 


NOTH: The leakage resistance obtained from a 
ler resistance check of a capacitor is not 
ED ап indication of а faulty capacitor. Іп 
all cases the capacitors are shunted with resis- 


tances, some of which have low values. Only a 
dead short is a true indication of a shorted 
Bapacıtor. 


PRINTED CIRCUIT BOARD MAINTENANCE TECHNIQUES 


ШИА ГОТ 13 intact but not covered with solder it is а 
бой contact. Do not attempt to cover with solder. 


| 2. Voltage measurements can be made from either side of the 
"board. Use a needle-point probe to penetrate to the wiring whenever 
в Pprovective coating is used on the wiring. А brass probe can be 

.K о an alligator clip adapted to the measuring instrument. 


З. "Always use a heat sink when soldering transistors. 


4. Врокеп or damaged printed wiring is usually the result 
РЕ ео, Strain or careless soldering. To repair small 
breaks, tin a short piece of hook-up wire to bridge the break, and 
¡holding the wire in place, flow solder along the length of wire so 
спас it becomes: part of the circuitry. 


5. When unsoldering components from the board, flow the 
solder onto the Soldering iron tip; never pry or.force loose a part 
to Бе removed. 


TROUBLE CHART 


КҮТ CEMAET 18 intended as a guide for locating trouble causes, 
"апа is used along with the schematic diagram. 


The Operacing conditions assumed for the trouble chart are as follows: 


(a) AC power of proper voltage and frequency is present 
at input terminals. 


(b) Either positive or negative terminal is connected to 
ehassis ground. 


(с) The power supply is connected for constant voltage with 


local sensing. See schematic; dotted lines indicate 
jumpers connected for local sensing operation. 


‚IH 128 Page 21 


Symptom 


1. POWER ON lamp 
DS1 does not light 
with POWER ON switch 
in ON positions no 
output voltage 


2. Unable tond: 
just output volt- 
age 


Sur Zero vo kt DE 
output, with POWER 
ON indicator 116 


Page 22 


TROUBLE CHART. 


Probable Cause 


No power input; 
POWER ON switch 

Sl defective; de- 
fective fuse Fl; 
thermostat 52 

open, fuse Fl blown 


Damaged OUTPUT 
VOLTAGE controls 


supply operating as 
constant current 
source with cross- 
over at CURRENT 
LIMITER setting 


OUTPUT VOLTAGE con- 
GEO LS Gure uly 
CCW 


Short circuit across 
output of supply 


series regulator 
section open 


R37, R38 defective, 
open Q4, CR18-20 


Emitter followers open 


Current sensing re- 
sistor open 


Improper preference 
supply operation as 
indicated by voltage 
between output term- 
inal CENGE: on 
fine regulator board 


replace 52% 


Remedy 


Check power source, line 
cord апа 1116 ۹777 1 plugs 
replace F1; 
shut off 116 و‎ ٢٢ ٢ uc 
cool and check ambient 
temperature 


Replace Fl; if it blows 
immediately, check diodes 
CR14-17 and capacitor Da 
replace as necessary 


Check ВТА and RIB for 
shorts and/or open, re- 
place as necessary 


Remove load and check for 
shorts and/or improper 
supply-load connections; 
refer to appropriate diss 
gram for correct connection 


Check OUTPUT VOLTAGE con- 
trols for proper setting 
and correct as necessary 


Check load and load con- 
nections, correct as nec- 
essary 


Check Q10-Q15 for open, 
replace as necessary 


Check R37, R38, ӨШ, ORIS-28 
for open, replace as nec- 
essary 


Check Q8 and Q9 for open, 
replace as necessary 


Check R43 for open, re- 
place as necessary 


The reference voltage be- 
tween terminal 7 and Т.Р. 
should be 7.5. Bo کل‎ 
if this voltage does not 
exist, then check Q6 for 
open, Q5 for short, ORO 
and CR9 for short or CR10 
and CR11 for open; гер1асе 
as necessary 3 


ІН 128 


Symptom 


Д Hieh ripple 
at line frequency 
pp twice line fre- 
quency and unregu- 
lated DC output 


5. Same as 4, 
except inter- 
mittent 


бы > High ripple 
at frequeney other 
than line or twice 
line frequency 


T. Large spikes 
at output 


LH 128 


TROUBLE CHART (cont'd 


Probable Cause 


Series regulator 
transistors shorted; 
emitter followers 
shorted; voltage 
amplifier ‘open 


Defective main 
rectifier: causes 
ripple at twice 
line frequency 


Line voltage too 
low 


Foreign matter fallen 
into unit 


Emitter follower 

Ico resistors open 
or changed value 
causing thermal run- 
a-way 


03611132019 due. to 
defective component 
in filter network 


Capacitor C10, CTI 
open 


Remedy 


Check and replace as 
necessary: Q10-Q15; 
Q8, Q9 and Q3 


Cr1i4-17 in addition 
to 08-012 and 93 


Check and correct AC 
input voltage at supply 
terminals 


Check for loose bench 
hardware and wire clip- 
pings that may have 
fallen through cover 


Check R33, R34 and R36 
values and replace as 
necessary 


Check for open Cl, C2 
and check for open and/or 
short in HIS, CGsand Co, 
R11 network and replace 
defective component 


Replace C10, Cll as 
necessary 


Page 23 


ADJUSTMENT OF CALIBRATION CONTROLS 


| 
Whenever parts are replaced, adjust calibration controls only when 
voltage and current indications are improper and do not reflect maxi- | 
mum ratings, 


Adjust Calibration Control R5 as Follows: | 


1, Remove AC power input to the supply and place POWER ON 
switch in OFF position, 


2, Unsolder wiper of R5 from resistor housing. 


3, Operate the power supply for constant voltage with local- 
sensing Jumpers connected as shown in figure Y, and no external load. 


4, Turn OUTPUT VOLTAGE control knobs fully clockwise and, 
using a DC voltmeter of one percent accuracy or better, adjust R5 to 
provide output voltage Eq MAX + 0,25 volts at 25°C ambient; where Eo 
MAX 18 the rated output voltage of the supply. 


5, After adjustment 18 completed, remove AC power input 
to the supply and solder wiper of R5 to potentiometer housing, 


Adjust Calibration Control Н1) as Follows: 


1, Remove AC power input to the supply and place POWER ON 
switch in OFF position, 


2. Unsolder wiper of R14 from resistor housing. 


3, Turn OUTPUT VOLTAGE control knobs and CURRENT LIMITER 
control fully CW, 


4, Operate the power supply for constant current crossover, 
connected as shown in figure 4, with a short circuit across the output 
terminals, 


5, Adjust КІЛ for 2.52 ampere output, using any DC ammeter 
of one percent accuracy or better, 


6, After adjustment 19 completed, remove AC power input to 
the supply and solder wiper of НІЛ to potentiometer housing. 
PERFORMANCE CHECKS 


Checks With Constant Voltage Operation 


Check the ripple and regulation of the power Supply using the test 
connection diagram shown in figure 15, Use suggested test equipment 
or equivalent to obtain accurate results, Refer to SPECIFICATIONS AND 
VEATURES for minimum performance standards, 


Page 24 LH 128 


Set the differential meter, DC VIVM (John Fluke Model 801H or equiva- 
lent ) to the selected power supply operating voltage. Check the power 
Supply load regulation accuracy while switching from the load to no- 
load condition. Long load leads should be a twisted pair to minimize 
AC pick-up. 


Use a Variac to vary the line voltage from 105-135 or 135-105 volts 
AC and check the power supply line regulation accuracy on the VTVM 
differential meter. 


Use a VIVM, Ballantine 320 or equivalent, to measure rms ripple volt- 
age of the power supply DC output. Use oscilloscope to measure peak- 
to-peak ripple voltage of the power supply DC output. 


Checks With Constant Current Operation 


Check the ripple or regulation of the power supply using the test 
connection diagram shown in figure 16 or 17. Refer to SPECIFICATIONS 
AND FEATURES for minimum performance standards. 


Check the power supply load regulation accuracy while switching from 
ШЕ ИТ to load condition. Measure the voltage across sens- 
ing resistor Rs. Use John Fluke Model 801H or equivalent for the VIVM 
connected across Rs. For Rs, use a resistor having the same value as 
ПАВЕ 1 the unit being tested. To obtain regulation figure, 
Substitute values obtained into regulation formula: 


AE 
Rs 
where AE is the voltage change in milli- 
volts and Rs is the resistance of the sens- 
ing resistor. 


= Regulation in milliamperes, 


1 ٢ - тату the line voltage from 105-135 or 135-105 volts 
АС and check the power supply line regulation accuracy using VTVM and 
. the regulation formula: 


AE 
Rs 


To measure rms ripple current of the power supply DC output, use a 
Ballantine Model 320 or equivalent meter and obtain ripple current Ir 
by substituting measured values into formula: 


BORN C. ete 
E go E 


s LH 128 š Page 25 


SERVICE 


When additional instructions are required or repair service 
desired, contact the nearest Office. оғ the Lambda Electronic sm PDA 
where trained personnel and complete facilities are ready to assist 
you. 


Please inelude the power supply model and serial number together 
with complete details of the problem. On receipt of this information, 
Lambda will supply service data or advise shipping for factori epai 
service. 


All repairs not covered by the warranty will be billed ао 
an estimate forwarded for approval before work is started. 


PARTS ORDERING 


Standard components and special components used in Lambda power 
supply can be obtained from the factory. In case of emergencias 
ical spare parts are available through any Lambda office; 

The following information must be included when ordering parts: 


1. Model number and serial number of power supply 
and purchase date. 


2. Lambda part number. 
Description of part together with circuit designatlon. 
4. If part is not an electronic part, or is пов В 


provide a description, function, and location "MD 
part. 


Page 26 LH 128 


CIRC, 
` DESIG. 


С1* 


C2 


C3 
C4+ 
C5 


C6+ 
СТ 


C8 


C9 
C10 


C11 
C12 


C13, 
C14 
C15+ 


C16+ 


C17 
C18 
C19- 
C23 
C244 +, 
C25 
CR1 
thru 
CR4 
CR5 


CR6 
CRT 


added to the model no. 
au CEE ERS OM this listing. 


PARTS LIST 


The electrical parts located on this model are listed here 
together with parts for models that carry the (FM) or (S) suffix. 
Enc 1157 also is valid for the same LH models with letter A 
Parte. ror в opblon and У option are included 


MODELS LH 128, LH 128FM, LH 1288 


LAMBDA UNIT 
DESCRIPTION NO, PRICE 
Cap., elect., 5 mfd CBN-50-014 $1.45 
-10% +100% 150 VDC, 
175V Surge 
Cap., elect., 520 mfd CBR-52-025 2.15 
-10% +100%, 100 VDC, 
130V Surge 
Cap., tant., 2.5 mfd CBN-25-010 1.80 
-15% +75% 100 vde 
Cap., mica 470 mmfd CCJ -47 -004 . 46 
+20%, 300 VDC 
Cap., mylar .01 mfd CGL-10-002 ‚36 
+10%, 200 VDC 
Same as C5 
Cap., tant., 1. 0 mfd CBN-10-009 1.33 
+20%, 35 VDC 
Cap., elect., 75 mfd CBP-75-009 1.96 
-10% + 100%, 55 VDC, 
75V surge 
Cap., mylar, .10 mfd CAM-10-012 .65 
+10%, 200 VDC 
Cap., mylar, .22 mfd CGM-22-002 .41 
+10%, 6 
Not assigned 
Cap., elect., 3,100 mfd CBS-31-024 11.97 
-10% +100%, 110 VDC, 
140V surge 
Cap., ceramic, 0.02 mfd CDL-20-003 .30 
+20%, 125 VAC 
Cap, mylar, .0068 mfd CGK-68-001 .34 
+10%, 200 VDC 
Cap, ceramic, 240 mmfd CDJ-24-001 504 
+20% 1000 VDC 
Same as C5 
Same as C7 
Not assigned 
Cap., mylar, .01 mfd CGL-10-002 . 36 
+10% 200 VDC 
Rectifier FBL-00-030 1.40 
Rectifier FBL-00-043 1.40 
or 

FBL-00-036 .60 
Same as CR1 
Same as CR5 


CIRC, 
DESIG. 


CR8 
CRI# 
CR9 
CR10, 
CR11 
CR12 
CR13 
CR14 
thru 
CR17 
CR18 
thru 


CR23+ + 
р51її 


DESCRIPTION 


Rectifier, zener diode 
Rectifier, zener diode 
Rectifier, zener diode 
Rectifier 


Not assigned 
Not assigned 
Rectifier 


Rectifier 


Same as CR1 

Pilot Light Assembly 
Fuse, cartridge, 6.25 
amperes, "SLO-BLO" 
3AG 

Meter, volts DC, 0-60 
VDC 

Meter, amperes DC, 0-3 
amperes 

Transistor, PNP 
Transistor, NPN 


Transistor, reference 
element 

Transistor, NPN 
Transistor, NPN 
Transistor, NPN 
Transistor, NPN 
Transistor, NPN 


Res., two-sec., ww, 
var., 12,000 ohms total, 
+5%, 2w each section 
Res., film, 2, 400 ohms 
+5%, 1/2w 

Res., wirewound, 6.2 
ohms +5%, 2w 

Res., wirewound, 1, 250 
ohms +1%, 2w 

Res., var., ww, 600 
ohms +10%, 1-1/2w 


MODELS LH 128, LH 128FM, LH 1288 (Cont) 


LAMBDA 
NO. 


FBM-1N965B 


FBM-1N3029B 


FBM-Z105 
FBL-00-036 


FBL-00-039 


FBL-00-054 
or 
FBL-00-037 


HRD-00-007 
FFC-06-250 
EBP-60-015 
EDN-30-019 
FBN-L103 
FBN-L101 
FBN-L104 
FBN-L102 
FBN-L108 
FBN-35903 


FBN-35903 
FBN-35902 


DNT-12-006 
or 
DNT-12-033 
DCS-24-001 
DFN-62-045 
DES-12-010 


DNR-60-012 


. 58 


Page 27 


CIRC, LAMBDA UNIT CIRC, LAMHDA J| 
DESIG, DESCRIPTION NO, PRICE DESIG, DESORIPTION NO, 4 
R6 Res., comp., 150, 000 DEB-1541 $ ,12 Rat Not assigned 
ohms +10% 1/2w Råbe Res., comp., 2, 200 DID-2221 
R7 Res., comp., 4, 700 DEB-4721 ‚12 ohms 410%, 1/2w 
ohms +10% 1/2w R29 Not assigned 
R8 Res,, comp., 8, 200 DEB-8221 ‚12 thru 
ohms +10% 1/2w ШЕ 
R9 Res., comp., 15, 000 DEB« 1631 ‚ 14 ПЕЕ Мен, , сотр», 440 0 0132211 
ohms 出 10% 1/2w 110% 1/2w 
R10 Res., comp., 39, 0 DEB-3931 ‚ 12 RIA, Rea,, Wirewound, 0 DPR 206061 
ohms +10% 1/2w Rab ohma 45%, 7۷ 
R11 Ros., comp., 100 ohms DEB-1011 ‚12 
+10% 1/2w R36 Same as R11 
R12 Res,, comp., 3,300 DEB-3321 ‚12 ROY Rəs., wirewound, 3,5 DFN«35-047 
ohms +10% 1/2w thru ohma 42%, Sw 
R134 Res,, comp., 390 ohms DEB-3911 (Ad RAA 
+10% 1/2w n43 Res., wirewound, 0, 21 БИМ 4 
R14 Res,, var,, ww, 5,000 DNS-50-015 ‚ 43 ohma 45%, ۷ 
ohms 410%, 1-1/2w [ Ros,, comp., 1, 000 DEB«1021 
RI5 Res., film, 4,700 отв — DCS-47-003 ‚26 ohma 410% 1/2w 
45%, ۷ 14644 Game as 4 > 
R16 Bui, var.) ЫП DNR-50-013 1,00 Bitt Awitch, toggle, SPAT 0821160171 
ohms 15%, буу „11. 
R17 Not assigned FDA»=11-034 
R18 Res,, wirewound, 500 DER-50-011 ‚07 82 Thermostat VKA-137-014 
ohms +1%, 2W ті Transformer ABA» 40 
R19 Res., wirewound, 7,500 1018-1-00 1, 22 11% Binding post, red НАС-01-206 
ohms 41%, 2w | J2* Dinding post, white WAC»01«205 
R20 Res., comp., 330 8 DEB-3311 ‚12 Jar Binding pont, black НАС-01-207 
%10% 1/2w 41% Tent jack, red HAR »00-002 
R21 Same as R11 J2** Teal jack, black HAN 006001 
R22 Res., film, 12, 000 ohms — DCT-12-000 ‚25 РЫ Muse, 5 атра PPT 05-000 
45%, 1/2w R” — Нов, , ww, 3. 0 0 DFN- 30-004 
R23 Res., film, 390 ohms DCR-39-001 ‚20 thru 42%, Bw 
45%, iw It42 
R24 Res. , win 470 DFR=-47-048 1,20 
ohms 42%, 10w DA TT "n 
R25 Not assigned PARTE TOR Re 
R26 Нев., comp,, 9, 100 DHB-9125 ‚20 


ohms 45%, 2w 


* Applies to "FM" models only 
** Not used on "8" and "FM" models 


PARTS LIST (Cont) 


MODELS LH 128, LH 128FM, LH 1288 (Cont) 


Transformer ТІ changes on unit with "IE option, 


MODELS LH 128, LH 128FM, LH 1288 (Cont) 


Wor 


transformer T1 used in this model peo standard parte 0 
for the standard transformer part no, and add 517 


"RU to the part no, 


Price for T1 does not chango, 


! This part only used on unita with serial по, prefixes А, В 
+ This part only used on units bearing serial по, prefix A 
++ This part not used on units bearing serial no, prefix A 
TT Not used on "8" models à 


"These parts only used on LH128A, LH128A- FM, LH12BA- 8 


PANTS FOR "V" OPTION 


The following parta 
change and ۹ 7 
ін added to DHT: 


ri Fuge, "BLO-BLO" 
1,25 amperen 


111-0 Å 


n52 Wes, , comp, , 120, 000 DEN» 1241 T 

(081) ohma s 10%, 1/2w 

11 Transformer Add Вий Han 
"V" to Hop. Weg, 
T1 no, } 


Page 28 


350 


Е 1 
ж 
СМ 
$ 200 x 7 
^ 
у 1 150 p 
o Q nå 
83 g 
E 100 > 
> (^ 
^o ٣۳ — 
Юю 
Å ا‎ | 
٩ ۴ 20 86 
CABLE LENGTH WIN FEET (BEE FIG 3) 
MIG 2WIRE CONNECTION (SEE. FIG 4) 
|76 
150 y 
W i25 
4 
å 
HE | 
dU m 
Q 
8 J : 
5 50 


25 


25 


FIG, 2, IMPROVED 2-WIRE CONNECTION (SEE КЇЗ б) 


; Гн ы 
En | 


SPY LOAD 


-0С604--------- le 


——— 


FIG, 8, CABLE LENGTH WIN FEET 


LOAD 


NOTE. 


* FOR NEGATIVE GROUND,DISCONNECT JUMPER FROM TERMINALS 
5 AND 6 AND RECONNECT TO TERMINALS 4 AND 5. 


FIGURE 4. TWO-WIRE CONNECTION 


105-135 VAC 


(9 @ (9 ® 


ES am PESE ada ess, M TE e لاس‎ en meret s eA 


LOAD 


NOTE: А 
X FOR NEGATIVE GROUND,DISCONNECT JUMPER FROM TERMINALS 
5 AND 6 AND RECONNECT TO TERMINALS 4 AND 5. 


FIGURE 5. IMPROVED TWO-WIRE CONNECTION 


105-135 VAC 


NOTE. 
X FOR NEGATIVE GROUND, DISCONNECT JUMPER FROM TERMINALS 
5 AND 6 AND RECONNECT TO TERMINALS 4 AND 5. 


FIGURE 6. FOUR- WIRE CONNECTION 


105-135 VAC 
45-480 CPS 


105-135 VAC 
45-480 CPS 


PROG. VTGE. 
20044 /VOLT 


PROG. VTGE.. 
200411 / VOLT 


(A) LOCAL SENSING (B) REMOTE SENSING 


NOTE: 
X FOR NEGATIVE GROUND, DISCONNECT JUMPER FROM 
TERMINALS 5 AND 6 AND RECONNECT TO TERMINALS 
4 AND 5. 


FIGURE 7. PROGRAMMED VOLTAGE, WITH EXTERNAL RESISTOR 


PROGRAMMING 
VOLTAGE 


PROGRAMMING 
VOLTAGE 


LOAD 


(A) LOCAL SENSING (B) REMOTE SENSING 


NOTE: 
Ж FOR NEGATIVE GROUND, DISCONNECT JUMPER FROM 
TERMINALS 5 AND 6 AND RECONNECT TO TERMINALS 
4 AND 5. 


FIGURE 8. PROGRAMMED VOLTAGE,WITH EXTERNAL PROGRAMMING VOLTAGE SOURCE 


105-135 VAC 


EGNE) 


LOAD 


NOTE: 


* FOR NEGATIVE GROUND, DISCONNECT JUMPERS FROM TERMINALS 
5 AND 6 AND RECONNECT TO TERMINALS 4 AND 5. 


FIGURE 9. PRECISION CONSTANT CURRENT 


PROG. CUR. 

1009 2W. 

FOR 5% TO 100% 
RATED CURRENT 


NOTE: 
X FOR NEGATIVE GROUND, DISCONNECT JUMPER FROM TERMINALS 
5 AND 6 AND RECONNECT TO TERMINALS 4 AND 5. 


FIGURE IO. PROGRAMMED PRECISION CONSTANT CURRENT 


[(M)UNIT — — 


EH 


| 
| Та 
eren 
| og 
| 
| 
| 
| CR 
05 M 
| | jx 
| 
| 
| 
| 
| 
| Rs 
| 
LOAD 
E 
x 
Wr CRs 
g 
lx 
(A) LOCAL SENSING (B) REMOTE SENSING 
NOTE: 


MAKE ONLY ONE GROUND CONNECTION FOR THE SERIES COMBINATION; TO CHANGE GROUND AS 
SHOWN, REMOVE JUMPER FORM TERMINALS 5 AND 6 ON (M) UNIT AND CONNECT ANY ONE OF 
THE OTHER JUMPERS AS SHOWN IN DOTTED LINE. 


FIGURE Il. SERIES CONNECTION 


nur 1 Exo UNITS. a 


105 -135 VAC 
45-480CPS 
105 135 VAC 
45-480CPS 


(A) LOCAL SENSING (B) REMOTE SENSING 


NOTE: 


X MAKE ONLY ONE GROUND CONNECTION FOR THE SERIES COMBINATION; TO CHANGE GROUND AS 
SHOWN, REMOVE JUMPER FROM TERMINALS 5 AND 6 ON (M) UNIT AND CONNECT ANY ONE OF THE 
OTHER JUMPERS AS SHOWN IN DOTTED LINE. 


FIGURE 12. ALTERNATE SERIES CONNECTION 


o o 8 ШШ 7 
105-135 VAC 44 | | 105-135 vac ES 
45-480 CPS -0 = OC | | 45-480 CPS BC = «DC 
| 


LEURS و يی‎ SS SS 


OOO Geo | 


| 

| 

| 
тоо 
juu 

| 

| 


NOTE: 
X FOR NEGATIVE GROUND, DISCONNECT JUMPER FROM 
TERMINALS 5 AND 6 AND RECONNECT TO TERMINALS 
4 AND 5. 


FIGURE 13. PARALLEL. CONNECTION, LOCAL SENSING 


Ч3Л055082 ІМЭУУПЭ LNVISNOO ONY 39VLIOA LINVISNO2'WVH9VIO 92018 “bl 340913 


glo чая 


-tl‏ 1182 910-010 دو 
1ndino IN3YYND 531935 NIV‏ 


£O 
له‎ 2 1dWV 
39V LTOA 


, 60 80 
84132۸00 1103 
“ЕРЕШЕ 


82 431134 


НІМ УІ GH tt 2940 ФО ; 2 

ЯНОМ LIN لا‎ 3 JI1dAV له‎ 3 ۸/۳۱٢٧ 6H9 ‘8U 331311933 

узала 1V11N3Y33310 LIWIn ‘934-334 AYVITIXOV 
9NISN3S ANVLIN3W31dNOO 1N3YYN9 


90 
YOLV 11938 
531535 


so 
ل1‎ 3 
39N3H3439S 


POWER SUPPLY 


POWER SUPPLY 


OSCILLOSCOPE 


0 
© 
RIPPLE 

© METER 

@) 
Sn Os 143 DIFFERENTIAL 
U Битен METER 
10 


O 
VARIAC IISV. AC 
O 


— feet) 


og 
< 
>o 
OG 
Gå 
(19) 

9% 


NOTES: 


I. REGULATION AND RIPPLE CHECK METERS MUST NOT ВЕ 
GROUNDED THROUGH THREE-WIRE LINE CORD TO GROUND. 


2. PERFORM CHECKS WITH LOCAL SENSING CONNECTIONS ONLY. 


FIGURE I5. TEST CONNECTIONS FOR CONSTANT VOLTAGE PERFORMANCE CHECKS 


SWITCH 


DIFFERENTIAL 
METER 
(VTVM) 


RIPPLE 
METER 


VARIAC ПОМ. AC 


105-135 VAC 
45-480CPS 


ee OÓ LINEZGND: 


NOTES: 


i, REGULATION AND RIPPLE CHECK METERS MUST NOT BE 
GROUNDED THROUGH THREE-WIRE LINE CORD TO GROUND. 


2. PERFORM CHECKS WITH LOCAL SENSING CONNECTIONS ONLY. 


FIGURE 16. TEST CONNECTIONS FOR CONSTANT CURRENT PERFORMANCE CHECKS 


POWER SUPPLY 


LOAD 


SWITCH 


RIPPLE 
METER 


O 


O LINE GND. 


oo 
< 
E 

og 
23 
wo 

og 


NOTES: 


I. REGULATION AND RIPPLE CHECK METERS MUST NOT BE 
GROUNDED THROUGH THREE-WIRE LINE CORD TO GROUND. 


2. PERFORM CHECKS WITH LOCAL SENSING CONNECTIONS ONLY. 


FIGURE 17. TEST CONNECTIONS FOR PRECISION CONSTANT CURRENT PERFORMANCE CHECKS 


DIFFERENTIAL 
METER 


(VTVM) 


-——— 1 


GENERAL DESCRIPTION 


Rack adapter LRA-1 is designed for 
use in equipment racks where rugged- 
ized mounting of units is required. 
The adapter can be used with or with- 
out chassis slides. 


Вак adapter LRA-2 is designed for 
simpie applications of rack installa- 
tion where chassis slides and rugged- 
ized mounting of equipment are not 
required. 


Both rack adapter LRA-1 and LRA-2 
can be used to install 1/4-rack or 
1/2-rack power supply units into equip- 
ment racks. Each adapter can accept 
various combinations of 1/l and 1/2- 
rack units up to four 1/4-rack units 
or two 1/2-rack units. 


INSTALLATION OF 1/2 RACK UNITS INTO 
LRA-1 


To install 1/2-rack power supply 
units, remove slide numbers 2 and 3 
and/or 6 and 7, together with securing 
hardware and associated slide bar nut. 


Using slide screws and slide bar nuts 
that were removed, store removed slides 
on the frame at the rear of the adapter 
where screw clearance holes are pro- 
vided for securing each slide to the 
adapter. 


SHIPMENT OF UNITS MOUNTED IN LRA-1 


To protect the unit against damage 
from shock and vibrations when trans- 
porting adapter with installed units, 
eight universal tie-down mounting 
holes, located in the adapter base, 
at the rear of the rack adapter, are 
used to secure 1/4-rack and/or 1/2- 
Pack units into the rack adapter. 
Secure each unit using two 6-32 x 5/8 
Screws, two lockwashers and two spacers 
installed from the bottom side of the 
rack adapter. See detail A for typical 
securing hardware. Eight spacers are 
Supplied with rack adapter LRA-1. 


RUGGEDIZED MOUNTING 


When ruggedized mounting of units 
is required, follow the procedure 
described for SHIPMENT OF UNITS 
MOUNTED IN LRA-1. See detail A for 
typical securing hardware. 


MOUNTING CHASSIS SLIDES 


Mount chassis slides using the 
following hardware. To assure unre- 
Stricted mounting of units into the 
adapter designated screw lengths 
must not be exceeded. Insert screws 
into designated holes and secure 
slide in position using long bar nut 
supplied with rack adapter LRA-1. 


CHASS ES TRAK NO, отет: 
OSSE o 10/16 fl-na(82?); 
use A holes. 


JONATHAN NO. 130 QD: 
6-39 x 1/2 Ғ1-һа(82%); 
use В апа € holes. 


GRANT PULLEY NO. 4435: 
5-22 K 5/16 fi-hd(100"); 
use B and D holes. 


USING BLANK PANELS AND BLANK CHASSIS 


Blank front panels Model LBP-10 
and LBP-20 are available for cover- 
ing any 1/4-rack or 1/2-rack opening 
respectively. The blank panels can 
be used with rack adapter LRA-1 and 


LRA-2 whenever a 1/4-rack or 1/2-rack 


space in the adapter is not occupied 


ву a unit.: 
ition using four 6-32 x 3/8 pan-head 


screws supplied with the rack adapter. 


Paneled blank chassis Models LBC-10 


(1/4-rack size) and LBC-20 (1/2-rack 
size) are available for any 1/4-rack 


or 1/2-rack equipment design package. 


These blank chassis enable the user 
of rack adapters LRA-1 and LRA-2 to 
design system equipment that can be 
packaged on ready-made chassis that 
are compatible with existing system 
components. Both blank chassis can 
be used with rack adapters LRA-1 
and LRA-2. 


Secure each panel in pos- 


REAR TIE-DOWN MOUNTING HOLES 
(FOR RUGGEDIZED MOUNTING 
SEE DETAIL "д" ) 


SLIDE BAR NUT 


SLIDE 
NOS. 2 83 


LRA-| 


LOCKWASHER 
SPLIT, NO.6 


БЕ SCREW, NO. 6-32 x A 


DETAIL A 


LRA2 


FRAME 
REAR 


OVER CHASSIS: 
гт (OVER CHASSIS) —- 


TE 8 


=) 
È 


| ITS Ye) 
17 


19 


7% ТУР: 
(№ RACK MOUNTING) 


22 TYP. 


(1/4 RACK 
MOUNTING) 


SLIDE 
NOS.687 


MOUNTING HOLES PROVIDED FOR CHASSIS SLIDES: 


"B'a"C" HOLES — LAMBDA SLIDES NO. KHT-30-007 (I PAIR), LENGTH=16,TRAVEL=15 


"ea 
"A"H 
"В" 5 


"с" &"D" SLOTS ARE 5/32 WIDE х 1/4 LONG 


lig х Эв SLOT (TYP) 


TABLE OF WEIGHTS 
> 

ша- | 12 | 18 | 
ЕГІС ШЕШЕГЕ 


"А" HOLES - CHASSIS TRAK, INC. 


"D" HOLES — GRANT PULLEY CO. 


OLES ARE 1/4 DIA. 
LOTS ARE 5/32 WIDE X 1/2 LONG 


FIGURE 18. 


NO. CTS-116 


NO.4435 -LENGTH=16,TRAVEL=15 


LONG BAR NUT (FOR OUTSIDE 
SLIDE MT'G.) 


RACK ADAPTERS LRA 1, AND LRA 2 

b 
E 
74 


SCB 128 С 


R24 
470 42% REFERENCE SUPPLY Ma 
10 — үкі — 624 一 一 一 一 一 一 -- — —— -------------------- 2 АЕ 
sorts IT | | 
i @ د‎ 
l. RESISTOR VALUES ARE IN OHMS UNLESS OTHERWISE NOTED. Ф) (өз) жы) o toov. N 
2. RESISTOR WATTAGE 1/2 WATT; RESISTORS ABOVE 2 WATTS `), FE Ç 2 SERIES (+9۷) RS 1250 21% 
ARE WIREWOUND UNLESS OTHERWISE NOTED. (922 CRIO ( ) REGULATOR å RIS RI4 RS ЕЕ = 600+10% 2w,ww 
ў +! FBL-00-0; 500+1% 5К+ 0% р 
33 rege COMPOSITION £ 10%; WIREWOUND * 5 % pe Tiran | ca. TEME WW 1 ٧ ES بې‎ k Ç R6 Ж ере 
A WISE NOTED. (34VAC) Т 55V R22 2 +61v +59.5 150K (+1.8V) 
` CAPACITOR TOLERANCES: ELECTROLYTIC 10% + 100%; IMF GR6 (+1.94) 
TANTALUM,-15% +75%; PAPER, %10%; CERAMIC,+20%,MICA, +20%, SURGE |2К:55% (+8.5V) 35V ; R44 ст 
MYLAR, +10%; UNLESS OTHERWISE NOTED. 6) (612) 2 WFILM TANT. CR4 GR2 
5. SYMBOLS: DEUX e 
7.5К+1 47к%5 он 200У 
} INDICATES CLOCKWISE ROTATION OF $ 2w,ww Ya WFILM OR GATE MYLAR | 
HAFT. Q5 REFERENGE 2 av 
å T 
== INDICATES CONNECTION TO CHASSIS. Er РЗ ыен E0 EBU FBN-LIOI 
JE PREREGULATOR ТУ) Ват, 27у) BN-L 
ICATES ADJUSTMENT OR CALIBRATION CONTROL. (NOTE 11) VOLTAGE +60.5V 92 FBN-LIO3 
~ Qi 
ЕГІ INDICATES ACTUAL UNIT MARKING. +57V (4>) Е USED CRT AMPLIFIER (+.82V) IN Re | 
[2] INDICATES FRONT-PANEL MOUNTED COMPONENT. CRII слу) 4: 09-00 042 en FBN-LIOI Øy EAA 
FBL-00-036 FBMCNSCSE FBL-00-036 EBE002056 EEE LMFILM 
Ж INDICATES FACTORY ADJUSTMENT, SEE INSTRUCTION MANUAL. R20 RIO DIFFERENTIAL (na 
39K 
© INDICATES TRANSFORMER LUG TERMINAL. | 20 +59,5V AMPLIFIER + 
+60V (+.7V) 2.5MF 
DH THIS DIODE IS LAMBDA PART NO. FBL-00-030; CAN (+.7V) 100V, TANT TBI 
BE REPLACED WITH STANDARD ТУРЕ IN645 DIODE ote REAR OUTPUT 
UNLESS OTHERWISE NOTED. (+1.04v) TERMINALS 
6. CONDITIONS FOR CIRCUIT POINT VOLTAGE MEASUREMENTS. ара 


А. CONSTANT VOLTAGE 
READ ITALICIZED NUMBERS FOR CIRCUIT POINT 
VOLTAGES WHILE IN CONSTANT VOLTAGE OPERATION. 
INPUT: 120 VAC, 60 CPS. 
OUTPUT: 60 VOLTS, OUTPUT CURRENT ZERO. 


B. CONSTANT CURRENT 
READ NUMBERS IN PARENTHESES FOR CIRCUIT POINT 
VOLTAGES WHILE IN CONSTANT CURRENT OPERATION. 
INPUT: I20 VAC, 60 CPS, 30*C AMBIENT. 


SERIES REGULATOR 
06 R42 


FOR LHI28FM ONLY 
MIT саа 


(2) 


OUTPUT: O VOLTS, OUTPUT CURRENT 2.4 AMPS (SHORT CIRCUIT). с13,С14 ба 
INDICATED VOLTAGES ARE TYPICAL VALUES AND ARE DG (25 МГ 
UNLESS OTHERWISE NOTED. سا اح‎ 


DC MEASUREMENTS TAKEN WITH 20,000 OHMS / VOLT 
VOLTMETER BETWEEN —DC (TERM. 4) AND INDICATED POINTS 
UNLESS OTHERWISE NOTED. 

7. DESIGNATIONS ARE LAMBDA PART NUMBERS. 


INDICATES TERMINAL LOCATED ON TERMINAL BOARDS "А", 
"С" &'D' OR PRINTED WIRING BOARD "B". 


| 
=| 


014 
FBN-35902 


013 
FBN-35902 


9. COAT BOTH SIDES OF MICA WASHER WITH DOW CORNING 
NO. 340 SILICONE GREASE. 


IO. C24, C25, R45, R28, CR23, 07 NOT USED ON UNITS BEARING 


SERIAL NO. PREFIX А; C4, C6, CIS, СІ6, A RI3 ONLY USED ОМ 
UNITS WITH SERIAL NO. PREFIX "А". (SEE SCHEMATIC NO. SCB |28 A) 


| RATING TABLE | TABLE 


IENT MAX. 
TEMP. LOAD 


012 
FBN-35902 


30°C 
|. CRS WAS FBM-IN3029B ON UNITS WITH SERIAL NO. PREFIXES А, В. me 
12. F2 NOT USED ON MODELS LH 128, LHI28S, LHI28FM ой 60°C 


FBN-35902 FOR LHI28FM| ONLY 71°C 


13. FI IS 3AMPS, AND R52 IS ADDED FOR UNITS WITH "У" OPTION 
ONLY. 


14. R37 THRU R421S 3.0 OHMS, SW ON UNITS WITH A SUFFIX. 


MICA 
INSULATING 


1 WASHER 


(+80.5\) 


оо 
FBN-35902 


FOR WIRING OF POWER SUPPLY 
TO LOAD REFER TO POWER 
SUPPLY-TO-LOAD WIRING DIAGRAMS, 


CAUTION (NOTE 13) 


NOT AT CHASSIS GROUND POTENTIAL 
DO NOT SHORT TO CHASSIS GROUND 


MAIN RECTIFIER 


99 


DA 
“--..сна5515 


Fi 9م‎ 


Y 


DOTTED CONNECTIONS SHOWN ON| 
6.25 AMP ] | TBI INDICATE JUMPERS IN 
GROUND E FOR LHi28 а PLACE FOR ^2 WIRE CONNECTION.” 
TYPICAL CRI4 THRU CR22 Å қ LHI28FM ONLY | 
CR5 A ся? SLO-BLO | 
FBL-00-043 
(NOTE 13) | { 3 THIS SCHEMATIC APPLIES TO UNITS E 
BEARING SERIAL NO. PREFIXES B,C | 
y ! } 200V 
y NOTE 9 н MYLAR or ma 
MICA SCHEMATIC DIAGRAM 
TYPICAL IR AL = 
CRI TO CR4 ACRE SRO CRI, Porras 25356 REGULATED POWER SUPPLY 
свг-002020 SIS GROUND AN 
en M $e [MODELS LHI28,LHI28S,LHI28FM | 
LS LHI28,LHI28S,L 
Fores FOR LHI28FM ONLY WHT لا‎ = 
BASE = MODELS LHI28A, LH (28 A-S, LHI28A 
MITTER SMS ASIE 
у, TRANSISTOR, PIN VIEW 
EMITTER Q7 8 Q9 
TYPICAL TYPICAL TRANSISTOR, PIN VIEW 
CR8 CRY QIO THRU 015 
Ap NOTE LAMBDA 
5 | [ } "iECTROMICS com. 
TRANSISTOR TRANSISTOR, BOTTOM VIEW MELVILLE, L. L, NE! ٣ ! 
BOTTOM VIEW 01 TO 04,06 


95 


t 


TYPICAL 
CRS A Ся? 
FBL-00-043 


ti 


TYPICAL 
CRI TO CR4 8 CRE 
FBL-00-030 


(NOTE 5) 


d 


TYPICAL 
CR8 


SCB 128А 


NOTES 


RESISTOR VALUES ARE IN OHMS UNLESS OTHERWISE NOTED. 
RESISTOR WATTAGE 1/2 WATT; RESISTORS ABOVE 2 WATTS 
ARE WIREWOUND UNLESS OTHERWISE NOTED. 


RESISTOR TOLERANCES: COMPOSITION + 10%; WIREWOUND + 5 % 
UNLESS OTHERWISE NOTED. 


CAPACITOR TOLERANCES: ELEGTROLYTIC-10% + 100%; 


TANTALUM,-15% +75 %; PAPER, + 10%; CERAMIC, + 20%; MICA, +20%; 


MYLAR, 210%; UNLESS OTHERWISE NOTED. 
SYMBOLS: 

INDICATES CLOCKWISE ROTATION OF SHAFT. 
== INDICATES CONNECTION TO CHASSIS. 
© INDICATES ADJUSTMENT OR CALIBRATION CONTROL. 
لا‎ INDICATES ACTUAL UNIT MARKING. 
[__] INDICATES FRONT-PANEL MOUNTED COMPONENT. 
Ж INDICATES FACTORY ADJUSTMENT, SEE INSTRUCTION MANUAL. 
© INDICATES TRANSFORMER LUG TERMINAL. 
ېو‎ 


THIS DIODE IS LAMBDA PART NO.FBL-00-030; CAN 
BE REPLACED WITH STANDARD TYPE IN645 DIODE 
UNLESS OTHERWISE NOTED. 


CONDITIONS FOR CIRCUIT POINT VOLTAGE MEASUREMENTS. 
A. CONSTANT VOLTAGE 
READ ITALICIZED NUMBERS FOR CIRCUIT POINT 
VOLTAGES WHILE IN CONSTANT VOLTAGE OPERATION. 
INPUT: 120 VAC, 60 CPS. 
OUTPUT: 60 VOLTS, OUTPUT CURRENT ZERO. 


B. CONSTANT CURRENT 
READ NUMBERS IN PARENTHESES FOR CIRCUIT POINT 
VOLTAGES WHILE IN CONSTANT CURRENT OPERATION. 
INPUT: 120 VAC, 60 CPS, 30°C AMBIENT. 
OUTPUT: O VOLTS, OUTPUT CURRENT 2.4 AMPS (SHORT CIRCUIT). 
INDICATED VOLTAGES ARE TYPICAL VALUES AND ARE DC 
UNLESS OTHERWISE NOTED. 


DC MEASUREMENTS TAKEN WITH 20,000 OHMS /VOLT 
VOLTMETER BETWEEN —DC (TERM. 4) AND INDICATED POINTS 
UNLESS OTHERWISE NOTED. 


DESIGNATIONS ARE LAMBDA PART NUMBERS. 


INDICATES TERMINAL LOCATED ON TERMINAL BOARDS "А", 
"С" &"D" OR PRINTED WIRING BOARD "B". 


9. COAT BOTH SIDES OF MICA WASHER WITH 
DOW CORNING NO. 340 SILICONE GREASE. 
MICA 
INSULATING 
CAUTION pao: 
NOT AT CHASSIS GROUND POTENTIAL amid 
E — — | 
DO NOT SHORT TO CHASSIS GROUND а 
GROUND 
CRI4 THRU CR22 
Y | NOTE 9 
MICA 
TYPICAL = 
INSULATING 
CRIO,CRII, دوو مل‎ c. 
TRANSISTOR, PIN VIEW 
MITTER Q8 8 Q9 
TYPICAL TRANSISTOR, PIN VIEW 
CR9 QIO THRU 015 
8 7 
[ОЕ _ CO] 8 
5 E 
TRANSISTOR, TRANSISTOR, BOTTOM VIEW 
BOTTOM VIEW о! TO 04,06 


Q5 


Fl 


6.25 AMP 
TYPE 3AG 


"SLO-BLO" 


470%2% REFERENCE SUPPLY 


AUXILIARY 
RECTIFIER 


E [^ |] på | 
asi me C 7 SERIES (+9v) R5 1250 +1% 
H REGULATOR } ris @ RI4 "T 600+10% 2W,WW | 
500+1% 5к+0% жим 
+L SME Q6 2W,WW * 17 | 2 +60v 
FBN-LIO2 ۱٧ R6 в 
R23 R22 C7 150K < 
75 V SURGE 390 +5% +68v *67V +] 1MF CR6 
1W,FILM |2К%5% 95٧ (+8.5V) 35V RI3 
мг ° cl5 
оета TANE .0068MF CR2 
وم‎ RIS cie 200V,MYL, 
E 7.5 К +1% ATKt5* Ril 200V 
2W,WW Yo WFILM MYLAR 
(47) cro Q5 240MMF| 94 c4 
FBM-IN30298 | РВМ 04 +60V 1000V | Fen-Lioı Ё 470 MMF 
PREREGULATOR И ur, LT) ERA FBN-LIOI FBN-LIO3 300УМІСА 
5. 7 VOLTAGE uere 
AMPLIFIER 
+57V (9) Е USED сат (“2 (+.82V) <N R2 | 
سم‎ (17У) FBL-00-043 CURRENT FBL-00-043 er Ben 
FBL-00-036 CR8 LIMIT 35V,TANT R3 | COMPLEMENTARY gate 
٢ FBM-IN965B AMPLIFIER DIFFERENTIAL f MIU. 
330 AMPLIFIER + 
+60V 2.5MF =p 
GV) xL 100V, TANT 
y 2595] (т) | REAR OUTPUT 
623) TERMINALS 


== .۰م 
CURRENT LIMITER‏ 
MAX. RATINGS‏ 


SERIES 
REGULATOR 
FOR LHI28FM ONLY 
P| | 


Із 


(2) 
63,614 | 
02 MF 
125 УАС 
СЕВАМ!С | 


Qis 
FBN-35902 


FOR LHI28FM ONLY 


(+80.5\) 


FOR WIRING OF POWER SUPPLY 
FBN-35902 TO LOAD REFER TO POWER 


SUPPLY-TO-LOAD WIRING DIAGRAMS. 


DOTTED CONNECTIONS SHOWN O 
TBI INDICATE JUMPERS IN 
PLACE FOR `2 WIRE CONNECTION." | 


MAIN RECTIFIER 


FOR LHI28 A 
LHI28FM ONLY 


Q9 


FBN-35903 Lå 
Ө; EMITTER 
200V FOLLOWERS 
MYLAR 


Q8 FBN-35903 


SCHEMATIC DIAGRAM 
REGULATED POWER 


FOR LHI28FM ONLY 
CONSUME 
1 


Ge لس‎ Ce 
Ney سا‎ 


GPS FEN EG 
| مس د‎ sa 
K 


"m “ ‘bee! 
el чу Vi к 
"асе wil. on 
FH e itu 47 


4 A, 


å ñ £N 
uL E IU Te 


i 


We warrant each instrument manufactured by 
us, and sold by us or our authorized agents, to be 
free from defects in material and workmanship, and 
that it will perform within applicable specifications 

for a period of five years after original shipment. Our 
obligation under this guarantee is limited to repairing 
or replacing any instrument or part thereof, (except tubes 
and fuses) which shall, within five years after delivery to 
the original purchaser, be returned to us with transportation 
charges prepaid, prove after our examination to be thus defective. 


We reserve the right to discontinue instruments without notice, and 
to make modifications in design at any time without incurring any 
obligation to make such modifications to instruments previously sold. 


LA MB DA ELECTRONICS co 


515 BROAD HOLLOW ROAD + MELVILLE, L. L, NEW YORK + 516 MYRTLE 


1 


V 
A VANS - SUBSIDIAR Y 
CBE 


1 


395 5 es 
| å 54895 
т" | D rap 
| E 


bse 
€ 


iT